Baixe o app para aproveitar ainda mais
Prévia do material em texto
Control of Parallel Converters for Load Sharing with Seamless Transfer between Grid Connected and Islanded Modes Ritwik Majumder, Student Member, IEEE, Arindam Ghosh, Fellow, IEEE Gerard Ledwich, Senior Member, IEEE and Firuz Zare, Senior Member, IEEE ABSTRACT: This paper describes control methods for proper load sharing between parallel converters connected to microgrid supplied by distributed generators. The model of the microgrid power system is simulated in PSCAD. It is assumed that the mi- crogrid supplies a load both in grid connected and islanded modes. Both passive loads and inertial loads are considered. A control strategy is proposed to improve the system performance through seamless transfer between islanded and grid connected modes. The controller is capable of handling constant impedance, as well as motor loads. The smooth transition between the grid connected and off grid mode is achieved by changing the control mode from voltage control in islanded mode to state feedback control in grid connected mode. Its efficacy has been validated through simulation for various operating conditions. Index Terms: Distributed power supply, Microgrid, Islanding and Resynchronization, Active and Reactive Power sharing. I. INTRODUCTION HE INTERCONNECTION of distributed generators (DGs) to the utility grid through power electronic convert- ers has raised concern about system stability and smooth trans- fer between the grid connected and standalone modes. Many innovative control techniques have been used for stability of the system as well as for proper load sharing. The most com- mon method is the use of droop characteristics for wireless load sharing. Parallel converters have been controlled to de- liver desired real and reactive power to the system. Local sig- nals are used as feedback to control the converters, since in a real system, the distance between the converters may make an inter-communication impractical. The real and reactive power sharing can be achieved by controlling two independent quan- tities – the power angle, and the fundamental voltage magni- tude [1-4]. The system stability during load sharing has been explored by many researchers [2, 5-7]. Transient stability of power sys- tem with high penetration level of power electronics interfaced (converter connected) distributed generation is explored in [2]. But the study is based on presence of an infinite bus. The im- portant issue of isolated operation of the network has been overlooked in the study. Moreover, smooth transfer between the grid connected mode and the standalone or islanded mode is crucial in microgrid operation. R. Majumder, A. Ghosh, G. Ledwich and F. Zare are with the School of Engineering Systems, Queensland University of Technology, Brisbane, Qld 4001, Australia. A transient droop characteristic is used [8] to achieve steady state invariant frequency and good current balance. Sometimes an additional faster loop is added to program the output im- pedance. Both inductive and resistive output has been investi- gated. In the resistive output, the active power is controlled by terminal voltage where the reactive power is controlled by the source angle. Karimi et al [9] developed a dynamic model and a control system for autonomous operation of a stand-alone Distributed Resource (DR). A stand-alone DR includes a dis- tributed resource and a local load which are interfaced elec- tronically. The DR is represented by a DC voltage source in series with a three phase voltage-sourced inverter and an RL filter, while the local load is modeled by a parallel RLC net- work. A state-space dynamic model is developed for the DR including the RLC network. Based on the dynamic model of the DR, a controller is designed to maintain stability and to control voltage and frequency of the stand-alone DR. Control of the DG system is important in both grid connected and islanded modes and the system stability becomes very crucial during the transfer between grid connected and islanded modes. A seamless transfer can ensure a smooth operation with proper load sharing and quick attainment of steady state. The aim of this paper is to set up power electronics inter- faced microgrid containing distributed generators. Schemes for controlling parallel connected converters in islanded and grid connected mode are presented. The control techniques for a smooth transfer between these two modes are also shown. A modular structure of the controller is presented. The structure can be modified to meet the control requirement for any other distributed system configuration. II. SYSTEM STRUCTURE The basic power system model with two DG sources con- nected to the load at the point of common coupling (PCC) is shown in Fig. 1. In this, the system runs in islanded mode when the circuit breaker (CB) is open; otherwise it runs in grid connected mode. The load can be a constant impedance load or a motor load. In Fig. 1, the voltage source VS is the utility voltage that is connected to the PCC with a feeder of imped- ance RS + jXS. The current drawn from the utility is denoted by Ig, while Pg and Qg are respectively the real and reactive power supplied by the grid. It is assumed that the DGs are constant dc voltage sources Vdc1 and Vdc2. The converter output voltages are denoted by V1∠δ1 and V2∠δ2 and they are connected to the PCC through reactances jX1 and jX2 respectively. P1, P2 and Q1, Q2 represent the real and reactive power supplied by the DGs. T ©2008 IEEE. Fig.1. The system under consideration. III. PROPOSED CONTROL STRUCTURE The starting point of the control is the conventional droop method, given by nQVV mPs −= −= ∗ ωω (1) where m and n are the droop coefficients, ωs is the synchro- nous frequency, V is the magnitude of the converter output voltage and ω is its frequency, while P and Q respectively denote the active and reactive power supplied by the con- verter. Thus the frequency and the voltage are being controlled by the active and reactive power output of the DG sources. A. Modular Control Structure The conventional droop controller, given by (1), is modified in the proposed control scheme. This is shown in Fig. 2 for DG1 only. A similar structure is also used for DG2. In this structure, V1∠δ1 and I1 are used for calculating the real power (P1) and reactive power (Q1) injected by DG1. These are then used in (1) to calculate ωs and V1* as per (1). The quantity ωs and the angle of the PCC voltage δPCC are then used to calcu- late the reference angle δ1*. This is described in the next sub- section. The reference magnitude V1 * and its angle δ1* are then used to generate the instantaneous reference voltages for the three phases. These are then compared with the measured val- Fig.2. The modular control structure, ules of the instantaneous phase voltages of V1. The resultant error is used in the feedback control to generate the switching action (u = ± 1) of VSC-1. The feedback control and converter structure are discussed in Section IV. B. Converter Voltage Angle Calculation The converter voltage angle control loop is shown in Fig. 3. The frequency ω1 is calculated from the droop given in (1). This is then compared with the frequency (ωPCC) of the PCC voltage. The error is passed through an integrator with a gain of KI and is then added with the integral of ωPCC to obtain φ1*. The angle φ1* rotates at the synchronous speed ωs while mak- ing an angle δ1* with the reference. Note that by changing the value of KI, we can influence the close loop dynamics without affecting the steady state frequency regulation. Fig. 3. Voltage angle control loop. IV. CONVERTER STRUCTUREAND CONTROL The converter structure is shown in Fig. 4. This contains three H-bridge converters that are connected to the DG sources, denoted by Vdc1. The outputs of the H-bridges are connected to three single-phase transformers that are con- nected in wye for required isolation and voltage boosting [10]. The resistance Rf represents the switching and transformer copper losses, while the inductance Lf represents the leakage reactance of the transformers. The filter capacitor Cf is con- nected to the output of the transformers to bypass switching harmonics. The inductance L1 is added to provide the output impedance of the DG source. Fig. 4. Converter structure. The advantage of the VSC scheme shown in Fig. 4 is that it can readily be used even when the loads (or supply side) con- tain unbalance and harmonics. In fact, the DG will be able to compensate for these to make the microgrid voltage balanced and distortion free. To achieve the same performance from a three-phase VSC, the dc bus neutral must be clamped. Since a DG is often directly coupled to the dc bus, this will not be possible. Furthermore, the transformers can boost a lower level dc voltage to the microgrid level. A. Converter Control The equivalent circuit of one phase of the converter is shown in Fig. 5. In this, u⋅Vdc1 represents the converter output voltage, where u = ± 1. The main aim of the converter control is to generate u. Fig. 5. Equivalent circuit of one phase of the converter. From the circuit of Fig. 1, state space description of the sys- tem can be given as PCCc vBuBAxx 21 ++=& (2) where uc is the continuous time version of switching function u. The discrete-time equivalent of (2) is ( ) ( ) ( ) ( )kvGkuGkFxkx PCCc 211 ++=+ (3) Based on this model and a suitable feedback control law, uc(k) is computed. The switching function u is then generated as 1 then elseif 1 then If −=−< +=> uhu uhu c c (4) where h is a small number. Two types of feedback controllers are used here. They are discussed below. B. Output Feedback Voltage Controller Let the output of the system given in (3) be vcf. From Fig. 2, it can be seen that the reference for this voltage is given in terms of the magnitude of the rms voltage V1 * and its rotating angle φ1*. From this the instantaneous voltage reference v1* for the three phases are generated. Neglecting the PCC voltage since it is a disturbance input, the input-output relationship of the system in (3) can be written as ( ) ( ) ( )( )1 1 − − = zN zM zu zv c cf (5) The control is computed from ( ) ( )( ) ( ) ( ){ }zvzvzR zSu cfc −= ∗− − 11 1 z (6) Then the closed-loop transfer function of the system is given by ( ) ( ) ( ) ( )( ) ( ) ( ) ( )1111 11 1 −−−− −− ∗ += zSzMzRzN zSzM zv zvcf (7) The coefficients of the polynomials S and R can be chosen based on a pole placement strategy [11]. Once uc is computed, the switching function u can be generated from (4). C. State Feedback Controller Let the state vector be defined by [ ]1iivx cfcfT = (8) The reference for vcf is v1 * mentioned in the previous sub- section. Given V1 * and φ1*, the phasor current through the ca- pacitor Cf is given by ( )°+∠= ∗∗∗ 9011 δω VCI fcf (9) The reference icf * is obtained from the instantaneous value of Icf *. We shall obtain the reference for i1 through its phasor quan- tity I1 *. Note from Fig. 1 that if the references are strictly fol- lowed * 1 * 1 * 111 IVjQP ×−∠=− δ (10) Let us define I1 * = I1p * + j I1q *. We can then write the follow- ing from (10) [ ] [ ]∗∗∗∗ ∗∗ ∗ ∗ −= += 1111 1 1 1111 1 1 cossin 1 sincos 1 δδ δδ QP V I QP V I q p (11) Therefore the phasor reference is given by ⎟ ⎟ ⎠ ⎞ ⎜ ⎜ ⎝ ⎛+= ∗ ∗ −∗∗∗ p q qp I I III 1 11 111 tan (12) Fig. 6. Source angle extraction from rotating angle. To calculate the reference from (12), the value of δ1* has to be obtained. The voltage angle controller of Fig. 3 generates a rotating angle φ1* which is equal to ωst + δ1*. The angle φ1* is reset after every 2π. Fig. 6 shows the variation along with the reference ωst. From this figure we can write ∗+== 110 2 δωπω tt ss Therefore we have ( )011 tts −=∗ ωδ (13) Once the references for the state vector (8) are obtained, the control law is computed from ( )∗−−= xxKuc (14) where K is the gain matrix and x* is the reference vector. The gain matrix, in this paper, is obtained through linear quadratic regulator (LQR) design. From uc, the switching function is generated as in (4). V. SIMULATION STUDIES Simulation studies are carried out with different types of loads and operating conditions to check the system response and controller action. Some of the results are discussed below. The system data used are given in Table I. TABLE I. SYSTEM PARAMETERS System Quantities Values Systems Frequency (ωs) 100π rad/s Source voltage (Vs) 11 kV rms (L-L) Feeder impedance (Rs + jXs) 3.025 + j12.095 DG-1 DC voltage (Vdc1) Transformer rating VSC losses Source inductance (L1) Filter Capacitance (Cf) Frequency droop coefficient (m) Voltage droop coefficient (n) 220 V 220 V/11 kV, 0.5 MVA, 2.5% reactance (Lf) 1.5 Ω 0.0578 H 30 µF 0.005 rad/s/kW 0.2045 kV/kVAr DG-2 DC voltage (Vdc1) Transformer rating VSC losses Source inductance (L1) Filter Capacitance (Cf) Frequency droop coefficient (m) Voltage droop coefficient (n) 220 V 220 V/11 kV, 0.5 MVA, 2.5% reactance (Lf) 1.5 Ω 0.0722 H 30 µF 0.00625 rad/s/kW 0.2727 kV/kVAr Passive load The load is varied between 4.84 + j30.25 Ω and 102.85 + j157.3 Ω Motor load (synchronous) Rated rms voltage (L-N) Rated rms line current Inertia constant Iron loss resistance 6 kV 5 kA 1 s 300 pu Motor load (induction) Rated rms voltage (L-N) Rated rms line current Rated power 6 kV 0.11 kA 50 hp A. Islanded Mode In the islanded mode, the VSCs are operated in voltage con- trol mode through output feedback. In this mode, the grid is not available and the total power demand of the load is sup- plied by the DGs. The frequency is also not fixed and is calcu- lated from the modified droop to meet the active and reactive power requirements. With any load change, the active and reactive power requirements change and the VSC reference voltage magnitude and angle must change to meet the new load requirement. Two types of load are considered here – constant impedance type load and motor load. Fig. 7 shows the response with impedance load, where the values of the load impedances are doubled at 1 s. The load is changed back to its nominal value at 1.5 s. It can be seen that DG-1 shares more load than DG-2 in accordance with their droop characteristics, while the grid does not supply any power. 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 -0.5 0 0.5 1 1.5 A ct iv e p ow er ( M W ) 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 -0.2 0 0.2 0.4 0.6 R ea ct iv e po w er (M V A R ) 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 -0.1 0 0.1 Time(s) C u rr en t- p ha se a (k A ) DG1 DG2 Grid DG1 DG2 Grid DG1 DG2 Grid Fig.7 System response with impedance load in islanded mode. Fig. 8 shows theresults when the inductor motor is con- nected in parallel with the passive load at 2 s and disconnected at 2.75 s. The motor is operated in speed control mode. The change in active power supplied by the DGs and output cur- rent of the inverters show proper load sharing with a quick steady state attainment. The zero power and zero current from the grid confirm the islanded condition. 1.8 2 2.2 2.4 2.6 2.8 3 3.2 0 0.5 1 1.5 2 A ct iv e p o w er ( M W ) 1.8 2 2.2 2.4 2.6 2.8 3 3.2 -0.6 -0.4 -0.2 0 0.2 0.4 Time (s) C u rr en t- p h as e a (k A ) DG1 DG2 Grid DG1 DG2 Grid Fig .8. System response with motor load in islanded mode. B. Grid Connected Mode In the grid connected mode, the steady state system fre- quency is fixed to the utility frequency. It is assumed that the distributed generators supply their rated power at rated fre- quency. When the load requirement is less than the total rated power of the DGs, the excess power flows from DGs go to the grid. In case of a motor load, the PCC voltage should not de- viate much from its nominal value as a sudden large change in the motor terminal voltage will result in a large power swing. The swing is reduce in those situations where a passive load is connected in parallel to the motor. Further to avoid power swing, the VSCs must supply the change in the power demand as quick as possible. To accomplish this, only a voltage con- trol may not be sufficient. It is desirable that a current control- ler is added to the voltage controller to ensure better load shar- ing and quick response. Therefore the control is changed to a state feedback control which uses the feedback of DG output voltage, output current and the current through the filter ca- pacitor. The reference voltage magnitude and angle are calculated from the droop similar to the islanded mode. However the steady state frequency is fixed to the grid frequency. The power sharing by the DGs is rating based. Thus the active and reactive power requirements from individual DG are calcu- lated based on their rating. The output current reference is calculated from the power and voltage reference. The refer- ence for the filter capacitor current is calculated from the volt- age reference. Fig. 9 shows the system response during a load change in the grid connected mode with impedance. In the grid con- nected condition, any change in load is picked up by the grid as the DGs always provide the rated power. In this case, the excess power is sent to the grid. The change in grid current with active power demand ensures a stable operation. 1.2 1.4 1.6 1.8 2 2.2 2.4 -0.5 0 0.5 1 1.5 A ct iv e p o w er ( M W ) 1.2 1.4 1.6 1.8 2 2.2 2.4 -0.2 -0.1 0 0.1 0.2 Time(s) G ri d C u rr en t -p h as e a (k A ) DG1 DG2 Grid Fig. 9. System response with impedance load in grid connected mode. Fig. 10 shows the results with a passive load when an in- duction motor gets connected at 2 s and disconnected at 2.75 s. It is obvious that the additional power required by the motor is coming from the grid as the DGs supply the rated power. Fig. 11 shows the results when a synchronous motor is con- nected in parallel with an impedance load. With the motor and impedance operating in the steady state, the motor is discon- nected at 1.5 s and reconnected at 3 s. It can be seen that the powers supplied by the DGs remain constant during both the transients and the oscillations in the grid current die out within 1 s. 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 0 1 2 3 A ct iv e p o w er ( M W ) 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 -0.4 -0.2 0 0.2 0.4 Time(s) G ri d c u rr en t -p h as e- a (k A ) DG1 DG2 Grid Fig.10. System response with induction motor load in grid connected mode. 1 1.5 2 2.5 3 3.5 4 4.5 0 0.5 1 A ct iv e p o w er ( M W ) 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 -0.04 -0.02 0 0.02 0.04 G ri d c u rr en t (k A ) 2.8 3 3.2 3.4 3.6 3.8 4 4.2 4.4 -0.04 -0.02 0 0.02 0.04 Time (s) G ri d c u rr en t (k A ) DG1 DG2 Grid Fig.11. System response with synchronous motor load in grid connected mode. C. Seamless Transfer between Grid Connected and Islanded Modes The results simulated so far show that a better load sharing and a quick steady state attainment are achieved with the volt- age control in the islanded mode, while the state feedback ensures better response in the grid connected mode. A seam- less transfer between these two modes is proposed in this pa- per by changing state feedback to voltage control and vice versa. Ordinarily, in the grid connected mode, the DGs operate under the state feedback control. When an islanding is de- tected, the DGs are switched to the voltage control mode. These are switched back to the state feedback control mode after resynchronization. The sequence of control from a grid connected operation to islanded mode and then again back to grid connected is given below. 1. Detect the islanding by zero current in the breaker con- necting the grid with the microgrid. 2. If islanded, switch to voltage control mode. 3. Calculate the reference voltage required for the individ- ual DGs to maintain the load power requirement from the droop. 4. Check for the clearing of the fault. 5. If resynchronization is desired, detect the grid voltage and frequency. 6. Calculate the reference voltages for the DGs to make the PCC voltage same as the grid voltage while continuing to supply the load requirement and with the proper shar- ing. 7. Calculate the change in angle required to match the phase for proper synchronization. 8. Change the voltage reference to the new calculated value. 9. Connect the breaker. 10. Switch to the state feedback control mode. Figs. 12 and 13 show the response of the system during islanding and resynchronization with the impedance load when the islanding occurs at 1.5 s and the resynchronization occurs at 2 s. Fig. 12 shows the power sharing and currents, while the PCC voltages are shown in Fig. 13 during the island- ing and resynchronization operation. Fig. 12, System response during islanding and resynchronization with imped- ance load. Fig. 13. PCC voltage during islanding and resynchronization with impedance load Islanding and synchronization with motor load have also been also investigated. An impedance load is an infinite sink as it can absorb any change in instantaneous real and reactive power. However an inertial load such as motor is not capable of sinking much power. Thus any change in the terminal volt- age will result in large oscillation in the real and reactive pow- ers. So the stability becomes a major issue during islanding with inertial load. Since the voltage control is a slow process, a re-initialization in the reference value is required to force the system to a new steady state quickly. It is assumed that an online load flow study is always per- formed in background with the microgrid load and generation. At the instant of islanding, the values obtained from the load flow are used to determine the new voltage reference. The new reference ensures minimal change in the load voltage after islanding and proper sharing of the loads among the DGs. These new values are assigned as the new reference for the controllers. Fig. 14 shows the active power sharing during islanding and resynchronization with a motorload. An induction motor is used here. The active power input to the motor load is also shown in this figure. It can be seen that this power remains constant during islanding and resynchronization, validating a seamless transfer between the two modes. Phase-a of the DG output currents along with the grid currents are shown sepa- rately during islanding and resynchronization in Fig. 15. It can be seen that all the currents reach their steady state values with 0.2 s, both during islanding and resynchronization. 0.5 1 1.5 2 2.5 3 3.5 0 0.5 1 1.5 2 2.5 A ct iv e p o w er ( M W ) 0.5 1 1.5 2 2.5 3 3.5 0.5 1 1.5 2 2.5 Time (s) A ct iv e p o w er o f M o to r L o ad ( M W ) DG1 DG2 Grid Fig. 14. System response during islanding and resynchronization with motor load. Fig. 15. System response during islanding and resynchronization with motor load. V. CONCLUSIONS In this paper, a modular controller structure with modified voltage angle control loop is proposed for better load sharing between the parallel connected inverters in a distributed gen- eration system. The integral control in the voltage angle loop helps to influence the close loop dynamics without affecting the steady state frequency regulation. By switching the control action of the DGs from state feedback in grid connected mode to voltage control in islanded mode, a seamless transfer is achieved. A step by step control method is proposed for a smooth transition during islanding and resynchronization. The efficacy of the controller is verified through PSCAD simula- tions with impedance as well with motor loads. ACKNOWLEDGEMENT The authors thank the Australian Research Council (ARC) for the financial support for this project through the ARC Dis- covery Grant DP 0774092. REFERENCES [1] F. Katiraei and M. R. Iravani, “Power Management Strategies for a Microgrid with Multiple Distributed Generation Units,” IEEE Transac- tions on Power Systems, Vol. 21, No. 4, pp. 1821-1831, 2006. [2] M. Reza, D. Sudarmadi, F. A. Viawan, W. L. Kling, and L. Van Der Sluis, “Dynamic Stability of Power Systems with Power Electronic In- terfaced DG,” Power Systems Conference and Exposition, PSCE'06, pp. 1423-1428, 2006. [3] M. Dai, M. N. Marwali, J. W. Jung, and A. Keyhani, “Power flow con- trol of a single distributed generation unit with nonlinear local load,” Power Systems Conference and Exposition, PSCE’04. pp. 398-403, 2004. [4] R. H. Lasseter, “MicroGrids,” Power Engineering Society Winter Meet- ing, Vol. 1, pp. 305-308, 2002. [5] J. M. Guerrero, L. G. de Vicuna, J. Matas, M. Castilla, and J. Miret, “A wireless controller to enhance dynamic performance of parallel inverters in distributed generation systems,” IEEE Transactions on Power Elec- tronics, Vol. 19, pp. 1205-1213, 2004. [6] R. H. Lasseter and P. Paigi, "Microgrid: a conceptual solution," in Power Electronics Specialists Conference, PESC’04. Vol. 6, pp. 4285- 4290, 2004. [7] M. C. Chandorkar, D. M. Divan, and R. Adapa, "Control of parallel connected inverters in standalone AC supply systems," IEEE Transac- tions on Industry Applications, Vol. 29, No. 1, pp. 136-143, 1993. [8] J. M. Guerrero, L. Garcia de Vicuna, J. Matas, and J. Miret, "Steady- state invariant-frequency control of parallel redundant uninterruptible power supplies," in IECON 02 [Industrial Electronics Society, IEEE 2002 28th Annual Conference of the], 2002, pp. 274-277 vol.1. [9] H. Karimi, H. Nikkhajoei, and R. Iravani, "A Linear Quadratic Gaussian Controller for a Stand-alone Distributed Resource Unit-Simulation Case Studies," in Power Engineering Society General Meeting, 2007. IEEE, 2007, pp. 1-6 [10] A. Ghosh and A. Joshi, “A new approach to load balancing and power factor correction in power distribution system,” IEEE Transactions on Power Delivery, Vol. 15, No. 1, pp. 417-422, 2000. [11] A. Ghosh, “Performance study of two different compensating devices in a custom power park,” Proceedings of the IEE − Generation, Transmis- sion & Distribution, Vol. 152, No. 4, pp. 521-528, 2005. Ritwik Majumder (S’07) received his B.E. in Electrical Engineering from Bengal Engineering College (Deemed University) in 2001 and his M.Sc. (Engg.) degree from Indian Institute of Science in 2004. From July 2004 to November 2004, he was with Tata Motor Engineering Research Centre in Jamshedpur, India. From November, 2004 to January 2006, he was with Sie- mens Automotive India and from January 2006 to May 2007, he was with ABB Corporate Research Centre, Bangalore, India. Since June 2007, he is a Ph.D. scholar in Queensland University of Technology. His interests are in Power Systems dynamics, Distributed Generation and Power Electronics Applications. Arindam Ghosh (S’80, M’83, SM’93, F’06) is the Professor of Power Engi- neering at Queensland University of Technology, Brisbane, Australia. He has obtained a Ph.D. in EE from University of Calgary, Canada in 1983. Prior to joining the QUT in 2006, he was with the Dept. of Electrical Engineering at IIT Kanpur, India, for 21 years. He is a fellow of Indian National Academy of Engineering (INAE) and IEEE. His interests are in Control of Power Systems and Power Electronic devices. Gerard Ledwich (M’73, SM’92) received the Ph.D. in electrical engineering from the University of Newcastle, Australia, in 1976. He has been Chair Pro- fessor in Power Engineering at Queensland University of Technology, Austra- lia since 2006. Previously he was the Chair in Electrical Asset Management from 1998 to 2005 at the same university. He was Head of Electrical Engi- neering at the University of Newcastle from 1997 to 1998. Previously he was associated with the University of Queensland from 1976 to 1994. His interests are in the areas of power systems, power electronics, and controls. He is a Fellow of I.E.Aust. Dr Firuz Zare (S’97, M’01, SM’06) was born in Iran in 1967. He holds a PhD degree in Electrical Engineering from Queensland University of Tech- nology in Australia. He has worked as a development engineer and a consult- ant in industry for several years. He has joined the school of engineering systems in QUT in 2006. His research interests are power electronic applica- tions, pulse-width modulation techniques, renewable energy systems and electromagnetic interferences.
Compartilhar