Baixe o app para aproveitar ainda mais
Prévia do material em texto
Author: J.Z. Page 1 of 4 056-092 ISSUE: 1 Recommended Practices for Wiring Resistive Sensors 1 OVERVIEW This training document is intended to assist with wiring resistive sensors to DSE modules. Outlined below are the DSE recommended wiring practices, as well as examples of common mistakes made when installing sensors. It is assumed that all personnel carrying out the work described have a sufficient level of technical knowledge to assess and complete the job to a competent level. 2 INCORRECT WIRING PRACTICES Connecting a resistive sensor to a DSE controller appears at first to be a straightforward procedure. There are, however some common practices which may inadvertently lead to erroneous sensor readings or a complete loss of sensor data. In particular, the wiring configuration of the ground and sensor common connections may affect readings. This is illustrated in the diagram below: To calculate the displayed values of resistive sensor inputs, the DSE module applies a fixed current to the Analogue Input circuits, and measures voltage at each active Analogue Input terminal with respect to the Analogue Input Common terminal. In this example the earth terminal of the Coolant Temp Sensor is wired to the battery negative common circuit. Configured as such the sensor is susceptible to voltage changes in the negative circuit, and will show erroneous readings when such changes take place. High Impedance in the Analogue Input Common cable causes a voltage difference with respect to earth. Damaged, low quality or excessively long cables all lead to this. Analogue Input Common is connected to the same circuit as a battery charger’s negative terminal. When the charger is active, the return current causes a voltage increase in the circuit. As with the Coolant Temp Sensor example, a change in negative circuit voltage leads to incorrect sensor data. The difference in this case is; a raised Analogue Input Common voltage will cause incorrect readings on all active resistive sensors. 056-092 ISSUE: 1 Page 2 of 4 Author: J.Z. 3 RECOMMENDED WIRING PRACTICES NOTE: The diagram shows a generic earthing configuration. For further information on earthing conventions, such as floating or positive earth, refer to the relevant DSE operator’s manual. DSE recommendations for wiring resistive sensors are outlined below in bullet notation. All points are intended solely as a guideline, and as such each installation must be evaluated individually from both an operational and safety perspective. o Sensor ground connections wired directly between the sensor body and engine block. o Analogue input common used solely as ground reference, and not providing a ground connection for any other device. o Analogue input common circuit unsusceptible to voltage increase as a result of current flow from another device, for example return current from a battery charger. o Consideration for the sensor cable lengths, cross-sectional area and quality made to ensure voltage drop across the cable remains within acceptable limits. Refer to relevant DSE Operator Manual and manufacturer’s specifications for the sensor. o Battery negative connected to earth. A typical example of recommended wiring practices is shown below: Analogue Input Common wired directly to earth point with no other connections. Correctly specified cable used. All sensor ground connections wired directly to engine block. Author: J.Z. Page 3 of 4 056-092 ISSUE: 1 4 COMMON FAULTS Other faults commonly associated with resistive sensors are: o PTFE Tape Around Sensor Threads. Often used to aid sealing, the PTFE tape also acts as electrical insulation. This is a problem on resistive sensors designed to use the surface they are screwed into (usually the engine block) as the earth connection. The PTFE tape creates a high resistance between the sensor and earth, causing incorrect values/loss of sensor readings. o Incorrect Washer/Seal Used with Sensor. Similarly to the PTFE tape, the wrong type of washer or seal for the selected sensor may cause a high resistance to the sensor common. Manufacturers guidelines must always be followed regarding sealing requirements. o Sensor Failure. The majority of resistive sensors utilise internal moving parts to provide variable readings. As with all moving components, these are subject to wear and will fail in time. Environmental factors such as water ingress may serve to additionally shorten the lifespan of such parts. A typical failing resistive sensor may display high readings, before becoming permanently open circuit. o Poor Termination. Incorrectly terminated sensor wires may cause high resistance, and thus incorrect readings. Furthermore, the connections are likely to be weaker and may fail sooner than expected, especially if attached to vibrating machinery such as an engine. 5 FAIL TO STOP AND THE OIL PRESSURE SENSOR The Fail to Stop alarm becomes active if a stop command has been issued by the DSE module, and any of the sensor values selected for Crank Disconnect are above specified limits when the Stopping Timer has completed. Depending on module type and configuration the Crank Disconnect function will read from the following values: o Oil Pressure o Generator Frequency o Engine Speed o Charge Alternator Voltage o Generator Voltage If the engine is physically verified to have stopped, and the alarm is present, the most likely cause is a fault in the Oil Pressure Sensor circuit. This may be due to any of the faults or incorrect wiring practices described elsewhere in this document. The Oil Pressure value is checked on the front panel of the DSE module or using the SCADA section of the DSE Configuration Suite PC software. Carrying out this quick and easy test may avoid a lengthy fault finding process. This Page is Intentionally Blank
Compartilhar