TABELA DE CONDUTORES III
 1º METODO : Condução de Corrente (A) 
 M. instalar Eletroduto Eletrocalha Livre-Shaft
 Tipo de Cabo PVC EPR PVC EPR PVC EPR
 (70ºC) (90ºC) (70ºC) (90ºC) (70ºC) (90ºC)
Seção(mm2) (A) (A) (A) (A) (A)
 1,5 13,5 18,5 15,5 20,0 17,5 22,0
 2,5 18,0 25,0 21,0 28,0 24,0 30,0
 4,0 24,0 33,0 28,0 37,0 32,0 40,0
 6,0 31,0 42,0 36,0 48,0 41,0 52,0 
 10,0 42,0 57,0 50,0 66,0 57,0 71,0
 16,0 56,0 76,0 68,0 88,0 76,0 96,0 
 25,0 73,0 99,0 89,0 117,0 96,0 119,0
 35,0 89,0 121,0 110,0 144,0 119,0 147,0 
 50,0 108,0 145,0 134,0 175,0 144,0 179,0 
 70,0 136,0 183,0 171,0 222,0 184,0 229,0
 95,0 164,0 220,0 207,0 269,0 223,0 278,0
 120,0 188,0 253,0 239,0 312,0 259,0 322,0
 150,0 216,0 290,0 275,0 358,0 299,0 371,0
 2º MÉTODO : MQTA (Máxima Queda de Tensão Admissível) 
 β (V/A.Km) 
 M. instalar Eletroduto Eletrocalha Livre-Shaft 
Tipo de Cabo PVC EPR PVC EPR PVC EPR
 (70ºC) (90ºC) (70ºC) (90ºC) (70ºC) (90ºC)
Seção ( mm²) (A) (A) (A) (A) (A) ( A ) 
 1,5 27,60 23,9 27,40 24,1 24,00 27,8
 2,5 16,90 14,7 16,80 15,0 14,80 17,3
 4,0 10,60 9,15 10,50 9,3 9,30 10,8
 6,0 7,07 6,14 7,00 6,2 6,30 7,1
 10,0 4,23 3,67 4,20 3,7 3,80 4,2
 16,0 2,68 2,33 2,70 2,35 2,40 2,7
 25,0 1,71 1,49 1,72 1,51 1,59 1,73
 35,0 1,25 1,09 1,25 1,10 1,19 1,26
 50,0 0,94 0,82 0,95 0,83 0,91 0,95
 70,0 0,67 0,59 0,67 0,59 0,67 0,67 
 95,0 0,50 0,44 0,51 0,44 0,52 0,50
 120,0 0,41 0,36 0,42 0,36 0,43 0,36
 150,0 0,34 0,31 0,35 0,31 0,36 0,31
 
 UNIP/GODINHO