Baixe o app para aproveitar ainda mais
Prévia do material em texto
1 NRJED311332EN Energy Automation Network Protection & Automation Guide 695 Terminology APPENDIX A1 - 2 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 Introduction A A1 - 3 B A1 - 5 C A1 - 7 D A1 - 10 E A1 - 13 F A1 - 15 G A1 - 16 H A1 - 17 I A1 - 18 K A1 - 20 L A1 - 21 M A1 - 22 N A1 - 24 O A1 - 25 P A1 - 27 R A1 - 30 S A1 - 33 T A1 - 36 U A1 - 37 V A1 - 38 X A1 - 38 Z A1 - 38 The introduction of computer technology means that the Protection Engineer must now be familiar with a range of technical terms in this field, in addition to the terms long associated with Protection and Control. Below is a list of terms and their meanings that are now commonly encountered in the Protection and Control field. Contents A1 A1 A1 - 3NRJED311332EN Appendix 1 Terminology A1 A1 A AC Alternating Current ACB Air Circuit Breaker Accuracy The accuracy of a transducer is defined by the limits of intrinsic error and by the limits of variations. Accuracy class A number used to indicate the accuracy range of a measurement transducer, according to a defined standard. Active power (watt) transducer A transducer used for the measurement of active electrical power ADC Analogue to Digital Converter A/D Conversion The process of converting an analogue signal into an equivalent digital one, involving the use of an analogue to digital converter Adjustment The operation intended to bring a transducer into a state of performance suitable for its use AGC Automatic Gain Control AI Analogue Input AIS Air Insulated Switchgear Alarm An alarm is any event (see below) tagged as an alarm during the configuration phase All-or-nothing relay An electrical relay which is intended to be energised by a quantity, whose value is either higher than that at which it picks up or lower than that at which it drops out A1 - 4 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 A (cont.) Anti-pumping device A feature incorporated in a Circuit Breaker or reclosing scheme to prevent repeated operation where the closing impulse lasts longer than the sum of the relay and CB operating times AO Analogue Output AR Auto Reclose: A function associated with CB, implemented to carry out reclosure automatically to try to clear a transient fault ARBITER Proprietary protocol for time synchronisation from ARBITER Systems, Inc. Paso Robles, California USA Arcing time The time between instant of separation of the CB contacts and the instant of arc extinction Auto-transformer A power transformer that does not provide galvanic isolation between primary and secondary windings AUX Auxiliary Auxiliary circuit A circuit which is usually energised by the auxiliary supply but is sometimes energised by the measured quantity Auxiliary relay An all-or-nothing relay energised via another relay, for example a measuring relay, for the purpose of providing higher rated contacts, or introducing a time delay, or providing multiple outputs from a single input. Auxiliary supply An a.c. or d.c. electrical supply other than the measured quantity which is necessary for the correct operation of the transducer AVR Automatic Voltage Regulator A1 A1 A1 - 5NRJED311332EN Appendix 1 Terminology A1 A1 B Back-up protection A protection system intended to supplement the main protection in case the latter should be ineffective, or to deal with faults in those parts of the power system that are not readily included in the operating zones of the main protection Bay Set of LV, MV, or HV plant and devices, usually controlled by a bay computer BC Bay Computer. Computer dedicated to the control of one or several bays within a substation BCD Binary Coded Decimal BCP Bay Control Point. A local keypad at bay level to control the elements of a single bay Biased relay A relay in which the characteristics are modified by the introduction of some quantity other than the actuating quantity, and which is usually in opposition to the actuating quantity Bias current The current used as a bias quantity in a biased relay BIOS Basic Input/Output System (of a computer or microprocessor) BT Booster Transformer SESA214753 Note Marked définie par SESA214753 A1 - 6 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 B (cont.) Booster Transformer A current transformer whose primary winding is in series with the catenary and secondary winding in the return conductor of a classically-fed a.c. overhead electrified railway. Used at intervals to ensure that stray traction return currents, with their potential to cause interference in nearby communication circuits, are minimised Burden The loading imposed by the circuits of the relay on the energising power source or sources, expressed as the product of voltage and current (volt-amperes, or watts if d.c.) for a given condition, which may be either at ‘setting’ or at rated current or voltage. The rated output of measuring transformers, expressed in VA, is always at rated current or voltage and it is important, in assessing the burden imposed by a relay, to ensure that the value of burden at rated current is used A1 A1 A1 - 7NRJED311332EN Appendix 1 Terminology A1 A1 C C Capacitance CAD Computer Aided Design Calibration The set of operations which establish, under specified conditions, the relationship between values indicated by a transducer and the corresponding values of a quantity realized by a reference standard. (This should not be confused with ‘adjustment’, q.v.) CB Circuit Breaker CBC Compact Bay Controller. Small capacity bay computer for Medium Voltage applications CBCT Core Balance Current Transformer CCR Central Control Room CDM Conceptual Data Modelling is an activity whose aims are: • to define objects and links and naming conventions for their identifications • to guarantee interoperability between subsystems • to define standard exchange formats between system configurator and subsystem configurators Characteristic angle The angle between the vectors representing two of the energising quantities applied to a relay and used for the declaration of the performance of the relay A1 - 8 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 C (cont.) Characteristic curve The curve showing the operating value of the characteristic quantity corresponding to various values or combinations of the energising quantities Characteristic Impedance Ratio (C.I.R.) The maximum value of the System Impedance Ratio up to which the relay performance remains within the prescribed limits of accuracy Characteristic quantity A quantity, the value of which characterises the operation of the relay, for example, current for an overcurrent relay, voltage for a voltage relay, phase angle for a directional relay, time for an independent time delay relay, impedance for an impedance relay Check protection system An auxiliary protection system intended to prevent tripping due to inadvertent operation of the main protection system CHP Combined Heat and Power Circuit insulation voltage The highest circuit voltage to earth on which a circuit of a transducer may be used and which determines its voltage test Class index The number which designates the accuracy class Closing Impulse time The time during which a closing impulse is given to the CB Closing Time The time for a CB to close, from the time of energisation of the closing circuit to making of the CB contacts A1 A1 A1 - 9NRJED311332ENAppendix 1 Terminology A1 A1 C (cont.) Compliance voltage (accuracy limiting output voltage) For current output signals only, the output voltage up to which the transducer meets its accuracy specification Conjunctive test A test of a protection system including all relevant components and ancillary equipment appropriately interconnected. The test may be parametric or specific Conversion coefficient The relationship of the value of the measurand to the corresponding value of the output Core Balance Current Transformer A ring-type Current Transformer in which all primary conductors are passed through the aperture of the CBCT. Hence the secondary current is proportional only to any imbalance in current. Used for sensitive earth-fault protection Counting Relay A relay that counts the number of times it is energised and actuates an output after a desired count has been reached. CSV Character (or Comma) Separated Values format. A widely used format for the exchange of data between different software, in which the individual data items a separated by a known character – usually a comma CT Current Transformer Current transducer A transducer used for the measurement of a.c. current CVT Capacitor Voltage Transformer. A voltage transformer that uses capacitors to obtain a voltage divider effect. Used at EHV voltages instead of an electromagnetic VT for size/cost reasons A1 - 10 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 D DAC Digital to Analogue Converter DAR Delayed auto-reclose DAT Digital Audio Tape DBMS Data Base Management system DCF77 LF transmitter located at Mainflingen, Germany, broadcasting a time signal on a 77.5kHz frequency DCP Device Control Point: local keypad on device level to control the switchgear, often combined with local/remote switch DCS Distributed Control System Dead Time (auto- reclose) The time between the fault arc being extinguished and the CB contacts re- making De-ionisation time (auto-reclose) The time required for dispersion of ionised air after a fault is cleared so that the arc will not re-strike on re-energisation Delayed Auto- Reclose An auto-reclosing scheme which has a time delay in excess of the minimum required for successful operation SESA214753 Note Marked définie par SESA214753 A1 A1 A1 - 11NRJED311332EN Appendix 1 Terminology A1 A1 D (cont.) Dependent time measuring relay A measuring relay for which times depend, in a specified manner, on the value of the characteristic quantity DFT Discrete Fourier Transform Digital Signal Processor A microprocessor optimised in both hardware architecture and software instruction set for the processing of analogue signals digitally, through use of the DFT and similar techniques Digital Signal Processing A technique for the processing of digital signals by various filter algorithms to obtain some desired characteristics in the output. The input signal to the processing algorithm is usually the digital representation of an analogue signal, obtained by A/D conversion Directional relay A protection relay in which the tripping decision is dependent in part upon the direction in which the measured quantity is flowing Discrimination The ability of a protection system to distinguish between power system conditions for which it is intended to operate and those for which it is not intended to operate Distortion factor The ratio of the r.m.s. value of the harmonic content to the r.m.s. value of the non- sinusoidal quantity DNP Distributed Network Protocol. A proprietary communication protocol used on secondary networks between HMI, substation computers or Bay Computers and protective devices A1 - 12 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 D (cont.) DOL Direct-on-Line Direct-on-Line A method of motor starting, in which full line voltage is applied to a stationary motor Drop-out (or drop-off) A relay drops out when it moves from the energised position to the un-energised position Drop-out/pick-up ratio The ratio of the limiting values of the characteristic quantity at which the relay resets and operates. This value is sometimes called the differential of the relay DSP Digital Signal Processing DT Definite time A1 A1 A1 - 13NRJED311332EN Appendix 1 Terminology A1 A1 E Earth fault protection system A protection system which is designed to respond only to faults to earth Earthing transformer A three-phase transformer intended essentially to provide a neutral point to a power system for the purpose of earthing Effective range The range of values of the characteristic quantity or quantities, or of the energising quantities to which the relay will respond and satisfy the requirements concerning it, in particular those concerning precision Effective setting The ‘setting’ of a protection system including the effects of current transformers. The effective setting can be expressed in terms of primary current or secondary current from the current transformers and is so designated as appropriate Electrical relay A device designed to produce sudden predetermined changes in one or more electrical circuits after the appearance of certain conditions in the electrical circuit or circuits controlling it NOTE: The term ‘relay’ includes all the ancillary equipment calibrated with the device Electromechanical relay An electrical relay in which the designed response is developed by the relative movement of mechanical elements under the action of a current in the input circuit EMC Electro-Magnetic Compatibility Embedded generation Generation that is connected to a distribution system (possibly at LV instead of HV) and hence poses particular problems in respect of electrical protection A1 - 14 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 E (cont.) e.m.f. Electro-motive Force ( or voltage) Energising quantity The electrical quantity, either current or voltage, which along or in combination with other energising quantities, must be applied to the relay to cause it to function EPROM Electrically Programmable Read Only Memory Error (of a transducer) The actual value of the output minus the intended value of the output, expressed algebraically Event An event is any information acquired or produced by the digital control system A1 A1 A1 - 15NRJED311332EN Appendix 1 Terminology A1 A1 F FAT Factory Acceptance Test. Validation procedures witnessed by the customer at the factory Fault Passage Indicator A sensor that detects the passage of current in excess of a set value (i.e. current due to a fault) at the location of the sensor. Hence, it indicates that the fault lies downstream of the sensor FBD Functional Block Diagram: One of the IEC 61131-3 programming languages Fiducial value A clearly specified value to which reference is made in order to specify the accuracy of a transducer. (For transducers, the fiducial value is the span, except for transducers having a reversible and symmetrical output when the fiducial value may be either the span or half the span as specified by the manufacturer. It is still common practice, however, for statements of accuracy for frequency transducers to refer to ‘percent of centre-scale frequency’ and, for phase angle transducers, to an error in electrical degrees.) FPI Fault Passage Indicator Frequency transducer A transducer used for the measurement of the frequency of an a.c. electrical quantity Full duplex communications A communications system in which data cantravel simultaneously in both directions A1 - 16 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 G Gateway The Gateway is a computer which provides interfaces between the local computer system and one or several SCADA (or RCC) systems GIS Gas Insulated Switchgear (usually SF6) Global Positioning System A system used for locating objects on Earth precisely, using a system of satellites in geostationary orbit in Space. Used by some numerical relays to obtain accurate time information GMT Greenwich Mean Time GPS Global Positioning System GTO Gate Turn-off Thyristor SESA214753 Note Marked définie par SESA214753 SESA214753 Note Marked définie par SESA214753 A1 A1 A1 - 17NRJED311332EN Appendix 1 Terminology A1 A1 H Half- duplex communications A communications system in which data can travel in both directions, but only in one direction at a time High-speed reclosing A reclosing scheme where re-closure is carried out without any time delay other than that required for de-ionisation, etc. HMI Human Machine Interface. The means by which a human inputs data to and receives data from a computer-based system. Usually takes the form of a Personal Computer (PC) (desktop or portable) with keyboard, screen and pointing device HRC High Rupturing Capacity (applicable to fuses) HSR High Speed Reclosing HV High Voltage HVDC High Voltage Direct Current A1 - 18 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 I I Current ICCP Term used for IEC 60870-6-603 protocol ICT Interposing Current Transformer (software implemented) I.D.M.T. Inverse Definite Minimum Time IGBT Insulated Gate Bipolar Transistor I/O Input/Output IED Intelligent Electronic Device. Equipment containing a microprocessor and software used to implement one or more functions in relation to an item of electrical equipment (e.g. a bay controller, remote SCADA interface/protocol converter). A microprocessor-based numerical relay is also an IED. IED is a generic term used to describe any microprocessor-based equipment, apart from a computer IGBT Insulated Gate Bipolar Transistor Independent time measuring relay A measuring relay, the specified time for which can be considered as being independent, within specified limits, of the value of the characteristic quantity Influence quantity A quantity which is not the subject of the measurement but which influences the value of the output signal for a constant value of the measurand SESA214753 Note Marked définie par SESA214753 SESA214753 Note Marked définie par SESA214753 A1 A1 A1 - 19NRJED311332EN Appendix 1 Terminology A1 A1 I (cont.) Input quantity The quantity, or one of the quantities, which constitute the signals received by the transducer from the measured system Instantaneous relay A relay that operates and resets with no intentional time delay. NOTE: All relays require some time to operate; it is possible, within the above definition, to discuss the operating time characteristics of an instantaneous relay Insulated Gate Bipolar Transistor A special design of transistor that is suitable for handling high voltages and currents (relative to an ordinary transistor). Frequently used in static power control equipment (inverters, controlled rectifiers, etc) due to the flexibility of control of the output Intrinsic error An error determined when the transducer is under reference conditions Inverse time delay relay A dependent time delay relay having an operating time which is an inverse function of the electrical characteristic quantity Inverse time relay with definite minimum time (I.D.M.T.) An inverse time relay having an operating time that tends towards a minimum value with increasing values of the electrical characteristic quantity IRIG-B An international standard for time synchronisation ISO International Standards Organisation A1 - 20 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 K K-bus (K-bus Courier) Term used for the Courier protocol on K-Bus interface for K-Relay range manufactured by AREVA Knee-point e.m.f. That sinusoidal e.m.f. applied to the secondary terminals of a current transformer, which, when increased by 10%, causes the exciting current to increase by 50% A1 A1 A1 - 21NRJED311332EN Appendix 1 Terminology A1 A1 L L Inductance LAN Local Area Network LCD Liquid Crystal Display LED Light Emitting Diode LD Ladder Diagram. One of the IEC 61131-3 programming languages LDC Line drop compensator Limiting value of the output current The upper limit of output current which cannot, by design, be exceeded under any conditions Local Control Mode When set for a given control point it means that the commands can be issued from this point Lock-out (auto-reclose) Prevention of a CB reclosing after tripping Long-term stability The stability over a period of one year Low-speed auto-reclose See Delayed Auto-Reclose LV Low Voltage A1 - 22 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 M Main protection The protection system which is normally expected to operate in response to a fault in the protected zone Maximum permissible values of the input current and voltage Values of current and voltage assigned by the manufacturer which the transducer will withstand indefinitely without damage MCB Miniature Circuit Breaker MCCB Moulded Case Circuit Breaker Mean-sensing transducer A transducer which actually measures the mean (average) value of the input waveform but which is adjusted to give an output corresponding to the r.m.s. value of the input when that input is sinusoidal Measurand A quantity subjected to measurement Measuring element A unit or module of a transducer which converts the measurand, or part of the measurand, into a corresponding signal Measuring range That part of the span where the performance complies with the accuracy requirements Measuring relay An electrical relay intended to switch when its characteristic quantity, under specified conditions and with a specified accuracy attains its operating value Metering (non-tariff) Values computed depending on the values of digital or analogue inputs during variable periods A1 A1 A1 - 23NRJED311332EN Appendix 1 Terminology A1 A1 M (cont.) Metering (tariff) Energy values computed from digital and/ or analogue inputs during variable periods and dedicated to energy measurement for billing (tariff) purposes Mid Point Sectioning Substation A substation located at the electrical interface of two sections of electrified railway. It contains provision for the coupling of the sections electrically in the event of loss of supply to one section ModBus Proprietary communication protocol used on secondary networks between HMI, substation computers or Bay Computers and protective devices MPSS Mid Point Sectioning Substation (electrified railways) Multi-element transducer A transducer having two or more measuring elements. The signals from the individual elements are combined to produce an output signal corresponding to the measurand Multi-section transducer A transducer having two or more independent measuring circuits for one or more functions Multi-shot reclosing A reclosing scheme that permits more than one reclosing operation of a CB after a fault occurs before lock-out occurs MV Medium Voltage A1 - 24 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 N N/C Normally Closed N/O Normally Open Nominal range of use A specified range of values which it isintended that an influence quantity can assume without the output signal of the transducer changing by amounts in excess of those specified Notching relay A relay which switches in response to a specific number of applied impulses NPS Negative Phase Sequence NS Neutral Section (electrified railways) Numerical relay A protection relay which utilises a Digital Signal Processor to execute the protection algorithms in software A1 A1 A1 - 25NRJED311332EN Appendix 1 Terminology A1 A1 O OCB Oil Circuit Breaker Off-Load Tap Changer A tap changer that is not designed for operation while the transformer is supplying load OHL Overhead line OLTC On Load Tap Changer. On Load Tap Changer A tap changer that can be operated while the transformer is supplying load. Opening time The time between energisation of a CB trip coil and the instant of contact parting Operating current (of a relay) The current at which a relay will pick up Operating time (CB) The time between energisation of a CB trip coil and arc extinction Operating time (relay) With a relay de-energised and in its initial condition, the time which elapses between the application of a characteristic quantity and the instant when the relay operates Operating time characteristic The curve depicting the relationship between different values of the characteristic quantity applied to a relay and the corresponding values of operating time Operating value The limiting value of the characteristic quantity at which the relay actually operates Optical Ground Wire – a ground wire that includes optical fibres to provide a communications link SESA214753 Note Marked définie par SESA214753 A1 - 26 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 O (cont.) OSI 7-layer model The Open Systems Interconnection 7-layer model is a model developed by ISO for modelling of a communications network. Output common mode interference voltage An unwanted alternating voltage which exists between each of the output terminals and a reference point Output current (of a transducer) The current produced by the transducer which is an analogue function of the measurand Output load The total effective resistance of the circuits and apparatus connected externally across the output terminals Output power (of a transducer) The power available at the transducer output terminals Output series mode interference voltage An unwanted alternating voltage appearing in series between the output terminals and the load Output signal An analogue or digital representation of the measurand Output span (span) The algebraic difference between the lower and upper nominal values of the output signal Overcurrent relay A protection relay whose tripping decision is related to the degree by which the measured current exceeds a set value. Overshoot time The overshoot time is the difference between the operating time of the relay at a specified value of the input energising quantity and the maximum duration of the value of input energising quantity which, when suddenly reduced to a specific value below the operating level, is insufficient to cause operation SESA214753 Note Marked définie par SESA214753 SESA214753 Note Marked définie par SESA214753 A1 A1 A1 - 27NRJED311332EN Appendix 1 Terminology A1 A1 P Parametric conjunctive test A conjunctive test that ascertains the range of values of each parameter for which the test meets specific performance requirements PCB Printed Circuit Board PCC Point of Common Coupling PED Power Electronic Device Phase angle transducer A transducer used for the measurement of the phase angle between two a.c. electrical quantities having the same frequency Pick-up A relay is said to ‘pick-up’ when it changes from the de-energised position to the energised position Pilot channel A means of interconnection between relaying points for the purpose of protection PLC Programmable Logic Controller. A specialised computer for implementing control sequences using software PLCC Power Line Carrier Communication Point of Common Coupling The interface between an in-plant network containing embedded generation and the utility distribution network to which the in-plant network is connected POW Point-on- Wave. Point-on-wave switching is the process to control moment of switching to minimise the effects (inrush currents, overvoltages) A1 - 28 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 P (cont.) Power Electronic Device An electronic device (e.g. thyristor or IGBT) or assembly of such devices (e.g. inverter). Typically used in a power transmission system to provide smooth control of output of an item of plant Power factor The factor by which it is necessary to multiply the product of the voltage and current to obtain the active power Power Line Carrier Communication A mean of transmitting information over a power transmission line by using a cariier fraquency superimpozed on the normal power frequency. PPS Positive Phase Sequence Protected zone The portion of a power system protected by a given protection system or a part of that protection system Protection equipment The apparatus, including protection relays, transformers and ancillary equipment, for use in a protection system Protection relay A relay designed to initiate disconnection of a part of an electrical installation or to operate a warning signal, in the case of a fault or other abnormal condition in the installation. A protection relay may include more than one electrical element and accessories Protection scheme The co-ordinated arrangements for the protection of one or more elements of a power system. A protection scheme may comprise several protection systems Protection system A combination of protection equipment designed to secure, under predetermined conditions, usually abnormal, the disconnection of an element of a power system, or to give an alarm signal, or both SESA214753 Note Marked définie par SESA214753 A1 A1 A1 - 29NRJED311332EN Appendix 1 Terminology A1 A1 P (cont.) Protocol A set of rules that define the method in which a function is carried out – commonly used in respect of communications links, where it defines the hardware and software features necessary for successful communication between devices. PSM Plug Setting Multiple – a term used in conjunction with electromechanical relays, denoting the ratio of the fault current to the current setting of the relay PSTN Public Switched Telephone Network PT100 Platinum resistance temperature probe A1 - 30 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 R R Resistance R.M.S.-sensing transducer A transducer specifically designed to respond to the true r.m.s. value of the input and which is characterised by the manufacturer for use on a specified range of waveforms Ratio correction A feature of digital/numerical relays that enables compensation to be carried out for a CT or VT ratio that is not ideal Rating The nominal value of an energising quantity that appears in the designation of a relay. The nominal value usually corresponds to the CT and VT secondary ratings RCD Residual Current Device. A protection device which is actuated by the residual current RCP Remote Control Point. The Remote Control Point is a SCADA interface. Several RCP’s may be managed with different communication protocols. Physical connections are done at a Gateway or at substation computers or at a substation HMI Reactive power (var) transducer A transducer used forthe measurement of reactive electrical power Reclaim time (auto- reclose) The time between a successful closing operation, measured from the time the auto-reclose relay closing contact makes until a further reclosing sequence is permitted in the event of a further fault occurring SESA214753 Note Marked définie par SESA214753 SESA214753 Note Marked définie par SESA214753 A1 A1 A1 - 31NRJED311332EN Appendix 1 Terminology A1 A1 R (cont.) REF Restricted Earth Fault Reference conditions Conditions of use for a transducer prescribed for performance testing, or to ensure valid comparison of results of measurement Reference range A specified range of values of an influence quantity within which the transducer complies with the requirements concerning intrinsic errors Reference value A specified single value of an influence quantity at which the transducer complies with the requirements concerning intrinsic errors Relay See Protection relay Resetting value The limiting value of the characteristic quantity at which the relay returns to its initial position Residual current The algebraic sum, in a multi-phase system, of all the line currents Residual voltage The algebraic sum, in a multi-phase system, of all the line-to-earth voltages Response time The time from the instant of application of a specified change of the measurand until the output signal reaches and remains at its final steady value or within a specified band centred on this value Reversible output current An output current which reverses polarity in response to a change of sign or direction of the measurand A1 - 32 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 R (cont.) Ripple content of the output With steady-state input conditions, the peak-to-peak value of the fluctuating component of the output r.m.s. Root Mean Square RMU Ring Main Unit ROCOF Rate Of Change Of Frequency (protection relay) RSVC Relocatable Static Var Compensator RTD Resistance Temperature Detector RTOS Real Time Operating System RTU Remote Terminal Unit. An IED used specifically for interfacing between a computer and other devices. Sometimes may include control/monitoring/storage functions A1 A1 A1 - 33NRJED311332EN Appendix 1 Terminology A1 A1 S SAT Site Acceptance Test. Validation procedures for equipment executed with the customer on site SCADA Supervisory Control and Data Acquisition SCL Substation Configuration Language. Normalised configuration language for substation modelling (as expected by IEC 61850-6) SCP Substation Control Point. HMI computers at substation level allowing the operators to control the substation SCS Substation Control System Setting The limiting value of a ‘characteristic’ or ‘energising’ quantity at which the relay is designed to operate under specified conditions. Such values are usually marked on the relay and may be expressed as direct values, percentages of rated values, or multiples SFC Sequential Function Chart: One of the IEC 61131-3 programming languages Short-term stability The stability over a period of 24 hours Simplex communications system A communications system in which data can only travel in one direction Single-shot reclosing An auto-reclose sequence that provides only one reclosing operation, lock-out of the CB occurring if it subsequently trips S.I.R. System Impedance Ratio Single element transducer A transducer having one measuring element A1 - 34 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 S (cont.) SOE Sequence Of Events SOTF Switch on to Fault (protection) Specific conjunctive test A conjunctive test using specific values of each of the parameters Spring winding time For spring-closed CB’s, the time for the spring to be fully charged after a closing operation ST Structured Text: One of the IEC 61131-3 programming languages Stability (of a transducer) The ability of a transducer to keep its performance characteristics unchanged during a specified time, all conditions remaining constant Stability (of a protection system) The quantity whereby a protection system remains inoperative under all conditions other than those for which it is specifically designed to operate Stability limits (of a protection system) The r.m.s. value of the symmetrical component of the through fault current up to which the protection system remains stable Starting relay A unit relay which responds to abnormal conditions and initiates the operation of other elements of the protection system STATCOM A particular type of Static Var Compensator, in which Power Electronic Devices such as GTO’s are used to generate the reactive power required, rather than capacitors and inductors A1 A1 A1 - 35NRJED311332EN Appendix 1 Terminology A1 A1 S (cont.) Static relay An electrical relay in which the designed response is developed by electronic, magnetic, optical or other components without mechanical motion. Excludes relays using digital/numeric technology Static Var Compensator A device that supplies or consumes reactive power, comprised solely of static equipment. It is shunt-connected on transmission lines to provide reactive power compensation STC Short Time Current (rating of a CT) Storage conditions The conditions, defined by means of ranges of the influence quantities, such as temperature, or any special conditions, within which the transducer may be stored (non-operating) without damage SVC Static Var Compensator System disturbance time (auto-reclose) The time between fault inception and CB contacts making on successful re-closure System impedance ratio The ratio of the power system source impedance to the impedance of the protected zone A1 - 36 NRJED311332EN Appendix 1 Terminology A1 A1A1 A1 T T101 Term used for IEC 60870-5-101 protocol Tap changer A mechanism, usually fitted to the primary winding of a transformer, to alter the turns ratio of the transformer by small discrete amounts over a defined range TCP/IP Transmission Control Protocol/Internet Protocol. A common protocol for the transmission of messages over the Internet TCS Trip Circuit Supervision TC57 Technical Committee 57 working for the IEC and responsible for producing standards in the field of Protection (e.g. IEC 61850) TF a) Transfer Function of a device (usually an element of a control system b) Transient Factor (of a CT) Through fault current The current flowing through a protected zone to a fault beyond that zone Time delay A delay intentionally introduced into the operation of a relay system Time delay relay A relay having an intentional delaying device TPI Tap Position Indicator (for transformers) Transducer (electrical measuring transducer) A device that provides a d.c. output quantity having a definite relationship to the a.c. measurand Transducer with offset zero (live zero) A transducer which gives a predetermined output other than zero when the measurand is zero Transducer with suppressed zero A transducer whose output is zero when the measurand is less than a certain value A1 A1 A1 - 37NRJED311332EN Appendix 1 Terminology A1 A1 U Unit electrical relay A single relay that can be used alone or in combinations with others Unit protection A protection system that is designed to operate only for abnormal conditions within a clearly defined zone of the power system Unrestricted protection A protection system which has no clearly defined zone of operation and which achieves selective operation onlyby time grading UCA Utility Communications Architecture UPS Uninterruptible Power Supply UTC Universal Time Coordinates A1 - 38 NRJED311332EN Appendix 1 Terminology A1 A1 V / X / Z V Voltage VCB Vacuum Circuit Breaker VDEW Term used for IEC 60870-5-103 protocol. The VDEW protocol is a subset of the IEC 60870-5-103 protocol Vector group compensation A feature of digital and numerical relays that compensates for the phase angle shift that occurs in transformers (including VT’s) due to use of dissimilar winding connections – e.g. transformers connected delta/star Voltage transducer A transducer used for the measurement of a.c. voltage VT Voltage Transformer X Reactance Z Impedance
Compartilhar