The function of the RPW-FSF relay is to monitor three-phase systems against phase loss and inversion. It can also monitor the voltage on the neutral, which must be connected. To use it with neutral, a bridge must be made between terminals A and B. It is recommended for use in electronic power controllers or in situations where there is a high index of harmonic currents. However, for situations with a high index of harmonic currents greater than recommended in IEEE519, it is recommended to use the ERWM model.