11 Motor Protection � 2006 by Taylor & Francis Group 11.1 INTRODUCTION The prot ection of motors varies consi derably and is gener ally less standar d- ized than the protectio n of the othe r apparatu s or parts of the power system. This result s from the wi de variet y of siz es, type s, and appl ications of motors. The prot ection is pri ncipally based on the import ance of the motor, which usually is closely relat ed to the siz e. Th is chapter deals with moto rs and the protectio n appl ied directly to them. Backup often associated wi th the con- necting circui ts is discusse d in Chapter 9. The pres ent discussi on is for motors that are switched by a circuit breaker, contactors, or starters, and for which the protection is separate from these devices and from the motor. Essentially, this covers motors at the 480 to 600 V level and higher. Not covered specifically or directly are motors for which the protection is built into the motor or starter, or for which fuses are the only protection. 11.2 POTENTIAL MOTOR HAZARDS The potential hazards normally considered are 1. Faults: phase or ground 2. Thermal damage from a. Overload (continuous or intermittent) b. Locked rotor (failure to start or jamming) 3. Abnormal conditions a. Unbalanced operation b. Undervoltage and overvoltage c. Reversed phases d. High-speed reclosing (reenergizing while still running) e. Unusual ambient or environmental conditions (cold, hot, and damp) f. Incomplete starting sequence These are for induction motors, which represent the large majority of all motors in service. For synchronous motors, additional hazards are 4. Loss of excitation (loss of field) 5. Out-of-step operation (operation out of synchronism) 6. Synchronizing out of phase , LLC. These can be reclassified relative to their origins: � 20 A. Motor-induced 1. Insulation failure (within motor and associated wiring) 2. Bearing failure 3. Mechanical failures 4. Synchronous motors: loss of field B. Load-induced 1. Overload (and underload) 2. Jamming 3. High inertia (Wk2) C. Environment-induced 1. High ambient temperature 2. High contaminant level: blocked ventilation 3. Cold, damp ambient temperature D. Source- or system-induced 1. Phase failure (open phase or phases) 2. Overvoltage 3. Undervoltage 4. Phase reversal 5. Out-of-step condition resulting from system disturbance E. Operation- and application-induced 1. Synchronizing, closing, or reclosing out of phase 2. High duty cycle 3. Jogging 4. Rapid or plug reversing 11.3 MOTOR CHARACTERISTICS INVOLVED IN PROTECTION The primary motor characteristics available and involved in the protection are 1. Starting-current curves 2. Thermal capability curve, which should include the permissible locked-rotor thermal limit 3. The K constant (Rr2=Rr1) These characteristics normally are obtained from the motor manufacturer and are basic for the application of protection. Typical curves are illustrated in Figur e 11.1. The maximum start ing-current curve is at the rated voltage . Currents for lower voltages exist to the left, with the knee at a higher time level. The thermal limits are three different curves, which often approximately blend together to a general curve, such as that shown. Thermal limits are relative indeterminate zones that engineers desire to have represented by a specific curve. 06 by Taylor & Francis Group, LLC. Motor running Operating-overload thermal limit curve Accelerating thermal limit curve Permissible locked rotor time 0.9 V 1.0 V Starting current curve Asymmetrical Motor load current Locked rotor current Current per unit or amperes T im e in s ec on ds FIGURE 11.1 Typical induction motor characteristics. � 20 1. The higher-current portion indicates the permissible locked rotor times. This is the time the rotor can remain stalled after the motor has been energized before thermal damage occurs in the rotor bars, rotor end rings, or in the stator, whichever is the limit for a particular design. In very large motors this locked-rotor thermal limit can be lesser than the starting time, so these motors must start rotating instantly to avoid thermal damage. This curve is from locked-rotor current at full voltage to that current at the minimum permissible starting voltage. 2. The accelerating thermal limit curve from locked-rotor current to the motor breakdown torque current, which is about 75% speed. 3. The operating or running thermal limit curve, which represents the motor overload capacity during emergency operation. 06 by Taylor & Francis Group, LLC. 11.4 INDUCTION MOTOR EQUIVALENT CIRCUIT As an aid in the protectio n and for protect ion analysi s, the equi valent motor diag ram can be reduc ed as show n in Figure 11.2. Th e typical valu es for induc tion motors in per unit on the motor kVA or kV, as shown in Figure 11. 2b, are Rs and R r ¼ 0.01 pu, jXm ¼ j3.0 pu, and jX ¼ jX d 00 ¼ 0.15 pu, and from these, the typical lock ed rot or or sta rting current is Istarting ¼ 1 jX 00d ¼ 1 0:15 ¼ 6:67 pu: (11:1) Th is is the sym metrical valu e; the asym metrica l current is higher (see Figure 11. 1). Because the shunt jXm is high relative to the other impedances, the equivalent at the motor input reduces with the foregoing typical values to (a) (b) Rr + jXr Rs + j X s Input j Xm j Xm jXRs Rs = Stator resistance jXs = Stator leakage reactance at rated frequency Rr = Rotor resistance jXr = Rotor leakage reactance at rated frequency jZm = Shunt exciting impedance Input (zM1, zM2) RrS (1−S ) For negative sequence For positive sequence Rr S Rr 2 – S Synchronous RPM − Rotor RPM Synchronous RPM jX ≅ jXs + jXr ≅ jXd� = 0+ running = 1.0 stalled S = FIGURE 11.2 Equivalent-circuit diagrams for induction motors: (a) equivalent diagram for an induction motor; (b) simplified equivalent induction motor diagram. � 2006 by Taylor & Francis Group, LLC. ZM1 ¼ ZM2 ¼ 0:144 ff82:398: (11:2) or practically equal to jXd 00 ¼ 0.15 pu, as commonly used for a stalled motor (S¼ 1.0). If the motor is running (S¼ 0.01), the foregoing values give ZM1 ¼ 0:927 ff25:878 and ZM2 ¼ 0:144 ff84:198 pu: (11:3) Thus, practically, ZM1 ¼ 0:9 to 1:0 pu and ZM2 ¼ 0:15 pu: (11:4) From stalled to running, the positive-sequence impedance changes from approximately 0.15 to 0.9 or 1.0 pu, whereas the negative-sequence imped- ance remains essentially the same, at approximately 0.15 pu. Moreover, these are based on the rated motor kVA, which is approximately equal to the motor horsepower (hp). These values will vary with each individual motor, but these typical values are close and quite useful if specific data are not available. 11.5 GENERAL MOTOR PROTECTION Protection for motors exists in many forms: a variety of designs and either packaged individually or in different combinations. Each has its features, which will not be restated or evaluated in this chapter. The fundamentals and basic aim should be to permit the motor to operate up to, but not to exceed, its thermal and mechanical limits for overloads and abnormal oper- ation conditions and, to provide maximum sensitivity for faults. These can usually be achieved in general terms as follows. 11.6 PHASE-FAULT PROTECTION Instantaneous nondirectional overcurrent relays (50,51) can be used to protect induction motors. Faults generally provide current greater than the locked- rotor starting current, except for turn-to-turn faults. Considerable current can flow between turns, but unfortunately, very little evidence of this is available at the motor terminals until it develops into other types, phase-to-ground or phase-to-phase. The motor is the end device in the electrical system, so instantaneous relays can be used. There is no coordination problem. The induction motor backfeed to system faults is relatively small (1=Xd 00 þ offset) and decays rapidly in a few cycles; therefore, nondirectional relays can be applied. The CT ratios supplyingthese relays should be selected such that the maximum motor current provides between 4 A and 5 A secondary current. � 2006 by Taylor & Francis Group, LLC. Phase- instantane ous relays should be set well above the asym metrica l lock ed rotor and well b elow the minimum fault current. This can be equated whe re ILR , the locked rotor sym metrica l is ILR ¼ 1 X1S þ Xd 00 , (11 :5) whe re X1S is the total reactance (impedance ) of the powe r system or source to the mot or. This equatio n is similar to Equat ion 11.1, whe re the max imum starting or locked-rotor current is with a very large or infinite source, so X1S approaches zero. A fault at the motor is I3f ¼ 1 X1S (11:6) and for a phase-to-phase fault with X1S¼X2S, Iff ¼ 0:866 I3f ¼ 0:866 X1S : (11:7) If PR is the ratio of the relay pickup (IPU) to locked-rotor current, PR ¼ IPU ILR : (11:8) Typically, PR should be 1.6–2.0 or greater. If PF is the ratio of the minimum fault-to-relay pickup current, PF ¼ Iff min IPU : (11:9) Desirably, PF should be 2–3 or greater. From Equation 11.9 and Equation 11.8, Iff ¼ PFIPU ¼ PFPRILR and Iff ILR ¼ PFPR or I3f ILR ¼ 1:155PFPR (11:10) or the three-phase solid fault at the motor should be 1.155 PFPR or larger for good instantaneous overcurrent protection. If the minimum recommended values of PR¼ 1.6 and PF¼ 2, the three-phase fault should be 3.7 times the � 2006 by Taylor & Francis Group, LLC. locked rotor curr ent. If PR ¼ 2, PF ¼ 3, the thr ee-phase fault should be at least 6.9 time s larger than the locked rotor current. Equat ing Equat ion 11.7 and Equat ion 11.10 and substitut ing Equat ion 11.5 yields Iff ¼ 0: 866 X1S ¼ PF PR X1S þ X 0d , X1S ¼ 0:866 X 00d PF PR � 0: 866 : (11 : 11) Thus, with PR ¼ 1.6, PF ¼ 2, X1S ¼ 0: 866 X 00d (2 � 1: 6) � 0: 866 ¼ 0: 371 X 00d and with the stand ard X 00d ¼ 0.15, X1S ¼ 0 .056 pu, or with PR ¼ 2, PF ¼ 3, and X 00d ¼ 0.15, X 1S ¼ 0.025 pu. This defines the source impeda nce, which should be as indicated or less for instant aneous overcurrent protect ion. Th e per-uni t values in the exampl es are on the motor kVA, kV base, whe re kVArated ¼ (hor sepower )(0: 746) (efficiency) (power factor ) : (11 : 12) In many applicati ons, the source X1S for all practical purpos es is the reacta nce of the suppl y transf ormer, which is connec ted on its pri mary to a large utility, which is a relative ly infinite sourc e. Fu rthermor e, the suppl y transform er is generally supplying other loads and so is larger than any specific motor; consequently, its reactance on the motor base will tend to be small. This can be il lustrated with the exampl e of Figure 9.19, whe re a 2500 kVA transformer with 5.75% X is shown supplying an 800 A feeder. Suppose that this is a motor: then, 800 A at 480 V equals 665 kVA. At 665 kVA, the transformer reactance XT is 5.75(665)=2500¼ 1.53% or 0.0153 pu. Assuming that XT is basically equal to X1S, this is well below the 0.025 pu limit derived from Equation 11.11 to provide good instantaneous relay protection. If the recommended foregoing setting criteria of PR and PF cannot be met, or when more sensitive protection might be desired, the instantaneous relay (or a second relay) can be set more sensitively if delayed by a timer. This permits the asymmetrical starting component to decay out. A typical setting recommendation for this is a PR of 1.1–1.2 with a time delay of 0.10 sec (six cycles at 60 Hz). A similar setting can be used if the applied instantaneous relay is insensitive to the offset component of fault current. Many modern microprocessor based relays are designed to meet this requirement. � 2006 by Taylor & Francis Group, LLC. If, on loss of volt age, runni ng motors are transferr ed from a bus to a hot bus, or if high-spe ed system reclosi ng reenergize s motors befor e their residua l volt age attain s a drop to about 33 % rated, very high transi ents can occur. Th ese curr ents are v ery hard on motors unless specifica lly desi gned for them. Ca reful attenti on must be give n to set the relays above this transi ent if the condi tion is tolerable. When the foregoi ng crite ria indicate that there is not suff icient margi n betwee n locked-r otor and fault current, differentia l p rotec- tion is indicat ed. 11.7 DIFFERENTIAL PROTECTION Diff erential protectio n (87) is preferred. Howeve r, for som e motors the two ends of the windings may not be available , and different ial protectio n cannot be applied . If both ends of the wind ings are available , the best differ ential, in terms of sensitivity, speed, and security, is to pass the conductors of the windings through a flux summation (ring) CT, as shown in Figure 11.3a. Th ese CTs are describ ed in Chapte r 5 and als o applied for smaller generator Motor Motor A B C A B C R R R R R R OP OP OP Circuit breaker (a) (b) 87 87 87 52 FIGURE 11.3 Differential protection for motors where the neutral leads are available: (a) with flux summation (ring)-type CTs and instantaneous overcurrent relays (50); (b) with conventional-type CTs and differential relays. � 2006 by Taylor & Francis Group, LLC. protectio n in Chapte r 8. Ty pical maximum openi ngs or window s in thes e CTs are about 8 in. in diameter . With a fixed ratio of 50:5 and a sensit ive instantane ous overc urrent relay (50) , the com bination can provide a pickup of n early 5 A prima ry curr ent. Th is is a flux-ba lancing differ ential, inde pend- ent of load and starting current mag nitudes and with only one CT per phase, so that matching CT perf ormance does not exist. Internal phase and ground protectio n is provided wi thin the motor and u p to the CT location. Other protectio n is require d for the connections to the circui t brea ker, sta rter, and so on. Th e limit ation is the size of the conduc tor in relat ion to the CT opening. Con ventional different ial with CTs in the neut ral and output leads should be applied where the flux sum mation type cannot be used. Nor mally, the two sets of CTs would be of the sam e type and ratio, so conven tional 87 tw o- restraint different ial relays are applica ble, as illustrate d in Figure 11.3b. With the equal CT ratios, the secondary currents through the relay restra int wi nd- ings (R) would be essential ly the same for all external faults and load and the operating current (O P) would be from a very small value to zero . For mot or faults between the two sets of CTs, all of the fault current flo ws through the (OP) operating winding for high sensit ivity to both phase and ground faults. The line-side CTs should b e as show n, so that the different ial zone includes the circuit brea ker, connec ting leads, as well as the motor. 11.8 GROUND-FAULT PROTECTION As for phase protectio n is concerned , instantane ous overc urrent relays are applied for ground -fault protectio n (50G, 50N, 51N). Wher e applicable , the preferred method is to use a flux summatio n-type current transf ormer, with the three mot or conductor s passing throu gh the CT openi ng. This provides a magnetic summation of the three-phase currents so that the secondary output to the relay is zero-sequence (3I0) current. This is shown in Figure 11.4a. The CT ratio, commonly 50:5, is independent of motor size, whereas the conven- tional CTs in the phases must be sized to the motor load. The advantage is high sensitivity with good security, but is limited by the conductor size that can be passed through the CT opening. As indicated in the preceding section, typical sensitivity is 5 amperes primary current. For larger motors and conductors, a ground relay in the neutral must be used as in Figure 11.4b. Although the load influences the CT ratios, the ground relay can be set sensitively and well below motor load. 50N must be set above any ‘‘false’’ residual current that can result from the unequal performance of the three CTs on high, unequal-offset, starting currents.This is difficult to predetermine, but the probability of a problem is very low if the phase burdens are balanced and the CT voltage developed by the maximum-starting current is not more than 75% of the CT accuracy class voltage. A lower 50N relay tap and consequent higher burden may help by forcing all three CTs to saturate more evenly. The resistance in the neutral � 2006 by Taylor & Francis Group, LLC. Motor Phase relays Conventional type CTs Ring-type CT A B C (a) (b) 50 51 50 51 50 51 Ground relay 50G 50N Motor Phase relays Ground relay Conventional type CTs A B C 50 51 50 51 50 51 FIGURE 11.4 Ground overcurrent protection for motors: (a) with the three conductors passed through a flux summation-type current transformer; (b) with conventional-type current transformers. circui t may also be of help . Th is increased burden, howe ver, should not be large enough to significa ntly inhibi t the relay sensitivity . Th ese latter ‘‘fixes ’’ are used generally aft er trouble is encoun tered during sta rt-up. Time delay coul d be used until the offset has decay ed, but this dela ys trippi ng for actual faults. With ground -fault limiting, as is com mon in suppl y system s for mot ors, the ground -fault current will be smaller than that for phase faults. If high- resist ance ground ing is used (see Chap ter 7), ground-fa ult curr ents wi ll be in the order of 1–10 A primary. The protection as shown in Figure 11.4a can provide reasonable sensitivity for these systems if the ground-fault current is greater than 5 A. Considerably more sensitive protection can be obtained by the application of a product overcurrent relay (32N). This general type was � 2006 by Taylor & Francis Group, LLC. described in Section 9.17. For thi s appl ication, a relay with a current coil and a voltage coil is used. It operate s on the produc t of voltage times current and for use in high-re sistance, ground ed systems; the maximum torque occurs when the current lea ds the voltage by 45 8 . The curr ent coil is connecte d in the neutral of the CTs in place of 50N of Figur e 11 .4b, and the voltage coil acro ss the ground ing resistor and in para llel with 59G in Figure 7.9 or Figure 7.10. The pola rity is that the relay will operate when zero-se quence current flows into the motor. As indicated in Chapter 7, the current in high-re sistance grounding is low, but the zero -sequence voltage is high. Typical pickup for this produc t o vercurrent relay is about 7–8 mA with 69 .5 V. This is well below the ground -fau lt leve ls of 1–10 A. 11.9 THERMAL AND LOCKED-ROTOR PROTECTION This protectio n involves the application of relays (49–51 ) to closel y match the thermal and lock ed-roto r curve s of Figure 11.1. Howeve r, it should be remember ed that these motor thermal curves are appro ximate represe ntations of therm al damage zones for gener al or no rmal operation . Th e relays should operate just before the limits are reached or excee ded. Ove r many years, this is accomplis hed by therm al relays to match the thermal-lim it curve s, and inverse -time–ove rcurren t relays for lock ed-roto r protectio n. This prot ection, designed and packa ged in various way s, provi des very good p rotection for mos t motors. Typic al applicatio ns to the motor characterist ics shown in Figur e 11.1 are illus trated in Figur e 11.5. Thermal relays are available in several forms: � 20 1. A ‘‘replica’’ type, where the motor-heating characteristics are approxi- mated closely with a bimetallic element within a current heater unit. These operate only on current. 2. Relays operating from exploring coils, usually resistance temperature detectors (RTD), embedded in the motor windings. These operate only on winding temperature, and the detectors are placed in the motor by the designer at the most probable hot spot or danger area. These are common in motors from about 250 hp and higher, but may not be installed in some motors unless specified. 3. Relays that operate on a combination of current and temperature. Care should be exercised to ensure that there are no operating conditions that may not be covered with the combinations, when both are required for relay operation. High current and high temperature normally indicate problems, but high current without measurable high temperature might exist for overheating in the rotor, bearings, drive machine problems, and in the controllers or connections. For these, the combination may provide limited to no protection. 06 by Taylor & Francis Group, LLC. Time in seconds Thermal relays 49 Overcurrent relay 51 Motor starting curve, Figure 11.1 Instantaneous relays 50 Current in primary motor amperes Motor thermal limit curve, Figure 11.1 FIGURE 11.5 Typical overload, locked-rotor, and fault protection for a motor. The comparison of motor-starting and inverse-time–overcurrent relay curves on the same plot, as is commonly done and shown in Figure 11.5, can provide false information. This may occur where the space between the starting current and locked-rotor limit is very narrow, which is usual for very large motors. Often in these situations, it appears possible to set the overcurrent relay so that its characteristic is above the motor start curve and below the locked-rotor limit, only to discover in service that the overcurrent relays operate under normal start. As a matter of fact, the curves for motor starting and relay operation are two quite different characteristics. The motor-starting curve is a plot of the changing current with time from locked-rotor or starting condition to the motor-load-operating current. The relay characteristic represents the operat- ing times for different constant-current values. With the overcurrent relay normally set at about one-half locked-rotor current or less, it begins operation � 2006 by Taylor & Francis Group, LLC. at the moment the motor is ener gized. Unless the starting current drops belo w the relay pickup befor e the relay time s out, it will initiate undesi rable tripping. Relay-ope rating times for v ariable current are not directly availa ble from its time char acteristic . This is a comple x calcul ation, but manufac turers h ave developed criteri a for indivi dual relays. The micro processor -type relays pro- vide better protectio n (see Section 1 1.16). 11.10 LOCKED-ROTOR PROTECTION FOR LARGE MOTORS (21) As indicat ed, the perm issible locked-r otor curr ent can be very clos e or lesser than the start ing current . In gener al, this occurs for very large modern motors. The prot ection for this can be a zero -speed swit ch built into the motor. If the motor does no t accele rate on energiz ation to open or operate the swit ch in a prescribed man ner, the supply circuit is opened . The concerns with usin g this type of protect ion are that the motor coul d sta rt and lock up at less than full- load speed; the other concern is difficul ty of tes ting and maint enance. Prot ection for locked rot ors can be obta ined by appl ying a distance relay, as describ ed in Chapter 6. The rel ay is set looking into the motor (Figure 11.6). The ratio of system voltage and starting current is an imped- ance, which can be determined and plotted as a vector on the R–X diagram. From a specific value at start, it increases in magnitude and changes phase angle as the motor accelerates. The distance 21 relay is set so that its MHO Vac 52a 52 21 VT DC 21 Bus Motor 62 62 Trip Locus of motor impedance during start 21 Operate area within circle x R FIGURE 11.6 Locked-rotor protection with a distance (21) relay and timer. � 2006 by Taylor & Francis Group, LLC. opera ting circle encloses the locked-rot or im pedance vector. When the motor is ener gized by clos ing breaker 52, the distanc e 21 relay operates and the time r 62 is energiz ed. By usin g an ac-opera ted timer, variabl e time with volt age is obta ined to match the longe r permissible lock ed-roto r time s at low er voltage . The heavy start ing current can cause the voltage to drop mom entarily duri ng the starting peri od. If the start is succe ssful, the im ped- ance phasor moves out of the 21 operating circle before the 62 timer cont act clos es. If the start is unsuccess ful, the impedance vector stays in the circle, and when timer 62 opera tes, the trip is initiat ed. The timer is set as dete rmined by the permi ssible lock ed-rotor time curve from full voltage to about 75 % or 80 % voltage . Th is protectio n does not cover failure to accele rate to full speed, nor to pull out with the rotation still cont inuing. 11.11 SYSTEM UNBALANCE AND MOTORS Th e mos t common cause of unbalance for thr ee-phase motors is the loss of phase resu lting from an open fuse , connec tor, or conduc tor. Unbalances in othe r connec ted load s can als o aff ect the motor. A voltage unbalance of 3.5 % can produc e a 25 % or greater increas e in mot or temper ature. Th is results primari ly from negativ e sequence produced by the unbal ance. This curr ent produces flux in the motor air gap rotating in the opposi te direct ion to the actual motor dir ection. The relative effect is esse ntially doubl e-frequ ency current in the rot or. Skin effect resu lts in higher resistanc e, and as outlin ed in Section 11.4, negat ive-seq uence impeda nce remains esse ntially at locked-r otor value. Thus, high current and high resistanc e com pound the heating effect. The total heating in a mot or is propor tional to I 21 t þ K 22 t , (11 :13) whe re I1 and I 2 are the posi tive- and negativ e-sequenc e curr ents, respective ly, in the motor and K ¼ Rr2 Rr1 ¼ conservative estimate as 175 I2 LR , (11:14) where Rr1 and Rr2 are the motor rotor positive- and negative-sequence resistances, respectively, ILR the locked-rotor current in per unit. Equation 11.13 shows that there is a high increase in heating from the negative-sequence component. The symmetrical components network for an open phase is shown in Figur e 11.7. Th is is a simplifie d circuit show ing the total source system as lumped impedances ZS1¼ ZS2. For any specific case, this circuit can be expanded to show more detail of the source or other loads. The supply transformer, for example, can be represented by its reactance (impedance) XT. � 2006 by Taylor & Francis Group, LLC. Open Other loads if present x y MotorSystem ZS1 = ZS2 Positive sequence Negative sequence ZS1 ZS2 IS1 IM1 IM2 IS2 x y x y ZM1 N1 N2 VS V2S V2M ZM1 ZL1 ZL2 ZM2 + + + ZM2 FIGURE 11.7 Simplified symmetrical component representation for an open phase. For an open phase betwee n the transf ormer and mot or, XT would be added in series with the sourc e impeda nces for the equival ent values of ZS1 and ZS2 . When the open phase is b etween the system and the transf ormer, XT would not be included in the sourc e equival ents, but added in series with the mot or impedance. This circui t is for an ungrou nded motor, as is the com mon practice. The zero -sequence networ k is not involved for one-p hase open, unless the systems on either side of the open are both grounded. The distribut ion of current s for an open ph ase using the network of Figure 11.7 is show n in Figure 11.8 for several situatio ns. Typic al per unit valu es of impedances shown are all on the motor kVA base, and are ZS1 ZS2 ¼ 0: 05 ff90 8 pu, ZL1 ¼ Z L2 ¼ 1: 0ff15 8 pu for static load s at the motor, ZM1 ¼ 0: 9ff25 8, ZM2 ¼ 0: 15 ff85 8: (11 : 15) These angles were include d in the calcul ations, but the simpl ification o f assuming all impeda nces at the same angl e gives close appro ximation s and � 2006 by Taylor & Francis Group, LLC. Is2 Is1Is1 = −Is2 = 0.96 �37.238 Is1 = −Is2 = 1.60 �40.178 Vs = 1 08 N1 IM1 IM1 IM1 IL1 IL1 IM2 IM1 = −IM2 N2 (a) (b) (c) 0.05 908 0.9 258 � Is2 Is2 Is1 Is1 IM2 = �1.51 �47.818 N1 N1 IM2 IM2 IM1 = 0.846 �44.918 IM2 = �0.120 36.308 IM1 = 1.076 23.588 IL2 = �0.227 22.198 IL1 = 0.762 �34.918 IL2 = �0.481 32.558 IL1 = 0.481 32.558Is2 = �0.361 31.308 Is1 = 1.55 �26.358 N2 N2 1.0 158 IL2 IL2 0.15 858 � � Vs = 1 08 Vs = 1 08 0.05 908 0.05 908 0.05 908 0.05 908 0.05 908 0.9 258 0.9 258 0.15 858 1.0 158 1.0 158 1.0 158 0.15 858 = 0.96 �37.238 FIGURE 11.8 Positive- and negative-sequence currents for an open-phase supply to a motor with and without associated static load. Values in per unit on the motor base: (a) open-phase sequence currents with motor only; (b) open-phase sequence currents with static load on motor bus, phase open on system side of motor; (c) open-phase sequence currents with static load on the motor bus, phase open between motor and the load. does not change the trends shown. With all values at 908, for example, IS1¼ 0.87 pu instead of the 0.96 pu in Figure 11.8a. From these sequence currents, it is observed that on either side of the open Ia¼ I1þ (�I2)¼ 0 correctly. The sound phase currents are Ib ¼ a2I1 þ aI2 ¼ �j ffiffiffiffiffiffi 3I1 p Ic ¼ aI1 þ a2I2 ¼ þj ffiffiffiffiffiffi 3I1 p ) when I1 ¼ �I2 (11:16) so in Figure 11.8a, Ib and Ic currents are 1.66 pu. Thus, it is seen that an open phase provides very low-phase currents relative to the normal motor-load current of about 1 pu; consequently overcurrent relays are not adequate to detect an open phase. � 2006 by Taylor & Francis Group, LLC. When static load is connec ted in parallel with the motor, as show n in Figure 11.7 and calculat ed in the exam ples of Figure 11.8b, the cont inued rotation of the motor gener ates a voltage on the opened phase . This continues to energiz e the load connec ted to this phase. The power is transferr ed acro ss the motor air gap and reduces the motor shaf t power so that pullout may occur. One exam ple that is indicated show s that the motor woul d pull o ut at 20 % of rated load, with static load three times larger than the motor load; or at 50% of rated load, with static load equal to the motor load. In addi tion, the low value of the mot or negat ive-sequence impeda nce implies that a large portion of negative-s equence current flows in the motor to increase h eating. This d istri- bution is illustr ated in Figur e 11.8 b. Th e mot or negat ive-sequence current can be low, as shown in Figur e 11.3c, only whe n the static load is single phased. The funda mental for an open phase is that the posi tive- and negativ e- sequence current s are equal and opposi te as long as zero sequence is not involved . This is usef ul to develop the un balance current s through wye–d elta transformer banks. These, as well as the cal culations in Figur e 1 1.8, are for the conditions immedia tely after the phase o pens and before the motor slows down, stalls, or its internal impedan ces change , and so on. The curr ents for an open phase on the primary side of a delta–wye transformer supplyin g a motor are show n in Figur e 11.9, and in Figure 11.10 for the o pen phase on the secon dary motor side. As developed in Chapter 3, if posi tive-seque nce current is shifte d 30 8 in one direct ion through the bank, the negative-sequence current shifts 308 in the opposite direction. The current directions shown in the circuit diagram for these two figures are correct for the phasor diagrams. Without these specific phasor diagrams, the IB in Figure 11.9 could be shown into the motor as indicated, but at ffiffiffi 3 p magnitude with IC at ffiffiffi 3 p flowing to the source. This is actually the flow, and is indicated in Figure 11.9 by the phasor diagram, showing that IB flows as indicated, but IC is 1808 from IB, both at ffiffiffi 3 p magnitude. If IB and IC were shown in opposite directions in the circuit diagram, the correct phasor dia- gram would be to show IB and IC in phase. These currents can be traced through the transformer with the unbalances indicated, recalling that 1.0 pu currentin the wye winding appears as 0.577 pu current in the delta winding. Negative-sequence voltage can be used to detect unbalance in motor circuits. By fundamental definition V2¼�I2Z2. With reference to the ex- ample of Figure 11.8, the per-unit negative-sequence voltages on the two sides of the open phase for situations a and b would follow. For situation c, V2S¼V2M because there is no open phase between the supply and the motor. Case A Case B V2S ¼ 00.96� 0.05¼ 0.048 1.6� 0.05¼ 0.08 V2M ¼ 00.96� 0.15¼ 0.144 1.5� 0.15¼ 0.227 � 2006 by Taylor & Francis Group, LLC. Open phase A A (a) Source IA Ia Ib a Ic b b a c c Motor IB IC B B C C Transformer IA1 Ia1 Ib1 Since Then Ic1 IB1 IC1 1.0 1.0 IC2 Ib2 Ia1 lags IA1 30� Ia 2 leads IA 2 30� Ia2Ic2 IB2 IA2 1.0 1.0 Ic = 2.0 Ic1 IC1 IC2 IC = 1.73 IA1 IA2 IA = 0 IB1 IB2 IB = 1.73 Total current flow (d) (c) (b) Negative sequence currents after the phase opens Positive sequence currents before and after phase opens Ib1 Ic2 Ib2 Ia2 Ia1 Ia = Ib = 1.0 FIGURE 11.9 (a) Unbalanced current flow through a delta–wye transformer bank to a motor for phase A open on the source side. (b) Positive-sequence currents before and after phase opens. (c) Negative-sequence currents after the phase opens. (d) Total current flow. � 2006 by Taylor & Francis Group, LLC. When the open phase is downstream or betwee n the V2 measur ement and the motor, the negat ive-sequence voltage relay will ‘‘see’’ V2S , which can be quite low because of the low-impedan ce sourc e. When the open phase is upstream or betwee n the V2 mea sureme nt and the supply, the relay will ‘‘see’’ V2M , whi ch is generally larger. Th us, negat ive-seq uence voltage is most usef ul for upstrea m open phase s, wi th phase -curren t comp arison for the downstream ones. 11.12 UNBALANCE AND PHASE ROTATION PROTECTION As suggeste d in Sect ion 11.11, there are sever al handles avai lable for unbal - ance detection: (1) magnitude differences between the three-phase currents, (2) the presence of negative-sequence current, and (3) the presence of nega- tive-sequence voltage. All three are used for protection. Open phase A A (a) IA Ia Ib a Ic b (b) Positive sequence currents before and after phase opens b a c c Motor IB IC B B C C Transformer source IA1 Ia1 Ib1Ic1 IB1 IC1 1.0 1.0 FIGURE 11.10 (a) Unbalanced current flow through a delta–wye transformer bank to a motor for phase A open on the motor or secondary side. (b) Positive-sequence currents before and after phase opens. (Continued on next page.) � 2006 by Taylor & Francis Group, LLC. IC2 Ia2 Ib2 Ic2 IB2 IA2 IB = 2.0 IC1 Ic1 Ic2 Ic = 1.73 Ia1 Ia = 0 Ib1(d) Total current flow Since IA1 leads Ia1 by 30� then IA2 lags Ia2 by 30� (c) Negative sequence currents after the phase opens Ib2 Ib = 1.73 IB1 IC2 IB2 Ia2 IA2 IA1 IA = IC = 1.0 FIGURE 11.10 (continued) (c) Negative-sequence currents after phase opens. (d) Total current flow. The current balance type (46) compare s the phase curr ent magnit udes and opera tes when one phase curr ent is sign ificantly different in magnit ude from either of the other two ph ase currents. This is very eff ective protect ion for indi vidual motor feed ers to detect open phases or unbal ances in that circui t. If othe r load s are suppl ied by the circuit to which this protect ion is connec ted, care shoul d be take n to ensur e that any open phase or unbal ance would not be cam ouflaged by the balanced current to the sound load . One relay should be appl ied for each load or feeder. Th e typi cal minimum sensit ivity of these relays is about 1 A in one phase with zero current in the o ther, or 1.5 pu in one phase and 1 pu in the other. Another type (46) resp onds to the negat ive-sequence curr ent, either in- sta ntaneously with a fixed time delay added, or fol lowing the I2 2t ¼ K char ac- teris tic, as used for generat or protectio n. These type s of relays are not widely appl ied for motor protectio n. The negativ e-sequenc e voltage type (47) is recomm ended to dete ct phase unbalance and phase reversal in the supply or source circuits. Ideal operating sensitivities are about 0.05 pu V2. One such relay should be connected through VTs (either wye–wye or open-delta VTs) to each secondary supply bus. As show n in Section 11.11, sufficien t V2 voltage is generally available for open phase in the source or upstream system. They should not be applied � 2006 by Taylor & Francis Group, LLC. for open-phase downstream or between the relay and motor, for as indicated, this V2 voltage may be quite low. When the phases are reversed, 1 pu V1 becomes 1 pu V2, so the negative- sequence relay certainly responds to phase reversals. Phase-reversal relays also are available that are equivalent to a small motor. Normal phase rotation produces restraint or contact-opening torque, whereas phase reversal causes operation or contact-closing torque. 11.13 UNDERVOLTAGE PROTECTION Low voltage on a motor results in high current and either failure to start, to reach the rated speed, or to lose speed, and perhaps pull out. Very often, protection for undervoltage is included as part of the motor starter, but an inverse time undervoltage relay (27) is recommended to trip when prolonged undervoltage exists and as backup. 11.14 BUS TRANSFER AND RECLOSING When motors, either induction or synchronous, are reenergized before they have stopped to rotate, high transient torques can result, with possible damage or destruction. This can occur when a rapid transfer of motors is made from a bus that has lost voltage to a live auxiliary bus. Such transfers are necessary to maintain vital services to the auxiliaries supplying large generating plants or to critical industrial processes. Another example is industrial plants supplied by a single-utility tie. Problems in the utility will require opening of the tie. Most experiences indicate that many faults in the utility are transient, resulting from lightning induction, wind, or tree contacts. As the utility is anxious to restore service promptly to its customers, the utility frequently uses high-speed reclosing (about 0.20–0.60 sec), and thus reenergizes the motors, with possible damage. The safe limits for reconnection of motors are complex and beyond this chapter’s scope. If rapid transfer is mandatory, special attention should be given to this during the design stage. Otherwise, the best policy is either to delay reclosures that reenergize induction motors, or to ensure that the motors are quickly disconnected from the system. For induction motors, reenergization should not occur until the motor voltage has dropped to 33% or less of normal. For synchronous motors, reclosing or reenergizing must not be permitted until proper resynchronization can be effected. This means opening the motor supply promptly on the loss of supply. An effective means to open the supply breaker under these conditions is the application of an underfrequency relay. Ideal underfrequency relay (81) setting would be 98%–97% of rated, with time to override the momentary voltage dip effects, but before reenergization can take place. If the plant has local generation, or there are other ties with generation of the supply feeder, � 2006 by Taylor & Francis Group, LLC. care should be take n to ensur e that the frequenc y declines on loss of the utili ty. Gen eration suffic ient to maint ain load , particula rly at light- load peri ods, resu lts in negligibl e frequ ency change . 11.15 REPETITIVE STARTS AND JOGGING PROTECTION Star ting motors repe titively with insu fficient time betwee n these starting time s, or opera ting them with extrem e load v ariations (joggin g), can result in high motor temper atures. It is possi ble for a high temper ature to follow a short-ti me load peak with subse quent low current load in norm al operation and not excee d the motorlimit s. Thermi stors on smaller motors and an inte- grat ing ther mal overload unit respondi ng to total heating (see Equation 11.13 ) for larger motors provide a means of protection. Relays (49) operating on both overcurrent and temperature have been used. They operate with high current and high temperature. A high temperature without overload or a high over- load without high temperature may not cause operation. Application of these requires careful analysis of the motor. However, the microprocessor units can monitor this effectively. 11.16 MULTIFUNCTION MICROPROCESSOR MOTOR PROTECTION UNITS Microprocessor motor protection units combine the various protection tech- niques for motor protection, as covered earlier, along with control, data collection and reporting (either locally or remote), and self-diagnostic fea- tures. The basic protection is essentially the same as has been provided over many years with individual relays. Thermal protection using thermal replica or RTD-type relays has been the most imprecise part, and the microprocessor units offer significant improvement. However, it should always be remem- bered that although microprocessors are very accurate, thermal limits are not precise. Designers can provide safe- or dangerous-operating zones, but it is difficult to supply a single curve as per the desire and demand of engineers. The microprocessor unit establishes electrical, thermal, and mechanical models that are derived from the input current, voltage, manufacturers’ motor data, and optionally RTDs within the motor. These models are used in the microprocessor algorithms to provide protection that is modified with time. Some of the features that are available in modern microprocessor based relays that are designed to enhance the level of protection available for motor protection include the following: � 20 1. Multiple set points that include setting of alarms in addition to tripping functions. For example, temperature-sensing devices may be set at a value that is below the insulation class level to provide alarms when 06 by Taylor & Francis Group, LLC. � 20 temperat ures excee d the expec ted full-load temperat ure rise leve ls. Trip set tings can be set at a temper ature correspo nding to the insula- tion class level or above depend ing on the critica lity of the proce ss served. 2. Logic to p revent overh eating caused by excessi ve starts in a given period. Settings for the numb er of starts and period are set based on the recommend ations of the man ufacturer. 3. ‘‘Smart’’ therm al overload protectiv e eleme nts that can track the real- time thermal capac ity of the motor and factor in such things as the effect of motor speed on the amo unt of cool ing provided. 4. Logic to prevent mot or start ing whe n v oltage is too low to assur e a successfu l start. 5. Wide setting ranges, program mable time –overcurr ent curves, multiple setting groups , and program mable logic allow protect ion to be custom - ized to fit the speci fic char acterist ics of the motor protected. 6. Better moni toring of motor performanc e is allow ed by providi ng a full line of metering and oscillog raphy capab ility. 11.17 SYNCHRONOUS MOTOR PROTECTION The prot ection discusse d in the foregoi ng for induc tion motor protect ion is applicable to synchro nous motors , with addition al prot ection for the field and for async hronou s operatio n. These motors usually include control and pro- tection for starting, field application, and synchroni zing. In addi tion, the following protect ion should be applied or consider ed. As illustr ated in Figur e 8.16, reductio n or loss of exci tation requires reactive power from the power system ; thus , lagging current flows into the motor. For small units, a power factor relay (55) is reco mmende d. Th is relay operates whe n current into the motor lags more than 308 . The usual max imum current sensit ivity occur s when the curr ent lags 120 8 , so a larg e curr ent is required for typi cal loss of field lagg ing currents o f 30–90 8. For large syn- chronous motors, distance loss-of-field relays, as described for generators, are recommend ed (see Sect ion 8.11). This provides improv ed p rotection for partial loss of field in addition to complete loss. Out-of-step protection may or may not be required, depending on the system and motor. Faults in the system that momentarily reduce the motor voltage may cause the voltage angles between the system and motor to swing apart sufficiently that, on fault clearing, the motor cannot recover and so will go out of step. If the motor is running synchronously, only DC voltage exists in the field or exciter windings. When it falls out of step from system disturbances or loss of field, ac voltage appears, which can be used to detect these conditions if the machine has brushes. With modern brushless exciters, the power factor relay (55) will provide both pullout and loss-of-field protection. 06 by Taylor & Francis Group, LLC. (a) (b) Bus Bus 52 52 47 47 87 49 49 50 50 51 51 46 46 50N 50N 50G 50G Ring- type Ct Ring- type CT Motor Motor RTD Alternate to 50G Alternate to 50G 27 27 VTs VTs CTs CTs CTs Notes: 1. The circles indicate functions that may be packaged individually or in various combinations. 2. Additional protection for synchronous motors covered in section 11.16. 3. Protection to avoid re-energization after short-time interruptions covered in section 11.14. 49 May operate on either current or RTD or by combination of both. Differential scheme of Figure 11.3a preferred if applicable CTs FIGURE 11.11 Typical recommendations for motor protection: (a) for motors with- out neutral leads and RTDs available; (b) for motors with neutral leads and RTDs available. � 2006 by Taylor & Francis Group, LLC. 11.18 SUMMARY: TYPICAL PROTECTION FOR MOTORS Typical protectio n recommend ed and com monly appl ied for the prot ection of motors is sum marized in Figur e 11.11. The applicatio n of the variou s relays is covered in the foregoing. These are general recommendations, recognizing that any specific application may be used more or less depending on local circumstances, economics, and individual preferences. 11.19 PRACTICAL CONSIDERATIONS OF MOTOR PROTECTION A general problem that has existed over the years with regard to motor protection is the lack of availability of complete data on the system driven by a motor to the protection engineer. Electrical engineers responsible for speci- fying and setting motor protection frequently do not communicate with the mechanical engineers who are familiar with the nature of the loads that are driven. As a result, motor protection is often applied on the basis of best estimates, standards, and on motor name-plate data. If the motor trips during starting conditions, the setting is increased in small steps until nuisance trips subside. This practice may be satisfactory for small, general-purpose applica- tions in which investment is small and the process is not critical. However, for larger or more critical applications, the protection engineer should make every effort to understand the details of the loading conditions that are connected to the motor as well as the operating characteristics of the motor, so that the related protection can be properly specified and set to minimize the potential for damage to the motor or shutdown of the process that it serves. Oscillography capability provided by many modern microprocessor relays provides an effect- ive tool for obtaining pertinent data during the process of placing a facility in service and while functioning during normal in-service conditions. BIBLIOGRAPHY ANSI=IEEE Standard C37.96, Guide for AC Motor Protection, IEEE Service Center. Brighton, R.J. Jr. and Ranade, P.N., Why overload relays do not always protect motors, IEEE Trans. Ind. Appl., IA 18, November–December 1982, pp. 691–697. Dunki-Jacobs,J.R. and Ker, R.H., A quantitative analysis of grouped single-phased induction motors, IEEE Trans. Ind. Appl., IA 17, March–April 1981, pp. 125–132. Gill, J.D., Transfer of motor loads between out-of-phase sources, IEEE Trans. Ind. Appl., IA 15, July–August 1979, pp. 376–381; discussion in IA 16, January– February 1980, pp. 161–162. Lazar, I., Protective relaying for motors, Power Eng., 82, No. 9, 1978, pp. 66–69. Linders, J.R., Effects of power supply variations on AC motor characteristics, IEEE Trans. Ind. Appl., IA 8, July–August 1972, pp. 383–400. � 2006 by Taylor & Francis Group, LLC. Regotti, A.A. and Russell, J.D. Jr., Thermal limit curves for large squirrel cage induction motors, IEEE Joint Power Generation Conference, September 1976. Shulman, J.M., Elmore, W.A., and Bailey, K.D., Motor starting protection by imped- ance sensing, IEEE Trans. Power Syst., PS 97, 1978, pp. 1689–1695. Woll, R.E., Effect of unbalanced voltage on the operation of polyphase induction motors, IEEE Trans. Ind. Appl., January–February 1975, pp. 38–42. � 2006 by Taylor & Francis Group, LLC. Table of Contents Chapter 011: Motor Protection 11.1 Introduction 11.2 Potential Motor Hazards 11.3 Motor Characteristics Involved in Protection 11.4 Induction Motor Equivalent Circuit 11.5 General Motor Protection 11.6 Phase-Fault Protection 11.7 Differential Protection 11.8 Ground-Fault Protection 11.9 Thermal and Locked-Rotor Protection 11.10 Locked-Rotor Protection for Large Motors 11.11 System Unbalance and Motors 11.12 Unbalance and Phase Rotation Protection 11.13 Undervoltage Protection 11.14 Bus Transfer and Reclosing 11.15 Repetitive Starts and Jogging Protection 11.16 Multifunction Microprocessor Motor Protection Units 11.17 Synchronous Motor Protection 11.18 Summary: Typical Protection for Motors 11.19 Practical Considerations of Motor Protection Bibliography Backmatter