Buscar

C130 imVision Tech Note -imVision Controller Network Settings 062314 Feb 14

Prévia do material em texto

February 20, 2014 
 
CommScope | Marta Ripa 1 
 
 
imVision Controller 
Default Network Settings and Configuration 
 
 
imVision Controllers have two RJ45 ports located on the rear labeled A/IN and B/Out. These ports can handle Ethernet 
10/100 Mbps communication as well as an alternative 485 serial communication. Their functionality is configured through 
the Push ONPush ONPush ONPush ON button next to each of them and will depend on the position of the Controller in the controller LAN. 
 
 
 
 
 
By default both Push ON buttons come in the “out” position. This configures both ports for “Controller LAN function”: this 
configuration would be the one used for a controller that is in the middle of a controller LAN (not in the first or last 
positions). 
If a Controller is in the last position, its Port B should be set to “pushed in” and the port will be left unused. 
If a Controller is in position 1 it will take the Network Manager function and its Port A needs to be connected to the 
customer LAN and configured as follows: 
a) Set the push-on switch for Port A to the pushed pushed pushed pushed inininin position 
b) On the controller screen, go to Home Home Home Home ----> Settings > Settings > Settings > Settings ----> > > > NetworkNetworkNetworkNetwork SettingsSettingsSettingsSettings 
The Network function is set to Disabled by default. Change to Network = EthernetNetwork = EthernetNetwork = EthernetNetwork = Ethernet 
 
The following default values are populated: change to desired values 
► IPV4 or IPV6 – IPV4 
► IPv4 IP Address – 192.168.1.10 
► IPv4 Subnet Mask – 255.255.255.0 
► IPv4 Gateway – 192.168.1.1 
► Primary DNS – none 
► Secondary DNS – none 
► Socket – 8510 
► Interface Speed – 100 MB/Sec 
► Duplex – Auto 
► Enable Ping Response – checked (enabled) 
imVision Controller Rear View