Vista previa del material en texto
1 SEALED WINDING CONFORMANCE TESTING AND RECENT REVISIONS TO NEMA MG-1 Copyright Material IEEE Paper No. PCIC-2007-14 Meredith K. W. Stranges Bharat Mistry Ramtin Omranipour Member, IEEE Member, IEEE Member, IEEE GE Consumer & Industrial GE Consumer & Industrial GE Consumer & Industrial 107 Park St. N. 107 Park St. N. 107 Park St. N. Peterborough, ON K9J 7B5 Peterborough, ON K9J 7B5 Peterborough, ON K9J 7B5 Canada Canada Canada meredith.stranges@ge.com bharat.mistry@ge.com ramtin.omranipour@ge.com Abstract - The sealed winding conformance test is often performed during the final acceptance test sequence for industrial motor stator insulation. The stator winding is first completely soaked with water, then receives a 10-minute insulation resistance (IR10) measurement, followed by a 60- second high potential (hipot) test at 1.15 times rated line-to- line voltage (VLL). A 1-minute insulation resistance (IR1) test is performed immediately after the hi-pot test. To define the test requirement, API 541 and 546 standards reference NEMA MG-1 20.18, which specifies an acceptance criterion for both IR measurements of (MΩ) ≥ VLL + 1, where [VLL + 1] is in kV. NEMA MG-1 20.18 refers to IEEE Std 43 for the insulation resistance test method and minimum insulation resistance. Until its most recent revision, IEEE Std 43 recommended the minimum IR1 (MΩ) ≥ VLL + 1 (kV). However, the current version of IEEE Std 43 (2000) recommends IR1 ≥ 100 MΩ for all stator windings built after about 1970. Modern epoxy-mica insulation systems should be able to meet this value when fully clean and dry. The wet conditions encountered during sealed winding tests may produce a different response in the insulation system. The sealed winding test is outside the scope of IEEE 43. The next revision of NEMA MG-1 20.18 will clarify the sealed winding test acceptance level of IR (MΩ) ≥ VLL + 1 (kV). This paper investigates the effect of test solution conductivity on the IR measurement, provides the NEMA-approved clarification of the sealed winding test specification and suggests further clarifications to the sealed winding test procedure. Index Terms — Sealed winding test, insulation resistance, hipot, stator winding. I. INTRODUCTION A. Purpose of Sealed Winding Test The sealed winding conformance test verifies that a form- wound stator can be energized in a very humid atmosphere without danger of winding failure. It uses insulation resistance (IR) to confirm that the complete insulation system, including the endwinding, is sealed. The principal benefit of the sealed winding conformance test is its ability to detect moisture- sensitive defects in the winding of a machine, particularly in the connections. If the phase connections, pole jumpers, and circuit rings are not adequately sealed, test failure is likely. Other test regimens employ condition-based monitoring to evaluate insulation performance trends for a specific installed machine [1, 2], or to assure the reliability of system design [3, 4, 5]. A high IR value alone does not prove the quality of the insulation, nor does it guarantee its long-term performance in operation. The sealed winding conformance test is customer- specified and generally applied to open machines. Examples include open drip-proof (ODP), and weather-protected (WP) units operating in wet, dirty and chemically corrosive conditions. The sealed winding test can also prove a sealed system on totally enclosed machines equipped with water-air or air-air coolers (TEWAC or TEAAC). B. Test Procedure The sealed winding test uses IR and hipot testing as acceptance criteria. NEMA MG-1 [6] provides the sealed winding test procedure and IR acceptance criterion. IEEE Std 43 [7] explains the theory and method for the IR test. All exposed areas of the stator winding must be completely soaked with water of specified surface tension. This can be done either by immersion of the entire stator, or by thoroughly spraying the stator while it is held in a test fixture; the methods are considered interchangeable. Stator windings that cannot be submerged must be sprayed for thirty minutes. NEMA MG-1 does not specify the wet test solution conductivity, although it provides a maximum surface tension. The soaked stator winding receives a 500-V dc IR test. The measurements are taken after applying the dc voltage for one minute (IR1), then every minute thereafter for a total duration of 10 minutes. The insulation resistance at 10 minutes (IR10) in MΩ must be at least VLL + 1 (kV). The winding is hipot tested at 1.15 times VLL. The IR1 taken following the hipot test must also meet the minimum value of VLL + 1 (kV). This paper presents data for stators tested using solutions of different conductivities. The clarification of the NEMA MG-1 acceptance criterion is also discussed, along with some further ideas regarding the interpretation of the sealed winding test. 2 II. SEALED WINDING TEST A. Effect of Solution Conductivity Three stator windings rated 13.8 kV were subjected to the sealed winding conformance test, using solutions of different conductivities. The intent was to determine the effect of varying the solution electrical conductivity on the insulation resistance values measured during the sealed winding test. The solutions chosen were deionized (DI) water, a mixture of DI and tap water, and tap water alone. A precipitation rate of 5 ± 0.5 mm/min was used, according to the recommended value for the wet test parameter [8]. A surfactant was added to each solution to reduce the surface tension to less than the value specified in NEMA MG-1. Table 1 shows the tested properties of each solution. The solution conductivity for test B was recommended by [8]. Fig. 3 shows a stator prepared for its spray test. Shown are the connection end of the stator and the spray nozzles. Test solutions were applied in order of lowest to highest conductivity. The stator was not dried between the tests. Sufficient time was allowed between successive tests so that the absorption current levels would not be influenced by the prior test. Figs 4 to 6 show values of IR vs. time for the subject stators, corrected to 40°C. TABLE 1. PROPERTIES OF AQUEOUS SPRAY TEST SOLUTIONS Stator Test Solution Surface Tension (dyn/cm, at 25°C) Conductivity (mS/m, at 20°C) A DI Water 22 3.0 B DI + Tap Water 25 5.0 1 C Tap Water 28 19.3 A DI Water 30 1.0 B DI + Tap Water 25 5.0 2 C Tap Water 30 19.2 A DI Water 30 2.2 B DI + Tap Water 26 5.9 3 C Tap Water 29 19.8 Fig. 3: A 13.8 kV stator prepared for spray testing Fig. 4: Insulation resistance for stator 1 during the spray test, using solutions of different electrical conductivity Fig. 5: Insulation resistance for stator 2 during the spray test, using solutions of different electrical conductivity 0 5 10 15 20 25 30 35 40 0 2 4 6 8 10 12 Time (minute) IR (G oh m s) Test A Test B Test C 0 5 10 15 20 0 2 4 6 8 10 12 Time (minute) IR (G oh m s) Test A Test B Test C 0 5 10 15 20 0 2 4 6 8 10 12 Time (minute) IR (G oh m s) Test A Test B Test C 3 Fig. 6: Insulation resistance for stator 3 during the spray test, using solutions of different electrical conductivity III. DISCUSSION A. Spray-testing Experiments Insulation resistance is the quotient of the applied direct voltage across the insulation divided by the total resultant current at a given time. The total resultant current is the sum of four different currents: surface leakage, geometric capacitance, conductance, and absorption [7]. When the direct voltage is applied to the stator winding of rotating machines, the geometric capacitance current decays to zero within a few seconds and the IR increases rapidly. The increase continues at a lower rate as the absorption current decays. The conductance and surfaceleakage currents remain constant through the IR test. For modern epoxy insulation systems, the conductance current is very small. The value of the surface leakage current depends on the condition of the stator winding and the length of the leakage path. During the sealed winding test, the stator winding is soaked with the water; this can create high surface leakage current, resulting in low IR. This is especially true for stator windings with relatively small clearances and short endwindings. Insulation resistance depends on the design of the particular winding; end arm length, coil-to-coil and phase-to- phase clearances, length of grading material and voltage rating all play a role. The voltage distribution over the endwinding of a dry stator varies depending on location along the coil end arms. During the sealed winding test, the distribution of moisture over the end winding and connections ensures that the entire winding is maintained at common ground potential while the dc- and ac test voltages are applied [9]. The results of the spray test using different solutions suggest that the solution conductivity did not significantly affect the IR. Values in the GΩ range indicate that the stator windings were sealed. Stators 1 & 3 had similar endwinding geometry and showed similar IR values. The endwinding geometry of stator 2 differed from that of the other two units, and it had less coils than the other units. It is curious that the measured IR values for the test with DI water were less than the other two tests. One possible explanation is the presence of minor contamination on the stators endwindings that was washed off during the first test. B. Test Standards The 2006 revision of NEMA MG-1 is vague, because it requires spray tested stators to have IR (MΩ) ≥ VLL + 1 (kV), and references IEEE Std 43 for IR acceptance criteria. The intent of the reference to IEEE 43 is simply to establish a test method, but its 2000 revision recommends IR1 ≥ 100 MΩ for all stators with modern epoxy-mica insulation systems. Previous versions of IEEE 43 recommended IR1 (MΩ) ≥ VLL + 1 (kV). The reference to the capability of modern systems to meet a higher IR value does not consider the sealed winding test. It should be noted that IEEE 43 cautions the reader about the limited information offered by the IR test, and that the observed values can be affected by even a small degree of moisture. The unintentionally conflicting statement in NEMA MG-1 offering two distinct acceptance criteria creates a potential confusion for the reader. The clarification as approved by the committee for NEMA MG-1 says: “a) After the spray test: Using 500 V dc, take a 10-minute insulation resistance measurement, following the procedure as outlined in IEEE 43. The minimum insulation resistance in megohms shall be machine rated kilovolts plus 1. b) After the 60Hz, 1.15 times rated voltage hi-potential test: Using 500 V dc, take a 1-minute insulation resistance measurement, following the procedure as outlined in IEEE 43. The minimum insulation resistance in megohms shall be machine rated kilovolts plus 1.” Although NEMA MG-1 calls for a 30-minute spraying time on the winding, it is not clear whether the initial IR measurement should be taken after the half-hour of spraying is complete, or if the ten minutes of IR measurements may begin after twenty minutes of spraying. NEMA MG-1 does not specify the aqueous solution conductivity. IV. CONCLUSIONS The sealed winding conformance test is a brief and superficial check of the condition of exposed areas of a stator winding. Measurement of insulation resistance and withstand of the accompanying hipot test used during the sealed winding test do not fully evaluate insulation system reliability (i.e., long-term life). Acceptance by a sealed winding test does not serve as a stand-alone quality measurement, but should be accompanied by other diagnostic tests to provide a more complete measure of insulation system acceptance. Although NEMA MG-1 clearly relates the sequence of events of the spray test, it is not clear if the IR testing or hipot should begin while the stator is being sprayed, or afterwards. Aqueous solution parameters and precipitation rates are also not provided. Test results from spraying three sealed 13.8 kV-rated windings with different solutions suggest that the solution conductivity does not significantly affect the IR. There is no doubt that the details of the test procedure can certainly affect the test result. To ensure a reproducible test result, the method must be consistent. The authors believe that the value of the sealed winding test and its ease of interpretation would be enhanced by further clarification of the method, and by including solution properties, perhaps by reference to IEEE Std 4 [8]. Further work is required to determine the effect of solution electrical conductivity and precipitation rate. The NEMA committee has approved the clarification of minimum acceptable insulation resistance given in NEMA MG-1 for sealed winding tests. The acceptance value remains IR (MΩ) ≥ VLL + 1 (kV), and the document will continue to reference IEEE 43 for the insulation resistance test method. Unique machine specifications may request a higher IR value, but the industry standard for a soaked winding does not exceed IR (MΩ) = VLL + 1 (kV). V. REFERENCES [1] IEEE Std 1434 (2000), Trial-Use Guide to the Measurement of Partial Discharges in Rotating Machinery 4 [2] IEEE Std 286 (2000) Recommended Practice for measurement of Power Factor Tip-Up of Electric Machinery Stator Coil Insulation [3] IEEE Std 1043 (1996), Recommended Practice for Voltage-Endurance Testing of Form-Wound Bars and Coils [4] IEC 60727, Parts 1 & 2, Evaluation of electrical endurance of electrical insulation systems (IEC Central Office, Geneva, Switzerland) [5] IEEE Std 429 (1994), Recommended Practice for Thermal Evaluation of Sealed Insulation Systems for AC Electric Machinery Employing Form-Wound Preinsulated Stator Coils for Machines Rated 6900 V and Below [6] NEMA MG 1-2006, Motors and Generators (National Electrical Manufacturers Association, Rosslyn, VA) [7] IEEE Std 43 (2000), Recommended Practice for Testing Insulation Resistance of Rotating Machinery [8] IEEE Std 4 (1995), IEEE Standard Techniques for High- Voltage Testing [9] M. Costello, F. Cook, F. Heredos, “Winding Immersion Testing: “Are Our Fears All Wet?” (PCIC Conference Record, 13-15 Sept. 1993) pp. 167 - 170. VI. ACKNOWLEDGEMENTS The authors would like to thank R. Perks for stator testing and D. Messervey for his technical review of the paper. VII. VITA Meredith Stranges holds degrees in Chemistry and Metallurgical Engineering from Brock University and McMaster University, respectively. She joined General Electric in 1997, and in 2004 became the Lead Insulation Engineer for GE Peterborough. Meredith specializes in qualification of insulation systems and materials for large industrial motors, and she has co-authored several papers in conjunction with colleagues. A senior member of IEEE, she is active in the Dielectrics and Insulation Society and the Standards Association. Meredith participates on international standards working groups for the IEEE-SA and IEC TC 2 on Rotating Machines. She is registered as a Professional Engineer in the province of Ontario. Bharat Mistry received the B.E. degree in electrical engineering from South Gujarat University, Surat, India in 1972. He immigrated to Canada in 1979 and began practicing as a Professional Engineer in Ontario. He has served industry in many areas including quality, maintenance and design. During the past 15 years, he has devoted his time to design and application of large rotating electrical machines for hazardous and non-hazardous locations, built to National and International standards.He has published many papers in “Electrical India”, and as an author and coauthor for IEEE/PCIC papers. He is a working group member for the development of NEMA MG-1 (global standard), IEEE 1349, and IEC TC 31/WG 27. Ramtin Omranipour graduated with a B.Sc. in Electrical Engineering from University of Science and Technology, Tehran, Iran, in 1991. Between 1991 and 1999, he worked as an Electrical Engineer for multiple organizations where he was in charge of maintenance and repair of electrical systems and equipment including high voltage transformers and rotating electric machines. In 2000, he began graduate studies at University of Waterloo, Ontario, Canada, where he conducted research on high voltage insulating materials mainly silicone-based products. In 2002, he joined the GE Large Motors & Generators Technology team at Peterborough, Ontario, Canada, as a technical designer. His area of interest is the design and development of large AC motors and generators, and development of insulation systems for large rotating machines.