Baixe o app para aproveitar ainda mais
Prévia do material em texto
Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 1 - Fast-front overvoltages may be: – lightning overvoltages affecting overhead lines; – lightning overvoltages affecting substations; – overvoltages due to switching operations and faults. Fast-front overvoltages may be: – lightning overvoltages affecting overhead lines; – lightning overvoltages affecting substations; – overvoltages due to switching operations and faults. Fast-Front Overvoltages Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 2 - Reasons for lightning overvoltages affecting OHL: – direct lightning strikes to the phase conductor Æ see later; – lightning strikes to tower/ground wire and subsequent back flashover; – induced by lightning strikes to ground nearby the OHL. Reasons for lightning overvoltages affecting OHL: – direct lightning strikes to the phase conductor Æ see later; – lightning strikes to tower/ground wire and subsequent back flashover; – induced by lightning strikes to ground nearby the OHL. Lightning Overvoltages affecting Overhead Lines (OHL) Amplitudes of induced overvoltages usually below 400 kV Æ problem for distribution systems, but not an issue for high-voltage (LIW(Um = 72.5 kV) = 325 kV, LIW(Um = 123 kV) ≥ 450 kV) Back flashovers • less probable in range II than in range I • rare in systems of Us = 550 kV and above The representative voltage stress is characterized by: – a representative voltage shapeÆ 1.2/50 µs; – a representative amplitude which can be either • an assumed maximum overvoltage or • a probability distribution of the overvoltage amplitudes. The representative voltage stress is characterized by: – a representative voltage shapeÆ 1.2/50 µs; – a representative amplitude which can be either • an assumed maximum overvoltage or • a probability distribution of the overvoltage amplitudes. Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 3 - Amplitudes and rates of occurrence depend on: – lightning performance of the OHLs connected to it; – substation layout, size and in particular number of OHLs connected to it; – instantaneous value of the operating voltage (at the moment of strike). Amplitudes and rates of occurrence depend on: – lightning performance of the OHLs connected to it; – substation layout, size and in particular number of OHLs connected to it; – instantaneous value of the operating voltage (at the moment of strike). Lightning Overvoltages affecting Substations Reduction of overvoltages phase-to-ground by • cables (due to their low surge impedance) • many lines connected in parallel (Æ reduction of effective surge impedance) see lecture on traveling waves Phase-to-phase: Effects of power-frequency voltage and coupling between conductors roughly cancel each other. Æ The neighbored phase may be considered as earthed. L1 L2 LI by direct strike to L1 induced LI voltage by coupling L1↔ L2 Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 4 - For back flashovers: Back flashovers most likely occur on the phase that has the highest instantaneous power-frequency voltage at opposite polarity. Æ Representative overvoltage composed of the representative LI voltage phase-to-earth at one terminal and 1 p.u. power-frequency voltage of opposite polarity at the other Terminal 2 Terminal 1 Terminal 2 Terminal 1 Longitudinal: Power-frequency voltage of opposite terminal to be taken into account! For direct strikes: Representative overvoltage composed of the representative LI voltage phase-to-earth at one terminal and 0.7 p.u. power-frequency voltage of opposite polarity at the other (empirical finding) Lightning Overvoltages affecting Substations Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 5 - Fast Front Overvoltages due to Switching Operations Occur when – equipment is (dis-)connected from the system via short connections, mainly in substations; – external insulation flashes over. Occur when – equipment is (dis-)connected from the system via short connections, mainly in substations; – external insulation flashes over. Representative voltage = Standard Lightning Impulse Voltage 1.2/50 µs (though the real voltages are usually oscillatory) Representative voltage = Standard Lightning Impulse Voltage 1.2/50 µs (though the real voltages are usually oscillatory) Amplitudes usually lower than those caused by lightning strikes. Maximum values: • circuit breaker switching without restrike Æ 2 p.u. • circuit breaker switching with restrike Æ 3 p.u. (exception: with vacuum breakers up to 6 p.u. Æ voltage limiters required!) • disconnector switching Æ 3 p.u. It may be assumed that phase-to ground overvoltages constitute the decisive stress for insulation coordination purposes. Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 6 - Direct Lightning Strikes to OHL 21 ln( ) 21 e for 0( ) 2 0 for 0 x M xf x x x β π β ⎡ ⎤− ⎢ ⎥⎣ ⎦ ⎧⎪ >= ⎨⎪ ≤⎩ Statistical distribution of parameters of the flash to be approximated by a lognormal distribution (Berger, Anderson, Eriksson, CIGRÉ) Probability density function: M ... Median = 0.5 probability – not to be mixed up with the mean or average value! β .... log standard deviation Calculation of the mean or average value: 2 2eµ M β = Calculation of the standard deviation: 2 2 2e e 1M β βσ = ⋅ − Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 7 - Direct Lightning Strikes to OHL – Berger's Data Lightning research station of Prof. Berger in a radio transmission station on top of Monte San Salvatore (912 m; Lake of Lugano, Switzerland) Installed 1942 on behalf of SEV Lightning studies up to ≈ 1970 Æ „Berger‘s Data“ Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 8 - Direct Lightning Strikes to OHL – Berger's Data t10/30 t30/90 I10 I30 I90 I100 F m m It S = I m m It S ′ = The strike current's front typically has a concave shape. The strike current's front typically has a concave shape. 2 2 F F F 0.484 2 2e 31.1 e 35 kA I I Iµ M β = ⋅ = ⋅ = Difference Median – Mean value: Mean value of first strike's final crest current Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 9 - Extract of the table – values of primary importance Direct Lightning Strikes to OHL – Berger's Data F m m It S = 91.5 µs 29 kA/µs 4.46 µs 1.54 µs µ, mean value 2 2eµ M β = Sm S30/90 Sm S30/90 57.4 kA/µs 32.1 kA/µs 29 kA/µs 8.7 kA/µs 35 kA 14.2 kA µ, mean value Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 10 - CIGRÉ and IEEE strike current probability curves, first strike, negative downward flash [CIG-91] Direct Lightning Strikes to OHL – CIGRÉ Model CIGRÉ curve: P ( I < I F ) The CIGRÉ distribution is based on the latest data available and better represents the actual data. Æ CIGRÉ curve should preferably be used! The CIGRÉ distribution is based on the latest data available and better represents the actual data. Æ CIGRÉ curve should preferably be used! IF, median = 33.3 kA IF, median = 61.1 kA Note: M = 61.1 kA for IF < 20 kA does not mean that this current really occurs. It is just a parameter that characterizes the curve, which is actually valid onlyin the range < 20 kA, however! Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 11 - Derived parameters of conditional lognormal distributions, derived from Berger's data Direct Lightning Strikes to OHL – Berger's Data Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 12 - Direct Lightning Strikes to OHL – CIGRÉ Model Average wave shape of the first and subsequent negative strike currents as developed by CIGRÉ [CIG-91] Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 13 - Direct Lightning Strikes to OHL – CIGRÉ Model Models of lightning strike acc. to IEC 60071-4 Double ramp shape Æ easy to use Double ramp shape Æ easy to use CIGRÉ concave shape, parameters from [CIG-91] Æ higher accuracy CIGRÉ concave shape, parameters from [CIG-91] Æ higher accuracy Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 14 - > 90%> 90% from exposed points such as aerials, tv towers no subsequent strikes, highest reported current peak values and charges Seldom! downward flash upward flash cloud-to-cloud flash negative cloud-to-ground positive cloud-to-ground negative ground-to-cloud positive ground-to-cloud Direct Lightning Strikes to OHL – strike Multiplicity Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 15 - Only 45% of negative downward flashes consist of one strike per flash. In all other cases: multiple strikes in time intervals of 10 ms to 100 ms (see HVT II, Chapter 11). Subsequent strikes have • higher front steepness • lower amplitude • up to 54 follow strikes reported • often: dc component (in ca. 50% of all cases)11 current impulses of 7 kA up to 63 kA peak value dc component scale of dc component Direct Lightning Strikes to OHL – strike Multiplicity Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 16 - Direct Lightning Strikes to OHL – strike Multiplicity Number of strikes per flash, negative downward flash 1) =∑ Probability of 4 strikes or more =∑ Probability of 8 strikes or more 1) R. B. Anderson, A. J. Eriksson Lightning Parameters for Engineering Application ELECTRA 69, Mar. 1980, pp. 65-102 • based on 6000 flash records from different regions of the world • median of the distribution: 2 • mean or average value: 3 Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 17 - TD = 20 ... 80 TD = 80 ... 180 Keraunic levels worldwide Middle Europe: TD = 10 ... 25 in equator regions: TD = 100 ... 180 Middle Europe: TD = 10 ... 25 in equator regions: TD = 100 ... 180 Lightning ground flash density Ng = number of lightning ground flashes per km2 and year = ⋅N T 1.25g d0.04 Ng in (km2·a)-1Empirical relation: TD = number of thunderstorm days per year • reported by Eriksson1) from observations in South Africa • generally accepted both by CIGRÉ and IEEE 1) A. J. Eriksson The Incidence of Lightning Strikes to Transmission Lines IEEE Trans. on Power Delivery, Jul. 1987, pp. 859-870 Direct Lightning Strikes to OHL – Lightning Activity Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 18 - Direct Lightning Strikes to OHL – Geometric Model For a specific current I, calculate the striking distance rg and rc. Draw a line parallel to the ground at a distance rg from the ground. With compasses centered at the tower top, draw an arc of radius rc until it intersects the parallel lines drawn in 2, above. Any strike that arrives between A and B will terminate on the ground wire, and any strike that arrives to the left of A or to the right of B will terminate to ground. Any strike that arrives between A and B will terminate on the ground wire, and any strike that arrives to the left of A or to the right of B will terminate to ground. Basic idea (see also HVT II, Chapter 11) Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 19 - Basic idea (see also HVT II, Chapter 11) g g( ) 2IN G N LD′= N(G)|I ... number of strikes to ground wire for current I L ... length of line ( )g g 3 kA ( ) 2 dN G N L D f I I ∞ ′= ∫ f(I) ... probability that current I occurs 3 kA = lowest observed lightning flash current amplitude D'g may be expressed in terms of striking distances and tower height: ( )22g c g c cosD r r h r Θ′ ′= − − = Direct Lightning Strikes to OHL – Geometric Model Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 20 - Practical approach (by empirical observations) (Eriksson) b ( )0.6g 28( ) 10 N b h N G + ⋅′ = N'(G) ... number of strikes to the line in (100 km · a)-1 Ng ... ground flash density in (km2 · a)-1 b … distance of outer conductors in m h … average ground wire height (htower – 2/3·sag) in m (assuming an approximate median current of 35 kA) N'(G) h TD = 35 d TD = 20 d [BAL-04] Note: in case of good shielding most of these strikes will hit the shield wire! Note: in case of good shielding most of these strikes will hit the shield wire! Direct Lightning Strikes to OHL – Geometric Model Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 21 - Striking distance Basic dependence: br A I= ⋅ for references, see [HIL-99] Adopted by CIGRÉ Working Group 0.75 c 7.1r I= ⋅ [I] = kA, [rc] = m = striking distance to an OHL conductor or ground wire Æ many different factors A, b published: Direct Lightning Strikes to OHL – Geometric Model Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 22 - Direct Lightning Strikes to OHL – Shielding Failure strikes between A and B Æ phase conductor strikes between B and C Æ ground wire strikes beyond A Æ ground strikes between A and B Æ phase conductor strikes between B and C Æ ground wire strikes beyond A Æ ground Shielding effect of ground wire Shielding failure rate: m g c g c 3 kA 2 2 ( )d I I SFR N LD N L D f I I = = ∫ Im is the maximum current at and above which no strikes will terminate on the phase conductor Æ see next slide α = shielding angleα = shielding angle L ... length of line Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 23 - Shielding effect of ground wire Æ Dc = 0Æ Currents I ≥ Im will hit ground wire or ground Æ Dc = 0Æ Currents I ≥ Im will hit ground wire or ground Point where all three striking distances rc,GW, rc,PhC, rg meet each other. Point where all three striking distances rc,GW, rc,PhC, rg meet each other. Direct Lightning Strikes to OHL – Shielding Failure Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 24 - Situation for I = Im α ϕ x ϕ = 180° - α – 90° x = 180° - ϕ - 90° = 180° - 180° + α + 90° - 90° = α c a c Direct Lightning Strikes to OHL – Shielding Failure Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 25 - Situation for I = Im c α 2 2 cm 4 cr − gm 2 2 cm 2sin 4 h yr cr α +− = − 2 2 cm 4 cr ⇒�As gm cm 2sin h yr r α +− = Simplification: gm cm mr r r≈ = m m 2sin h yr r α +− ≈ m 2 1 sin h y r α + ≈ − Direct Lightning Strikes to OHL – Shielding Failure Fachgebiet Hochspannungstechnik OvervoltageProtection and Insulation Coordination / Chapter 4 - 26 - Situation for I = Im Direct Lightning Strikes to OHL – Shielding Angle m 2 1 sin h y r α + ≈ − With 0.75m m7.1r I= ⋅ (see slide 20) ⇒ 0.75m m2 7.11 sin h y r Iα + ≈ ≈ ⋅− ( ) 1 0.75 m 2 7.1 1 sin h y I α +⎡ ⎤⎢ ⎥≈ ⎢ ⎥⋅ −⎢ ⎥⎣ ⎦ Examples: h = 60 m, y = 45 m, α = 30 °⇒ Im ≈ 36.3 kA h = 30 m, y = 25 m, α = 15 °⇒ Im ≈ 9.1 kA The higher the structure and the larger the shielding angle, the higher is the maximum current of a direct lightning strike to the OHL conductor. The higher the structure and the larger the shielding angle, the higher is the maximum current of a direct lightning strike to the OHL conductor. Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 27 - Situation for I = Im deg h = 60 m, y = 45 m h = 45 m, y = 35 m h = 30 m, y = 25 m [BAL-04] Direct Lightning Strikes to OHL – Shielding Angle Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 28 - iBlitz i uu i = iBlitz/2 u = Z·i i iBlitz i uu i = iBlitz/2 u = Z·i i Strom- und Spannungswellen nach Blitzeinschlag in ein Leiterseil i = istroke /2 u = Z·i istroke Current and voltage surges after lightning stroke into a line conductor iBlitz i uu i = iBlitz/2 u = Z·i i iBlitz i uu i = iBlitz/2 u = Z·i i Strom- und Spannungswellen nach Blitzeinschlag in ein Leiterseil i = istroke /2 u = Z·i istroke Current and voltage surges after lightning stroke into a line conductor Choice of Im Direct Lightning Strikes to OHL – Shielding Angle If flashovers of the insulators shall be avoided, following requirement has to be fulfilled: 50 neg m 2 Z U I ⋅< Example:Um = 420 kV Æ U50 neg = 2 100 kV, Z = 350 Ω ⇒ Im < 12 kA Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 29 - Direct Lightning Strikes to OHL – Corona Damping When the corona inception voltage is exceeded Æ corona Corona inception voltage of a single conductor: 0 0 i 60 r Z EU ⋅ ⋅= Z0 ... natural (non-corona) surge impedance in ΩE0 ... critical voltage gradient in kV/cm r ... conductor radius in cm Critical voltage gradient (CIGRÉ): 0 0.37 1.2223 1 kV/cmE d ⎛ ⎞= +⎜ ⎟⎝ ⎠ d ... conductor diameter in cm 0 10 20 30 40 50 60 0 2 4 6 8 10 12 conductor diameter (cm) c r i t i c a l v o l t a g e g r a d i e n t ( k V / c m ) Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 30 - Direct Lightning Strikes to OHL – Corona Damping When the corona inception voltage is exceeded Æ corona Corona inception voltage of a single conductor: 0 0 i 60 r Z EU ⋅ ⋅= Z0 ... natural (non-corona) surge impedance in ΩE0 ... critical voltage gradient in kV/cm r ... conductor radius in cm Critical voltage gradient (CIGRÉ): 0 0.37 1.2223 1 kV/cmE d ⎛ ⎞= +⎜ ⎟⎝ ⎠ d ... conductor diameter in cm Example: 123-kV OHL (d = 1.9 cm, r = 0.95 cm, Z0 = 450 Ω) 0 0.37 1.2223 1 = 42 kV/cm 1.9 E ⎛ ⎞= +⎜ ⎟⎝ ⎠ i 0.95 450 42 299 kV 60 U ⋅ ⋅= = Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 31 - Direct Lightning Strikes to OHL – Corona Damping Effect of corona • Apparent increase of radius from non-corona conductor radius r to corona conductor radius Rc • Æ Increase of conductor capacitance (whereas inductance remains unchanged) • Æ Decrease of surge impedance for surge front: • Æ Decrease of velocity for parts of surge voltage u > Ui: 0 c L LZ Z C C C∆ ′ ′= ⇒ =′ ′ ′+ 0 c 1 1 ( ) v v L C L C C∆= ⇒ =′ ′ ′ ′ ′+ t = t0t > t0 Decrease of steepness!Decrease of steepness! Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 32 - Direct Lightning Strikes to OHL – Corona Damping Effect of corona Steepness of the surge depending on traveling distance: C0 0 1 1S K S = ⋅ +A A Sℓ ... steepness of surge after traveling distance ℓ in kV/µs KC0 ... corona damping constant in µs/(kV·m) ℓ ... traveling distance in m S0 ... initial steepness of surge in kV/µs Distribution 5 x 10-6 [IEC 60071-2], [BAL-04] Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 33 - Direct Lightning Strikes to OHL – Corona Damping [BAL-04] (for S0Æ ∞) Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 34 - Direct Lightning Strikes to OHL – Corona Damping Time V o l t a g e ca. 2200 kV/µs ca. 370 kV/µs Measured overvoltage surges on a single-line conductor Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 35 - Back Flashover iB = 2·iE + iM uM = iM·RM RM ... tower surge impedanceRM ... tower surge impedance uinsul. = uM - uL At unfavorable phase relation: uinsul. = uM + |uL| If uinsul. > ud, LI Shield wire Line conductor See HVT II, Chapter 11 and [BAL-04] Problem: extreme du/dt-values!Problem: extreme du/dt-values! For tower footing resistances < 10 Ω: Flashovers at IB > 190 kA Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 36 - Protection by Surge Arresters and Representative Overvoltage • Due to separation effects, surge arresters have a limited protection distance. • The larger the distance between arrester and the equipment to be protected and the higher the steepness, the higher the fast front overvoltage at its terminals. Representative overvoltage when surge arresters are applied (simplified equation): rp pl pl rp pl pl 2 for 2 (!) 2 for 2 U U ST U ST U U U ST = + ≥ = < S ... steepness of surge in kV/µs T ... travel time along distance L in µs 0 LT c = L ... distances a1 + a2 + a3 + a4 in m Æ next slide c0 ... velocity of light: 300 m/µs Example: Um = 420 kV Æ Upl = 825 kV; S = 1000 kV/µs; L = 30 m rp pl 30 m2 825 kV 2 1000 kV/µs 1025 kV 300 m/µs U U ST= + = + ⋅ ⋅ = Note: Urp depends exclusively on steepness and distance arrester ↔ equipment, but not on the overvoltage amplitude! Note: Urp depends exclusively on steepness and distance arrester ↔ equipment, but not on the overvoltage amplitude! Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 37 - Protection by Surge Arresters and Representative Overvoltage Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 38 - Steepness is reduced inversely proportional to number n of connected lines: C0 C0 0 1 1 1S KK S = ≈ ⋅⋅ +A AA (for S0Æ ∞) C0 1S n K = ⋅ ⋅A A Considerations on steepness S – Impact of number of connected lines Sℓ ... steepness of surge after traveling distance ℓ in kV/µs KC0 ... corona damping constant in µs/(kV·m) ℓ ... traveling distance in m S0 ... initial steepness of surge in kV/µs (Explanation see next slide) Protection by Surge Arresters and Representative Overvoltage Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 39 - Considerations on steepness S – Impact of number of connected lines n = 1:n = 1: 2U0 Z UTr= → ∞−1 ZZ n =Tr 02U U n = 2:n = 2: 2U0 Z UTr= =−1 ZZ Z n = ⇒ = ⋅Tr Tr 0 0 1 2 2 2 2 U Z U U U Z n = 3:n = 3: 2U0 Z UTr= =−1 2 Z ZZ n = ⇒ = ⋅Tr Tr 0 0 1 2 2 3 3 U Z U U U Z … and when thevoltage amplitude is reduced, the steepness is reduced proportionally. Protection by Surge Arresters and Representative Overvoltage Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 40 - Practical observations on the relevant traveling distance ℓ : 1) Shielding failures do not occur in the first span adjacent to the substation. Reason: shielding is intentionally improved by lower shielding angles or double ground wires. 2) Back flashovers do not occur at the first tower(s) adjacent to the substation. Reason: low footing impedance due to connection to substation earthing. C0 1S n K = ⋅ ⋅A A Considerations on steepness S – Impact of number of connected lines Sℓ ... steepness of surge after traveling distance ℓ in kV/µs KC0 ... corona damping constant in µs/(kV·m) ℓ ... traveling distance in m n ... number of connected lines Protection by Surge Arresters and Representative Overvoltage The minimum value of ℓ is one span length Lsp.The minimum value of ℓ is one span length Lsp. ( )rp C0 sp t 1S n K L L = ⋅ ⋅ + Srp ... representative steepness of surge in kV/µs Lsp ... span length in m Lt ... overhead line length with the adopted return rate; in m ⋅t adopted return rate 1/a = shielding failure rate + back flashover rate 1/a m L Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 41 - Protection by Surge Arresters and Representative Overvoltage rp pl 2U U ST= + (from slide 35)S ... steepness of surge in kV/µsT ... travel time along distance L in µs ( )rp pl C0 sp t 12U U T n K L L = + ⋅ ⋅ + Introduction of a factor A describing the lightning performance of the OHL: C0 0 2A K c = ⋅ [IEC 60071-2] compare with slide 31, e.g.: 6 C0 µs0.6 10 kV m K −= ⋅ ⋅ Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 42 - Protection by Surge Arresters and Representative Overvoltage ( ) ( )0rp pl plsp t sp t cA A LU U T U n nL L L L = + = ++ + L ... distances a1 + a2 + a3 + a4 in m Assumed maximum value (worst case) by assuming the return rate equal to zero, i.e. Lt = 0: rp pl sp A LU U n L = + (To be used for convenience if the result gives satisfyingly low Urp) Note: n should reasonably be set to n = 1 (if only one line is connected) or n = 2 (if two or more lines are connected). Assuming n > 2 could yield too optimistic results that are not valid in a real failure scenario (e.g. possible loss of lines). Note: n should reasonably be set to n = 1 (if only one line is connected) or n = 2 (if two or more lines are connected). Assuming n > 2 could yield too optimistic results that are not valid in a real failure scenario (e.g. possible loss of lines). Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 43 - Protection by Surge Arresters and Representative Overvoltage rp pl sp 11000 kV 30 m825 kV 1238 kV 2 400 m A LU U n L = + = + ⋅ = Example: Um = 420 kV Æ Upl = 825 kV; A = 11000 kV (quadruple bundle); L = 30 m; Lsp = 400 m; ≥ 2 lines connected; shielding failure rate (typ. for Germany; one OHGW): 2.5 per 100 km and year = 2.5·10-5 (a·m)-1 adopted failure rate: 1·10-3 a-1 rp pl sp t 11000 kV 30 m825 kV 1200 kV 2 (400+40) m A LU U n L L = + = + ⋅ =+ LIWV = 1425 kV; 15% safety factor Æ allowed umax = 1211 kV 5 3 t 5 1 10 40 m 2.5 10 L − − ⋅= =⋅ a) using the "worst case" equation: 4 b) using the "realistic" equation: Note again: No effect of the lightning overvoltage amplitude!! Note again: No effect of the lightning overvoltage amplitude!! Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 44 - Protection by Surge Arresters and Representative Overvoltage Example: Um = 420 kV Æ Upl = 825 kV; A = 11000 kV (quadruple bundle); L = 30 m; Lsp = 400 m; ≥ lines connected shielding failure rate (typ. for Germany; one OHGW): 2.5 per 100 km and year = 2.5·10-5 (a·m)-1 adopted failure rate: 1·10-3 a-1 rp pl sp t 11000 kV 30 m825 kV 1031 kV 2 (400+400) m A LU U n L L = + = + ⋅ =+ LIWV = 1425 kV; 15% safety factor Æ allowed umax = 1211 kV 3 t 6 1 10 400 m 2.5 10 L − − ⋅= =⋅ Effect of double OHGW in span field adjacent to substation: shielding failure rate reduced by factor of 10, i.e. to 2.5·10-6 (a·m)-1 Note: these equations yield the representative overvoltages, which are not implicitly the real overvoltages (see next two slides)! Note: these equations yield the representative overvoltages, which are not implicitly the real overvoltages (see next two slides)! Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 45 - Protection by Surge Arresters and Representative Overvoltage Making use of breakdown voltage-time-characteristic of the insulation 0 200 400 600 800 1000 1200 1400 1600 1800 2000 0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 t [µs] U [ k V ] V-t air V-t SF6 1.5 MV/µs 1.0 MV/µs 0.7 MV/µs 0.5 MV/µs 3.0 MV/µs Steepness of overvoltage 0.3 MV/µs V-t-curves of 245 kV AIS and GIS equipment (LIWV = 1050 kV) The V-t-curve of GIS is flatter due to more homogeneous field distribution. Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 46 - Protection by Surge Arresters and Representative Overvoltage Making use of breakdown voltage-time-characteristic of the insulation Example: Um = 300 kV LIWV = 950 kV Upl = 550 kV Case 1: the representative overvoltage Urp is the real overvoltage as there is no time dependance of the V-t-curve. Case 2: the representative overvoltage Urp is lower than the real overvoltage, e.g. 650 kV. (The first voltage peak will not cause a dielectric breakdown.) The real overvoltage at the equipment's terminals, limited by the surge arrester, has oscillations due to traveling wave effects. 0 200 400 600 800 1000 0 5 10 15 Time in µs A m p l i t u d e i n k V 1 2 Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 47 - Very-Fast-Front Overvoltages • VFFO originate from disconnector operations or faults within GIS due to the fast breakdown of the gas gap and the nearly undamped surge propagation within the GIS. • Amplitudes are rapidly damped and front times increased when leaving the GIS through the bushing. • VFFO are usually not a concern or a dimensioning parameter for the hv insulation. Therefore no standardized test has yet been defined (and is not under consideration, either). • Mainly an EMI problem, as external electric fields may appear between the metal enclosure and ground Æ problem for secondary control circuits. Countermeasures: usual means of EMC. OHL VFFO measured in a GIS [ETG-93] (LS…circuit breaker; TR…disconnector, operated; D…bushing; OHL…overhead line Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 48 - Very-Fast-Front Overvoltages Occurrence of VFFO depends on type of disconnector: SF6 disconnecor, type A SF6 disconnector, type B Fachgebiet Hochspannungstechnik Overvoltage Protection and Insulation Coordination / Chapter 4 - 49 - Very-Fast-Front Overvoltages 10 -7 10-6 10 -4 10 -2 10 0 102 10 4 10 6 cont. service voltage DC-voltage temporary overvoltage slow-front overvoltage VFTO fast-front overvoltage 7 6 5 4 3 2 Û p.u. second 1 0 very-fast-front-overvoltage
Compartilhar