MANUAL
for the design of residential buildings
(to SNiP 2.08.01-85 part 2)
6. FLOORS
6.1. Interfloor floors of residential buildings consist of a load-bearing section and a floor. Floors over noisy non-
residential premises located in a residential building (shops, canteens, public service establishments, etc.) are
recommended to be designed with a double floor (a self-supporting reinforced concrete ceiling slab not directly
connected to the slab of the load-bearing part of the floor). If there is a technical floor between the residential part
of the building and the built-in noisy premises, a self-supporting ceiling is not required. Soundproofing of floors
from airborne and impact noise should be checked in accordance with SNiP II-12-77.
6.2. Floors over technical underground spaces and driveways should be designed as insulated. The required
heat-transfer resistance above the underground space is recommended to be determined based on the condition
of ensuring 50% (per 1 hour) of air exchange in the underground space, using the air-heat balance level. In this
case, it is necessary to take into account the influence of enclosing structures and the heat transfer of heating
and hot water supply pipes located underground.
Floors
6.3. Floors of residential buildings are classified by type of covering (parquet, linoleum, plank, slab) and by type of
construction (single-layer, layered, separate solid and separate with voids - on joists).
6.4. Single-layer flooring is laid directly on floor slabs or on a leveling layer installed on the floor slabs.
For single-layer flooring in all rooms of the apartment, except for sanitary facilities, it is recommended to use
linoleum on a heat- and sound-insulating subbase according to GOST 18108-80, or similar materials that meet
the requirements of current technical specifications. Floor covering materials must have a biostable, non-rotten
subbase.
In sanitary facilities, as well as in vestibules, corridors outside apartments, stairwells, elevator lobbies, etc., it is
recommended to install floors made of ceramic (metlakh) tiles. In sanitary facilities, floors made of linoleum on a
rubber backing are permitted.
Single-layer flooring is recommended for interfloor ceilings whose load-bearing structure provides an airborne
sound insulation index of at least 51 dB. When calculating the sound insulation of a ceiling with a single-layer
floor, it is necessary to take into account the reduction in sound insulation due to resonant floor vibrations and
indirect noise transmission from adjacent structures.
6.5. A laminated floor consists of a hard floor covering and a sound-insulating layer.
It is recommended to use block parquet (GOST 862.1-85) and parquet panels (GOST 862.4-77 and TU 13-767-
84) as a floor covering. It is recommended to use wood-fiber boards of grades 4, 12, and 20 (GOST 4598-86) as
a soundproofing layer. In case of floor covering made of block parquet, it is recommended to provide an
additional distribution layer of wood-fiber boards of grade PT-100 (GOST 4598-86). The required thickness of the
soundproofing layer is determined by calculation or based on the results of in-kind soundproofing measurements.
It is recommended to use layered flooring in interfloor ceilings, the load-bearing part of which provides an
airborne sound insulation index of at least 50 dB, as well as in ceilings above colder rooms, when additional
insulation of the ceilings is required.
6.6. A split hollow-core floor consists of a covering, a rigid base, and a soundproofing layer.
All types of linoleum (see Section 6.4), PVC tiles, and other similar materials are recommended for use as
coverings for split hollow-core floors. Parquet flooring (GOST 862.4-87) and ultra-hard wood-fiber boards (GOST
4598-86) are also acceptable. The rigid base is recommended to be a 40 mm thick monolithic screed made of
lightweight concrete with porous or porous aggregates and a phosphogypsum binder of at least class B10 and a
density grade of no more than D 1200. When using parquet flooring, the screed can be made of fine-grained
heavy concrete. For room-sized floor slabs, it is recommended to install the screed in a factory as part of a
complete floor slab. When installing concrete screeds with porous aggregates in a construction environment, it is
recommended to grind the top surface of the screed. Leveling such screeds with cement mortar is not permitted.
It is recommended to place layers of waterproof paper or other similar material between the monolithic screed
and the soundproofing layer, overlapping them at the joints.
Precast floor screeds are recommended to be made of concrete with porous aggregates of at least B12.5 grade
or gypsum-cement-pozzolanic concrete of at least B5 grade.
Floor coverings made of ordinary (non-warm) linoleum (GOST 7251-77, GOST 14632-79, GOST 16914-71), PVC
tiles (GOST 16475-81), superhard wood-fiber boards (GOST 4598-86) are recommended to be laid on a concrete
screed on porous fillers with a density grade of no more than D1200 or a screed made of gypsum-cement-
pozzolanic concrete with a density grade of no more than D 1300.
As a soundproofing layer for separate hollow-core floors, it is recommended to use: mineral wool heat-insulating
slabs on a synthetic binder (GOST 16297-80), semi-rigid grade 125, rigid grade 150, 35-60 mm thick (GOST
9573-82), soft wood-fiber boards of grade 4 with a density of no more than 250 kg/ , 20 ¸ 40 mm thick (GOST
4598-86), fiberboard slabs on grade 300 Portland cement, 50 mm thick (GOST 8928-81), calcined sand,
expanded clay of maximum size 20 mm, and other similar materials, the layer thickness of which is established
based on the results of sound insulation studies in natural conditions.
m3
6.7. A split floor with voids consists of a floor covering, joists, and soundproofing spacers under the joists.
It is recommended to use single-layer parquet boards and wooden panels as a covering for a split floor with voids
(TU 13-767-84). It is also permissible to use tongue and groove boards (GOST 8242-75), as well as superhard
wood-fiber boards on solid flooring made of non-tongue and groove boards 22 mm thick made of low-grade wood
and commercial short-length waste from sawmilling and wood processing, or of particleboards of grade P-3 with a
thickness of at least 19 mm (GOST 10632-77*).
It is recommended to make joists from rectangular wooden beams with a cross-section of 40 × 80 mm or wedge-
shaped beams 40 mm high, 70 mm wide at the top and 26 mm wide at the bottom. The distance between the
joist axes is determined depending on the floor structure: for a base thickness of 19 × 22 mm, the distance
between the joist axes should not exceed 400 mm, and in other cases, 500 mm.
It is recommended to use slab materials used for the construction of the soundproofing layer of separate hollow-
core floors as soundproofing spacers under the joists (see section 6.6).
6.8. It is recommended to separate a laminated floor with a parquet covering, a wooden floor on joists è the
concrete base of the separate floor along the contour from the walls and other structures with a gap 10–30 mm
wide, filled with soundproofing material and covered with a skirting board or coving.
6.9. It is recommended to use a separate floor when constructing the load-bearing part of the floor from solid and
hollow-core slabs for which the airborne sound insulation index is less than 50 dB.
6.10. It is recommended to locate the floors of basements and technical underground spaces above the
groundwater level. If this solution is not feasible, it is recommended to provide for water lowering measures in the
design through drainage, etc. The use of pressure-resistant structures is permitted only if water lowering is
impossible. In this case, the exterior walls of the underground section and the reinforced concrete basement floor
slab must have continuous waterproofing on the ground side and be designed to withstand additional forces from
hydrostatic pressure.
Floor slabs
6.11. Precastis allowed to use four lifting loops
located in the middle of each side (Fig. 52, d). The specified slabs should be calculated using formula (254),
taking into account the coefficient b from Table 17.
Table 17
 Coefficient b for a slab lifted by four lifting loops (Fig. 53) when determining bending forces
l = l / l in the transverse direction at points in the longitudinal direction at points
 A WITH IN WITH
1 -0.0965 0.0497 -0.0963 0.0497
1.1 -0.0995 0.0470 -0.1027 0.0530
1.2 -0.1025 0.0445 -0.1035 0.0562
1.3 -0.1055 0.0422 -0.114 0.0592
1.4 ¾0.1085 0.0402 -0.118 0.0620
1.5 -0.1115 0.0385 ¾0.122 0.0647
1.6 -0.1145 0.0370 -0.125 0.0675
1.7 -0.1175 0.0357 -0.128 0.0702
1.8 -0.1205 0.0347 ¾0.30 0.0730
Note. A negative b value indicates that the upper zone of the slab is in tension.
Fig. 53. Calculation diagram for a precast floor slab supported along the contour.
The remaining calculation and design conditions for such slabs are the same as for slabs with six lifting loops.
6.61 When concreting monolithic structures, it is necessary to use the optimal amount of formwork, which is
related to its turnover time and formwork removal conditions. Therefore, in addition to the basic calculation for the
operational load, the slab is additionally tested, if necessary, for strength and crack resistance under the action of
a load, taking into account the specifics of the building construction technology.
6.62. There are two options for dismantling the formwork of a monolithic floor slab: complete formwork removal
and partial formwork removal with re-support on prefabricated supports.
The slab during complete stripping is calculated for loads taking into account its own weight with a load safety
factor of g = 1.2 and a concentrated load from the weight of the worker and load G = l.3 kN ( g = 1.3) located in
an unfavorable section of the slab. The formwork stripping strength of concrete is adopted in accordance with
SNiP III-15-76.
When concreting monolithic structures or during partial stripping of the floor slab, the underlying slab is checked
for concentrated loads Q transferred by stacks when the concrete has gained strength at the time of loading.
The design model of the monolithic slab is taken as a single-span beam clamped on supports with a span of l .
6.63. In a precast-monolithic floor structure, when calculating installation loads, it is necessary to check the shell
slab at the following stages of installation:
when lifting and installing the shell in the design position;
when concreting the monolithic layer of the floor.
The shell slab is lifted using a slinging grip or a self-balancing crossbar using four, six, or eight lifting loops. The
number of loops is determined by calculation. The shell is installed in the design position on a temporary system
of support purlins and struts, after which the monolithic layer of the slab is concreted.
The shell slab is calculated with the following load safety factors: when calculating for installation loads, g = 1.5;
when calculating for loads arising during concreting of the monolithic layer from the shell's own weight, g = 1.1;
from the weight of the monolithic concrete layer , g = 1.2; and from the load of people and vehicles, equal to 1.5
kN/m2 g = 1.3.
The shell is installed at the required design strength of concrete, but not less than 70%.
The design scheme of the shell for installation effects is taken as a continuous beam in the design direction.
6.64. The structural solution of the shell can be implemented in two versions: without external reinforcement or
with external reinforcement.
In the first case, the shell reinforcement is placed in the thickness of the slab, in the second, to increase the
2 1
f f
1
f
f
f
, 
f
strength (rigidity), the shell is additionally reinforced with triangular frames with external reinforcement.
6.65. The bending moment supported by the section of the shell is taken equal to the greater of the values of M 
and M , determined by the formulas:
M = R bh /3.5; (255)
М = R A [ h ‑ 0.5 R A /( R b )], (256)
where h and h are the thickness and working height of the shell section; b is the calculated width of the shell;
As the cross-sectional area of the design reinforcement.
In the presence of external reinforcement, the calculation of the shell in the support section is made from the
condition
(257)
where А¢ is the cross-sectional area of the external reinforcement; h¢ is the working height equal to the
distance from the compressed face of the shell to the center of the cross-sectional area of the external
reinforcement.
The lifting of the shell with external reinforcement to the design position is carried out using the lifting loops.
The formation of cracks in the shell before the operational stage of work is not allowed.
EXAMPLES OF FLOOR SLABS CALCULATION
Example 8. A simply supported floor slab along the contour of a large-panel building (Fig. 53).
Initial data. The slab dimensions in plan are 3580 ´ 6580 mm. Thickness is 120 mm. Dimensions of the support
platforms: along the short span - 50 mm; along the long span - 70 mm.
Design spans of the slab: l = 3580 - 50 = 3530 mm; l = 6580 - 70 = 6510 mm.
The ratio of the design spans l = l / l = 6510/3530 = 1.844.
The slab is made of heavy concrete of compressive strength class B 15, cassette-made. Design resistances:
For the ultimate states of the first group (when calculating for long-term loads) R = 8.5 × 0.9 × 0.85 = 6.5 MPa;
R = 0.75 × 0.9 × 0.85 = 0.57 MPa;
for the ultimate states of the second group R = 11 MPa; R = 1.15 MPa.
The initial modulus of elasticity of concrete under compression and tension for cassette-made products E = 20.5
× 10 × 0.85 = 17.4 × 10 MPa.
Loads on 1 m of slab excluding its own weight: design — 4500 N/m (~ 450 kgf/m ); standard — 3600 N/m 
(~ 360 kgf/m ); Long-term — 2600 N/m (~ 260 kgf/m ).
The mass of 1 m of the slab is 0.12 × 2500 = 300 kg/m .
Total loads on the slab taking into account the safety factor for the intended purpose, g = 0.95:
calculated — q = 0.95 (300 × 9.81 × 1.1 + 4500) = 7350 N/m ;
standard — q = 0.95 (300 × 9.81 + 3600) = 6216 N/m ;
long-term — q = 0.95 (300 × 9.81 + 2600) = 5266 N/m .
The maximum value of the bending moment in the slab when supported according to the beam scheme along
two long sides M = ql /8 = 7350 × 3.53 × 6.51/8 = 74530 N/m = 74.53 × 10 N × mm.
Calculation of the strength of the slab under the action of operational loads. We assume the reinforcement of the
slab with a welded mesh, in which the bars along the span l break off every other one according to the moment
diagram. We will preliminarily assign reinforcement along the span l from steel of class A-III, and along the span
l from steel of class Bp-I. With such reinforcement, according to clause 6.31, the coefficient g = 0.9. We
assume that h = 100 mm, h = 92 mm. Then the coefficient 
According to Fig. 46 at l / h = 3530/120 = 29.4 and l = 1.844 coefficient g = 0.90. Bending moments along
spans l and l , corresponding to the optimal reinforcement scheme:
N×mm;
N×mm. Let us determine the required reinforcement along the
span l : N = R h x = 6.5 × 100 ×
0.158 = 103 N/mm.
According to Table 10, we adopt reinforcement with a diameter of 10 mm made of steel of class A-III with a pitch
of 300 mm ( N = 98 N/mm; a = 261 mm /m).
The reinforcement coefficient m = a /( h × 10 ) = 261/(100 × 10 ) = 2.6l × 10 = 0.261 % > m = 0.05
%.
Required reinforcement along span l : N 
= R h x = 6.5 × 92 × 0.014 = 8.4 N/mm.
According to Table 10, we adopt reinforcement with a diameter of 3 mm made of grade Bp-1 steel with a pitch of
300 mm ( N = 8.86 N/mm, and = 23 mm /m).
b
s
b bt
2 
1
s s s 01 s s b
1 01
is
s o
1 2
2 1
b
bt
b,ser bt,ser
b
3 3
2 2 2 2
2 2 2
2 2
p
2
n
2
l
2
o
2 
1
2 6
1
1
2 s
01 02
1 p
1 2
1 s1 b 01 1
s1 s1
2
1 s1 01
3 3 ‑3
min
2 s 2
b 02 2
s1 s2
2
Reinforcement coefficient We check the condition 0.5( m + m ) =
0.5(0.261+ 0.025)10 = 0.141 % > m = 0.05 %.
Calculation of the strength of the board under the action of installation loads. The assembly weight of the slab
taking into account the dynamic coefficient of 1.4 G = 300 × 9.81 × 1.4 × 3.58 × 6.58 = 97 × 10 N.
We will adopt a lifting scheme for six loops located in the middle of the short sides and in thirds of the long sides.
Using formula (254), taking into account the values given in Table 16 (with l = 1.844), we determine the bending
moments per unit length of the slab cross-section.
Bending moments at point C (in the middle of the slab):
in the transverse direction b = 0.05; M = 0.05 × 97 × 10 = 4.8 ´ 10 N×mm/mm;
in the longitudinal direction b = 0.0283; M = 0.0283 × 97 × 10 = 2.75 × 10 N×mm/mm.
When calculating for installation loads, we take into account that the slab can be lifted at 70% of its strength, then
the calculated compressive resistance (taking into account the coefficient 1.1, which takes into account the short-
term action of dynamic loads)R = 8.5 × 0.85 × l.l × 0.7 = 6.0 MPa.
Bending moments supported by the slab with the adopted reinforcement (when calculating for assembly loads):
in the transverse direction ( M = 98 N/mm; h = 100 mm). m = N ( h ‑ N /2 R ) = 98(100 ‑ 98/2 × 6)
= 9000 N > 4.8 × 10 N;
in the longitudinal direction ( N = 8.86 N/mm; h = 92 mm) m = N ( h ‑ N /2 R = 8.86(92 ‑ 8.86/2 ×
6) = 808 N m = 0.05 %; m = 84/(92 × 10 
) = 0.09 × 10 = 0.09 %;
m = 0.5( m + m ) = 0.5(0.251 + 0.09)10 = 0.170 % > m = 0.05 %.
The adopted reinforcement satisfies the strength conditions under operational and installation loads and the
requirements for the minimum percentage of reinforcement.
Calculation of slab for cracking. The load at which cracking should be checked is q = 6216 N/m = 6.2 × 10 
N/mm .
The bending moment corresponding to the formation of cracks during bending along the span l is determined
approximately by the formula M = l h R /3.5 = 6510 × 1202 × 1.15/3.5 = 30.8 × 106 N×mm.
According to the graph in Fig. 48, for l = 1.844, the coefficient a = 0.095.
The load at which cracks form in the span of the slab,
N/mm l/200 =
3530/200 = 17.6 mm. The deflection exceeds the permissible value. It is necessary to increase the slab
reinforcement. Let us double the reinforcement along the span l , then M = 2.6 × 9 ´ 10 = 121.8 × 10 
N×mm; m = 0.5(2 × 0.251 + 0.09) = 0.295%; x = 0.1 + 0.5 × 0.295 × 10 × 390/11 = 0.152; The required
deflection is ensured. We will finally accept: along the span l — reinforcement with a diameter of 8 mm with a
pitch of 100 mm made of steel of class A-III; along the span l — reinforcement with a diameter of 4 mm with a
pitch of 150 mm made of steel of class Bp-I. Example 9. A hollow-core slab of a large-panel building supported
on three sides (Fig. 54). Fig. 54. Diagram for an example of calculating a precast hollow-core slab supported on
three sides
l 1 01 01
02
crc
- 3 2
crc
4 
1 1 crc b1 b
3 4 - 3 3
3
crc b2 b2 crc
ser b2 crc 1 crc ser crc
1 1
6 6
-2
1
2
It is necessary to determine the calculated reinforcement, check the strength, deflections and crack resistance of
a hollow-core slab supported along two short sides and one long side on the walls of a large-panel building. The
slab has a combined reinforcement: prestressed reinforcement along the long side and welded mesh in two
directions.
Initial data. The slab dimensions are 5980 ´ 3580 mm, thickness 220 mm. The diameter of the voids d = l40 mm,
the pitch of the voids s = 200 mm, the number of voids n = 17. The thickness of the ribs: extreme - b = 90
mm, intermediate - b = 60 mm. The thickness (height) of the upper and lower flanges h¢ = h = 40 mm.
After the installation of partitions on it, the slab is clamped on the supports at the platform joints of the wall
panels. Slab support depth: 80 mm along the short sides, 100 mm along the long side.
Calculated slab spans: l = 5980 - 2 × 0.5 × 80 = 5900 mm; l = 3580 - 0.5 × 100 = 3530 mm; l = l / l = 0.6.
The slab is made of heavy concrete of compressive strength class B20. Concrete resistances R = 15 MPa, R
 = 1.4 MPa, R = 11.5 × 0.9 = 10.3 MPa, R = 0.9 × 0.9 = 0.81 MPa. Initial modulus of elasticity of concrete
E = 24000 MPa.
Prestressed reinforcement made of steel class At-V with a diameter of 10-12 mm, for which R = 785 MPa, R
 = 680 MPa, E = 190,000 MPa, the price of 1 ton is 181 rubles.
Non-prestressed reinforcement made of wire class Bp-I with a diameter of 5 mm, for which R = 395 MPa, R 
= 360 MPa, E = 170,000 MPa, the price of 1 ton is 202 rubles.
Protective flanges: for prestressed reinforcement - 25 mm, for non-prestressed reinforcement - 15 mm.
The load on the slab is uniformly distributed.
Standard load per 1 m of the slab: from the slab's own weight 4 kN; from the weight of the floor 0.1 kN, from the
weight of the partitions 1.3 kN, temporary load 1.5 kN, including long-term 0.3 kN.
Calculated loads taking into account the safety factor for the intended purpose g = 0.95:
when calculating the strength
q = (1.1×4 + 1.2×0.1 + 1.1×1.3 + 1.3×1.5) 0.95 = 7.5 kN/ = 7.5×10 N/mm ;
when checking crack resistance
q = (4 + l.3) 0.95 = 5.0 kN/m = 5×10 N/mm ;
q = (0.1 + 1.5) 0.95 = 1.52 kN/m = 1.52×10 N/mm ;
when checking deflections and crack openings
q = q = 5 kN; q = (0.1 + 0.3) 0.95 = 0.4 kN/m = 0.4×10 N/mm .
Checking the strength of the slabalong the voids. Moments of inertia of concrete section of slab:
during bending along voids
I = l h /12 ‑ npd /64 = 3530×220 /12 ‑ 3.14×17×140 /64 = 2.79/10 mm;
during torsion
We calculate the dimensionless parameter
Reduced thicknesses of shelves h = h¢ = h + 0.0569 d = 40 + 0.0569×140 = 48 mm.
The strength of the slab in section along the void averaged along its width without reinforcement is checked
according to the condition
Since q = 7.5 kN/m , strength without reinforcement is not ensured. It is necessary to provide for the installation
of reinforcement.
Determining the reinforcement required according to the strength conditions. When calculating the strength, the
slab is considered simply supported on three sides (two short and one long). Partial clamping of the slab at the
platform joints is not taken into account in the safety margin.
The calculated section heights along spans l , l , respectively : h = 220 ‑ 25 ‑ 0.5 × 10 = 190 mm; h = 220
‑ 15 ‑ 0.5 × 5 = 208 mm. Along span l the slab has combined reinforcement. We will assume, as a preliminary,
that the areas of prestressed and non-prestressed reinforcement along the span have a ratio of 3:1. Then, for
combined reinforcement, the reduced resistance of the reinforcement R = (3 R + R )/4 = (3 × 680 + 360)/4
= 600 MPa, the reduced price of 1 t C = (3 × 181 + 202)/4 = 186 rubles.
For reinforcement along the spanl R = 360 MPa, C = 202 rubles. We determine the coefficient g = ( R 
C )/( R 1C ) = (369 × 186)/(600 × 200) = 0.56.
vac w o
w f f
1 2 2 1
b,ser
bt,ser b bt
b
s,ser
sp sp
s,ser s
s
n
m2 -3 2
1 n
2 -3 2
2n
2 -3 2
1l 1n 2l
2 -3 2
2
3 4 3 4 9
f,red f,red 1
2
1 2 01 02
1,
s1 s p s
s1
2 s2 s2 s s2
s1 s s2
The bending moment from the design load in the middle section when the slab is supported according to the
beam scheme along two short sides M = ql l /8 = 7.5 × 5.9 × 3.530/8 = 115.2 kN×m = 115.2×10 N×mm.
Let us check the condition l > 0.25 g h / h . We have l = 0.6 = 0.36 > 0.25 × 0.56 × 202/190 = 0.15.
The condition is satisfied.
Let us determine the optimal reinforcement of the slab according to the strength condition: v = 0.5 g h /( lh
 ) = 0.5 × 0.52 × 202/(0.6 × 190) = 0.495;
 M = M v /(3 l ) = 115.2 × 0.495 /(3 × 0.6)
= 15.7 × 10 N×mm.
Let us determine the required reinforcement of the slab. Height of the compressed zone of concrete
Since x = 21.8 mmbending according to the beam scheme
along the span l Mg = gl l /8 = 4 × 10 × 3530 × 5900 = 6.14-10 N×mm ( g = 4 kN/m = 4 × 10 N/mm
— distributed load from the slab’s own weight).
Then s = P / A + ( P e ‑ Mg ) e / I = (3.725 × 10 /5.15 × 10 + (3.725 × 10 × 80 ‑ 6.14 × 10 ) ×
80/2.79 × 10 = ‑ 0.182 MPa.
The minus sign means that the stresses are tensile. In this case, the stress losses s = 0.
The first prestress losses
Let us now determine the second prestress losses:
losses from relaxation of prestressed reinforcement when tensioned on the stops s = 0;
losses from shrinkage s = 40 MPa;
losses from concrete creep are not taken into account, since the stresses s are tensile.
Then the second losses
Total losses s = 102 + 40 = 142 MPa > 100 MPa. Therefore, we do not increase the found value of losses.
Taking into account all losses, the compression force
Distance r is determined as for an elastic body by the formula r = I ( y A ) = 2.79 × 10 /(110 × 5.15 × 10 =
49.2 mm.
Taking into account the found values M = 1.4 × 4.01 × 10 + 3.47 × 10 (80 + 49.2) = 101 × 10 H×mm > M 
= 51 × 10 N×mm. Cracks do not form in the span.
Let us now check the possibility of cracks forming on the support when the slab is clamped by the walls. Since
the bending moment M = R I/y = 1.4 × 2.79 × 109/110 = 35.5 × 10 N×mm > M = 16.4 × 10
N×mm, then cracks do not form on the support.
When checking the slab's bending strength along the span l It was established that cracks may form along the
voids. When checking the crack resistance of the slab, it is necessary to take the standard load on the slab q 
instead of the calculated one , and the value of R instead of the calculated tensile strength of concrete R ¾
. Conditionally, crack formation Since q = q + q = (5 + 1.52)10 = 0.00652 N/mm , then when checking
according to the second group of limit states, cracks along the voids do not form. Checking slab deflections.
Since cracks do not form in the slab under the action of standard loads, the deflections are determined as for an
elastic body. As a first approximation, we determine the deflections as for a slab simply supported along two short
sides using the formula The deflection calculated for the beam support scheme is less than the maximum
permissible. Therefore, there is no need to specify the value of the slab deflection, taking into account support on
three sides and clamping on the supports. Example 10 . Monolithic floor slab of solid cross-section, clamped on
three sides (Fig. 55). Fig. 55. Schemes for an example of calculating a monolithic floor slab . Initial data. A 13 cm
thick slab in a 6 x 6 m structural cell of a precast-monolithic building with internal walls made of monolithic
concrete and curtain wall panels. The floor slab is cast in a single cycle with the internal walls. The internal walls
f f red 1 f f
1 1
1
pl
pl 1 1
2
7 3
sp
sp sp s,ser s,ser
sp
1 sp
2
3 4
6 bp
1 5
bp,
1 5
red
2 5 2
op red p
1 2
2 
1
 -3 2 7 2 -3 2
bp 1 red 1 op op
 5 5 5 7
 o
6
i
s
bр
red red
 9 5
crc
 7 5 6
n
 6
o 
crc t,ser red
 6 o 
n
 6
2
n
bt,ser bt
n n1 n2
-3 2
and the floor slab are made of heavy concrete of strength class B15. Calculation scheme of the slab: the slab is
clamped on three sides and has no support on the fourth side. Calculated spans of the slab: l = 6000 - 160 =
5840 mm; l = 6000 - 80 = 5920 mm. The aspect ratio of the slab l = l / l = 5920/5840 » 1is satisfied;
at supports a = 402 mm , a¢ = 196 mm ,
the condition a ³ a is satisfied.
Checking the bearing capacity of the slab with the adopted reinforcement:
m = 13.56 × 0.15 = 2.03 × 10 N×mm;
s sn s,ser
s
s sn s,ser s
0 
1
0 
2
0 
3
crc,1
2 2 -3 2
n
crc2 1
 2 2 -3 2
n
crc, 3
 2 2 -3 2
n
si s,crc s1 s2 s,crc
crc
2
bt,ser
 2 6
crc
o crc b
2 
0
 6 2
s,crc crc s o
 6 2
an
an
 5 2
an bt
 5 5
an an o
 5 6
an
o
6 2
s,an
6 2
1 an s,1 s,an
1 crc s,1 s,crc
s,1
2
1 s s,1 o s s,1 b
6
1 2 1 I I 1 II II 1 1
- 3
1 1 1
6
1
2
1
6
o
6 2
s,1
6 2
i s, 2
2
s,1
2
s,1I
2
1
s, 1
2
2
s , 2
2
s,1 s , 2 s,crc
s, 1
2
s,I
2
s, i s,crc
2
6
m¢ = 9.55 × 10 N×mm; m = 2.03 × 2 = 4.06 × 10 N×mm; The strength of the slab is ensured. Calculation of
the opening of cracks normal to the longitudinal axis is performed according to formula 1. In the supporting
section q = 2.85 × 10 N/mm q = 4.14 × 10 N/mm ; f = f 
+ ( f — f ) ( q — q )/( q — q ).Slab deflection before the moment of crack formation in the
spanwhere j = 2 - to take into account the effect of long-term creep of concrete, b° = 0.34 (see Table 13).Slab
deflections in the ultimate state are determined as for a slab clamped along a contour with an aspect ratio of l 
: 2 l , l¢ = 2 l / l = (2 × 5920)/5840 » 2,
o 01 02
s o
 2
o
 6 2 6
 4 3
c rc
l
 -3 2
crc
 -3 2
crc
ser crc l crc ser crc
b2
1
2 2 1
where q is the coefficient taking into account the degree of clamping of the plate in the support sections,
determined at y £ y :
y = m /m = (18.65 × 10 )/(13.56 × 10 ) = 1.375;
y¢ = m¢ / m = (9.55 × 10 )/(13.56 × 10 ) = 0.7.
From the condition y + y¢ £ y + y¢ we accept
y + y¢ = y + y¢ = 1.37 + 0.7, then
q = 1/(1 + 0.25å y ) = 1/[1 + 0.25(13.75 + 0.7 + 13.75 + 0.7)] = 0.49;
v = 0.15 is the coefficient characterizing the elastic-plastic state of concrete in the compressed zone; h1 = l +
0.2(2l — 1) = 1 + 0.2(2 × 1 — 1) = 1.2 is the coefficient taking into account the increase in the ultimate deflection
at the middle of the free edge of the slab clamped on three sides at l > 0.5; h = h /( h ‑ 0.7) = 14/(14 — 0.7)
= 1.05 — coefficient taking into account possible deviations in the thickness of the protective layer of
reinforcement;
The rigidity of the slab is ensured.
7. ROOFS Roof
structures
7.1 . It is recommended to design attic roofs for residential buildings using precast reinforced concrete elements.
For buildings less than 5 storeys, attic roofs may be designed as pitched roofs with roofing made of piece
materials.
It is recommended to arrange the entrance to the attic and exit to the roof from the stairwell through a fireproof
door measuring 1.5 ´ 0.8 m. It is recommended to provide an entrance to the attic in each section of the building,
and an exit to the roof at the rate of one exit per 1000 m , while in all cases it is recommended to provide exits
to the roof in the end sections.
7.2. Attic reinforced concrete roofs are subdivided:
by the thermal regime of the attic - with a cold (including open) and warm attic;
by the method of removing air from the exhaust ventilation of the building - into roofs with the discharge of air
from the ventilation to the outside (cold attic) and with the discharge of air from the ventilation into the attic space
(warm and open attic);
By roof design — made of reinforced concrete slabs (without thermal insulation or insulated slabs);
By roof type — rolled and non-rolled with or without protective mastic (paint) waterproofing (for weather-resistant
concrete).
In a roof with a cold attic (Fig. 56), the interior space is ventilated with outside air through openings in the walls,
the cross-sectional area of which, with a reinforced concrete roof, must be no less than: in climatic zones I and II
— 1/500, in III and IV — 1/50 of the floor area. In a roof with an open attic, the area of ventilation openings in the
walls is determined by heat engineering calculations for winter and summer operating conditions.
Fig. 56. Diagram of a roof with a cold attic
a — covering with roll roofing; b ¾ covering with non-roll roofing
1 — reinforced concrete roofing panel for roll roofing; 2 — reinforced concrete roofing panel with roll-free roofing;
3 — reinforced concrete water collection channel; 4 — supporting panel; 5 — floor slabs; 6 — insulation layer
with protective layer; 7 — supply and exhaust openings in the walls; 8 — ventilation duct block; 9 — insulated
internal drain pipe
In case of pitched roof made of piece materials, the attic space is ventilated through the gaps between its sheets,
therefore in climatic zones I and II, ventilation openings may be reduced to 0.01.
In case of roof with cold open attic (Fig. 57), thermal insulation is laid on attic floor slabs. It is recommended to
II I
1 I 1
6 6
I I I
6 6
II II I I
II II I I
i
2 01 01
2
protect the thermal insulation layer along the attic perimeter for a width of at least 1 m from moisture. Ventilation
shafts and sewer riser exhaust ducts in case of cold attic must be insulated above the attic floor.
Fig. 57. Diagram of a roof with an open attic
a — covering with roll roofing;b — covering with non-roll roofing
1 — reinforced concrete roofing panel for roll roofing; 2 — reinforced concrete roofing panel with non-roll roofing ;
3 — reinforced concrete water collection channel; 4 — floor panels; 5 ¾ support panel; 6 — head of the
ventilation block; 7 — exhaust ventilation shaft; 8 — ventilation opening in the external wall; 9 — insulation layer
with a protective layer; 10 — insulated branch pipe of the internal drainpipe
In a roof with a warm attic (Fig. 58), the attic space, which has insulated frieze external walls and an insulated
roof covering, is heated by warm air coming from the exhaust ventilation of the house. To remove air from the
attic space, exhaust shafts should be provided, one for each section. The attic space should be sectioned by
walls into isolated compartments. Doorways in the walls, providing a through passage through the attic, must
have sealed jambs. To protect the exhaust ventilation shafts from precipitation in a cold attic, it is recommended
to install protective umbrellas above them.
Fig. 58. Diagram of a roof with a warm attic
a - covering with roll roofing; b - covering with non-roll roofing
1 - lightweight concrete panel covering for roll roofing; 2 - ditto, tray; 3 — double-layer roofing panel with roll-free
roofing; 4 — ditto, tray; 5 — support panel; 6 — floor panels; 7 — solid external walls; 8 — ventilation unit cap; 9
— exhaust ventilation shaft; 10 — protective hood; 11 ¾ water collection tray; 12 — internal drain
Roofs with a cold attic are permitted to be used in residential buildings of any number of storeys. Roofs with a
warm attic are recommended for use in buildings of 9 or more storeys.
The admissibility of using roofs with a warm attic in buildings less than 9 storeys high must be substantiated by a
technical and economic calculation. In buildings less than 5 stories tall, roofs with heated attics are not
recommended.
Ventilation units with ducts passing through the attic and venting air to the outside must be at least 0.7 m above
the roof level (for roof slopes up to 10%).
In roofs with ventilated air discharged into the attic space, which functions as a static pressure ventilation
chamber, exhaust is achieved through exhaust shafts, and in roofs with an open attic, also through ventilation
openings in the frieze walls.
The reinforced concrete roof deck consists of pitched slabs, which form inclined surfaces for runoff, and gutter
slabs, which collect and drain gutter water into the internal drainage system.
The width of the open portion of the gutter slabs is recommended to be at least 0.9 m, and the distance between
its bottom and the attic floor is at least 1.2 m.
For roofs with internal drainage, it is recommended to install at least one roof drain in the gutter slabs per section.
Downspouts and downspouts within the cold attic should be insulated. In low-rise buildings with external
unorganized drainage (in buildings 1-2 stories high), the building should be positioned with a 2-meter setback
from the red line, with canopies installed over entrances and balconies.
7.3. Roofs made of piece materials are recommended to be made of asbestos-cement sheets, tiles, or other
similar materials.
Roll roofing is made from layers of rolled roofing materials that are glued to the roofing elements at the
construction site.
For rolled roofing, it is recommended to use roofing felt according to GOST 10923-82 (roofing felt with coarse-
grained dressing, lining roofing felt with dust-like or fine-grained dressing), roofing parchment (GOST 2697-83),
glass roofing felt (GOST 15879-70), fusible roofing felt (TU 21-27-53-76), rolled isol (GOST 10296-79) and rolled
mesh fiberglass fabrics made of alkali-free glass.
For gluing roofing materials, it is recommended to use hot bitumen roofing mastics (GOST 2889-80).
The bottom layer of roll roofing is recommended to be partially glued to the base, including perforated roofing felt
("breathing roof"). When using continuous roll materials, it is recommended to adhere them to the base in strips
or spots over an area of approximately 30%. In all cases, the roofing felt should not be glued along the joints of
the slabs in a 25 cm wide strip. When using roofing felt with a coarse-grained dressing in the top layer of the
roofing felt, it is permissible to omit the protective gravel layer in climatic zones I-III.
The recommended slope for roll roofing on slopes is at least 2%, and in trays, at least 1%.
Roll roofing is not recommended for use in climatic zones I and IV.
In a roof with non-roll roofing, the protective functions are performed by the concrete of the roofing panel,
protected by waterproofing mastics applied to the upper surface of the panel, usually in a factory setting.
Waterproofing protective mastics for non-roll roofing must adhere to the concrete and maintain strength and
elasticity over the operating temperature range in accordance with the technical specifications for these materials.
Mastic and paint compositions must meet the following requirements: compressive strength of at least 0.5 MPa,
adhesion to concrete in shear of at least 1 MPa, frost resistance of at least 100 cycles, water resistance at a
pressure of at least 0.8 MPa, heat resistance of at least 90 °C, relative elongation at 20 °C of at least 200%.
Concrete, from which panels for roll-free roofing are made, must meet the requirements specified in Table 18 for
panels with a protective mastic paint and without surface waterproofing.
Table 18
Characteristics of concrete slabs Minimum value of concrete index
coatings with protective
mastic paint
without waterproofing (weather-
resistant concrete)
Concrete class by compressive strength B25 B25
Concrete class by tensile strength B 1.6 B 1.6
Concrete grade by water resistance W6 W8
Concrete grade by frost resistance at the outdoor
temperature of a cold five-day period, °C: 
above minus 15 F200 F300
from minus 15 to minus 35 F300 F400
below minus 35 F300 F500
In roofs with non-roll roofing, the slope pitch must be at least 5%, and in gutters, at least 2%. The roofing panel
design must ensure the absence of cracks on the upper surface with protective paint under operating conditions,
and for panels without waterproofing, also during formwork removal. The upper facing surface of roofing panels
must comply with category A2 according to GOST 13015.0-83 for panels with protective paint and category A1 for
panels without waterproofing.
7.4. Reinforced concrete attic floor elements (roofing slabs and gutter slabs) are recommended to be designed
with support on both sides. The use of continuous structures is not recommended.
Roofing slabs are recommended to be supported on external walls and gutter slabs located along the central axis
of the building. For external non-load-bearing walls, it is recommended to provide for the installation of reinforced
concrete beams in the plane of the external walls, supported by the load-bearing transverse walls of the
residential floors.
The adopted support scheme for precast roofing elements must ensure freedom from temperature deformations
of the roofing or its parts. At the same time, the stability of the roofing structures must be ensured.
7.5. For roll roofing, roofing slabs are designed with a smooth upper surface. It is recommended to provide
concrete dowels
at the slab joints. For roll roofing, it is recommended to lay profiled concrete stones on the eaves.
7.6. For non-roll roofing, it is recommended to design the joints of roofing slabs with side ribs at least 10 cm high,
covered with concrete flashings. Where the roofing slabs rest on the gutter, it is recommended to form a
cantilever overhang at least 30 cm long with a drain rib along the edge. For non-roll roofing, it is recommended to
support the roofing panels on the exterior walls to form an overhang. If necessary, the eaves assembly is installed
with a concrete parapet.
It is recommended to manufacture prefabricated elements in an inverted position ("face down") and movethem
into the working position using tilters. To ensure the required frost resistance and water resistance of the
concrete, it is recommended to use vibration-impact technology for the manufacture of roofing elements and
provide for heat and moisture treatment in a "soft mode."
7.7. Roof covering slabs with a cold attic are recommended to be designed as thin-walled ribbed panels made of
reinforced concrete: with the ribs facing down for roll roofing and with the ribs facing up for non-roll roofing. The
t t
thickness of the roofing slab shelf is recommended to be at least 40 mm, and the thickness of the non-roll tray is
recommended to be at least 60 mm.
Insulated attic roofing slabs for non-roll roofing must have a minimum 40 mm thick top layer of dense concrete
and 100 mm high side ribs. It is recommended that the slabs be designed as two-layer slabs, including those with
thermal inserts.
Insulated attic roofing slabs for roll roofing are recommended to be designed as single-layer lightweight concrete
slabs, including those with thermal inserts or three-layer slabs.
7.8. Attic floor slabs should be designed with the same construction as the interfloor slabs.
Thermal calculation
7.9. Thermal calculations for a warm attic are based on the assumption that heat loss from the attic floor is limited
and condensation does not form on the inner surface of the external enclosures, while maintaining the thermal
balance of the unheated space.
It is recommended to start the calculation with determining the air temperature in the attic according to sanitary
and hygienic conditions
t = t ¾ D на в пер (258)
where t is the indoor air temperature, °С; D t is the standardized temperature difference at the ceiling surface,
taken equal to 4 °С; R is the heat-transfer resistance of the attic floor, m2 °С/W; а is the heat-transfer
coefficient of the inner surface of the enclosure, W/m2 °С.
The heat-transfer resistance of the coating is determined according to the heat balance condition
(259)
where t is the air temperature in the attic, ° С; t is the outdoor air temperature, °С; t is the air temperature
in the ventilation ducts, °С; q is the specific heat gain with ventilation air, W/m2 °С; А is the reduced area
of the external walls.
The outside air temperature is taken to be the temperature of a cold five-day period. The air temperature in the
ventilation ducts is considered to be 1°C higher than the inside air temperature. Specific heat gain with ventilation
air is determined as the ratio of the product of the standard air flow rate, its density, and its heat capacity to the
area of the roof.
The temperature of the inner surface of the roof
(260)
must not be lower than that shown in the graph in Fig. 59.
Estimated outside air temperature, °0
Fig. 59. Calculated temperatures of the inner surface of the coating
t — main coating; t — cold section
If the specified condition is met, the attic temperature is entered into formula (259) under the condition of no
condensation
(261)
The actual air temperature in the attic is determined by formula
I 
чер в
t
R
о 
,
в
Н
пер 
о
×
в
×
чер Н вен
вен
×
ст
pok cold
(262)
7.10. Heat engineering calculation of an open attic is performed based on the condition of preventing
condensation on the surface of the coating and maintaining heat, humidity and air balances. Air exchange in the
attic is determined by the influx of outside air under the moisture balance condition
G = G [( d ‑ d )/( d ‑ d )], (263)
where G , G — reduced flow rate of outside and ventilation air, kg/h×m2 coating; d , d — moisture
content of outside and ventilation air, g/kg.
The actual air temperature in the attic is determined from the heat balance condition
(264)
where c = 1.01 kJ/kg×°C is the heat capacity of air.
The temperature of the inner surface of the covering is determined by the formula
t = t ‑ ( t ‑ t )/( a R ). (265)
Taking the temperature t as the dew point, we find the calculated (saturation) moisture content of the air d .
Taking into account the air balance, we calculate the actual moisture content of the air in the attic
d = ( G d + G d )/( G + G ), (266)
which cannot be greater than the calculated one. Otherwise, the calculation is continued until the values match.
The area of the opening per 1 m of the external walls for attic ventilation is calculated using the formula
A = BG /(3600 y v ), (267)
for which the air velocity in the opening is found from expression
(268)
where y is the density of the outside air, kg/m ; V is the wind speed, m/s; k , k are the aerodynamic
coefficients for the windward and leeward sides; åx is the sum of the local air flow resistance coefficients; B is the
building width, m.
The temperature and moisture content of the outside air and the wind speed are taken as average long-term
values for January. The moisture content of the ventilation air is determined as the sum of the moisture content of
the outside air and the increase in the moisture content in residential premises, which is taken as 3.3 g/kg for
gasified houses and 3 g/kg for houses with electric stoves.
8. VOLUMETRIC BLOCKS
8.1. It is recommended to design two types of load-bearing volumetric blocks (Fig. 60):
the first ¾ of a one-piece box-shaped element open on the external wall side and an attached external wall panel
(of the "lying cup" type);
the second — of a one-piece box-shaped element open on the floor side, an attached floor slab and, in some
cases, an insulating external wall panel (of the "cap" type). The use of other types of volumetric blocks should be
specially justified.
n in in p p n
n in
of
n v
pok ger ger n
pok 
v
pok 
o
pok p
ger v v n n v n
o n n o
n
3
n n p
Fig. 60. Diagram of a volumetric block of the "lying cup" ( a ), "cap" ( b ) type
8.2. It is recommended to make box-shaped elements of load-bearing volumetric blocks in the form of a five-
plane structure made of concrete of class not lower than B10 with flat or ribbed walls and an intact ceiling slab of
variable thickness.
It is recommended to design the internal surfaces of the walls of the box-shaped element with technological
slopes in height or length of no more than 15 mm.
8.3. In the first type of volumetric block, it is recommended that the walls and floor slab be ribbed; with the ribs
facing outward; the ribs of the longitudinal walls and the floor slab are located in the same plane with a pitch of
1000-1100 mm. The floor slab may be flat with ribs along the contour. For buildings less than 10 stories high, if
necessary, the walls can be flat and thicker. The recommended rib height is 100-120 mm, and the wall thickness
between ribs is at least 60 mm. The end walls of the volumetric block are recommended to be flat, 60-100 mm
thick . The
ceiling slab is recommended to be at least 80 mm thick.
In volumetric blocks of the second type, it is recommended to design the walls as flat with local thickenings on the
outer side of the volumetric block along the intersection of its faces. The following cross-sections are
recommended for the elements: for longitudinal walls between the thickenings along the contour — from 55
(bottom) to 65 mm (top) made of heavy-weight concrete or from 30 to 90 mm made of lightweight concrete; for
transverse walls — from 80 to 90 mm made of any concrete; for a ceiling of variable cross-section with a
minimum thickness of 40 and 60 mm, respectively, for heavy-weight and lightweight concrete, and a thickness of
¾ 90 mm at the junctions with the walls. It is recommended to design the floor slab as ribbed, with contour ribs no
less than 160 mm high and a slab thickness of 50 mm for heavy-weight concrete and 110 mm for lightweight
concrete. In a slab made of heavy-weight concrete, the height of the intermediate ribs is recommended to be 20
mm less than the height of the contour ribs. It is permissible to design a slab without intermediate ribs, with a
thickness of at least 80 mm. The floor slab is attachedto the box-shaped element using a mortar joint and
welding of embedded parts.
8.4. The walls of volumetric blocks of panel-block buildings, on which precast floor slabs rest, shall be designed
with a thickness of at least 120 mm based on fire safety requirements.
The following schemes for transferring vertical loads (support) from block to block are recommended:
along the entire (or part of) the wall contour, which ensures a more uniform loading of the walls, high load-bearing
capacity of the block and lower consumption of materials;
along four corner sections, which brings the block operation scheme closer to a building with a hidden frame; this
scheme allows for maximum opening of openings and mortarless support of blocks, which may prove expedient
during building assembly, for example, in northern conditions.
8.5. Depending on the type of precast concrete block, external walls are designed as three-layer, two-layer, or
single-layer.
In precast concrete blocks of the first type, the external wall is made of single-layer or three-layer panels, joined
with box-shaped elements in a factory setting.
In precast concrete blocks of the second type, the external wall is formed by a single-layer or two-layer panel,
manufactured in a single production cycle or joined in a factory setting with the external wall of a box-shaped
element.
It is recommended that single-layer and three-layer panels for external walls be designed similarly to the walls of
large-panel buildings.
8.6. Load-bearing precast concrete blocks of sanitary cabins be designed from concrete or sheet materials.
It is recommended to design a concrete block from heavy or lightweight concrete of at least class B10. It is
permissible to design walls and ceiling slabs from gypsum concrete of at least class B5. It is recommended to
adopt the design of a concrete volumetric element as a one-piece molded element with five external faces
(excluding the floor or ceiling) and internal partitions. It is recommended to adopt a minimum wall and ceiling
thickness of 50 mm. The ceiling slab may be made of sheet materials.
It is recommended to design a volumetric block made from sheet materials consisting of a reinforced concrete
floor slab, a frame, and sheet material cladding. A frameless solution may be used for factory assembly of a
volumetric block; in this case, it is recommended to connect the sheets using profiled elements manufactured
using the extrusion method.
8.7. To ensure the required difference in floor elevations of bathrooms and other rooms of the apartment, the floor
panel elevation in the bathroom should be 20 mm lower than in the walk-through airlock and kitchen. It is
recommended to provide for the manufacture of a floor slab for the bathroom with a finished ceramic tile covering.
8.8. Internal partitions between rooms included in the volumetric block are recommended to be monolithically
connected to the walls and ceiling. It is recommended to connect monolithic partitions to the walls and ceiling
along an arc of a circle with a radius of 10-20 mm.
8.9. Reinforcement of box-shaped elements of volumetric blocks is recommended to be performed in the form of
spatial reinforcement cages assembled on special jigs from meshes and frames, which are connected to each
other by contact welding.
It is recommended to reinforce the ceiling slab with a welded mesh with cells no larger than 250 x 250 mm made
of class Bp-I wire with a diameter of at least 3 mm.
Flat walls are recommended to be reinforced with bent welded cages consisting of three longitudinal rods with a
diameter of at least 6 mm, installed at a pitch of no more than 1500 mm. The same frames are recommended for
installation at the intersections of the box-shaped element's faces, in the ribs, and in the haunches.
Reinforcement with individual rods or frames must be provided along the perimeter of the openings.
The walls of non-load-bearing volumetric elements are recommended to be reinforced with welded mesh, similar
to the ceiling slab.
Reinforcement of the floor slab and above-head lintels is determined by calculation.
8.10. The design of the volumetric block must allow for its lifting and installation using either hinges or special
grips on the floor panel or horizontal haunches at its top.
8.11.When transporting a precast concrete block, it is recommended to provide linear support on wooden
spacers. To protect the precast concrete block from precipitation, it is recommended to provide special precast
ceiling slab covers.
When transporting precast concrete blocks on railway platforms, it is necessary to use an elastic fastening
system using damping spacers. 8.12. It is recommended that the following sequence be used to
calculate the operational loads of precast concrete blocks: Based on the building calculation, determine the
forces acting in the block wall planes; determine the eccentricities of the vertical forces relative to the neutral
plane of the wall; and check the load-bearing capacity of the blocks and their connections. In addition, the
strength, rigidity, and crack resistance of an individual block are tested for the forces arising during the
manufacturing process, transport and installation impacts, and the building's resistance to emergency impacts.
When selecting building design schemes to determine the forces in the wall planes, in most cases, conventionally
rigid or flexible floor disks should be adopted. Rigid diaphragms are those in which the joints of floor panels in
their plane ensure the transfer of horizontal shear forces — platform joints of large-panel buildings; joints of
panels with monolithic seams between them in the presence of at least two keys per length of the joint of two
elements; joints of supporting floor panels on volumetric blocks, in which the vertical load from the walls of the
overlying blocks is transferred through the supporting ends of the panels. Rigid diaphragms (Fig. 61, a ) are also
considered to be floor disks of the same diameter of a building consisting of two or more columns of volumetric
blocks, which are connected at the floor level by at least two welded ties on embedded parts. Fig. 61. Structural
schemes of horizontal diaphragms of rigidity 1 — volumetric blocks; 3 — Floor slabs. Flexible slabs are those in
which the floor panels are supported on the solid blocks through "point pins," when horizontal connections
between adjacent block columns are achieved by welding embedded parts, and in other cases not listed in the
previous paragraph. In the calculation model of a building with flexible slabs, it is recommended to divide the
slabs into several (smaller) fragments, in which the slabs are considered rigid (Fig. 61, b ), and calculate these
fragments separately. 8.13. Block columns are recommended to be considered as cantilevered I-beams of solid
cross-section. Depending on the number and location of doorways in the longitudinal walls of the blocks, two
types of columns are distinguished (Fig. 62).
Fig. 62. Calculation schemes of vertical rigidity diaphragms of a column made of volumetric blocks.
Blocks in columns of the first type have no openings in the longitudinal walls or have one opening. Their cross-
section is formed by summing the sections of walls in the same directions.
Blocks in columns of the second type have at least one opening in each of the longitudinal walls. The columns
are then divided into separate vertical load-bearing elements (in the form of a rectangle, T-section, I-beam, or
channel), connected by over-receiver lintels.
For multi-branch composite bars, to simplify the calculation, it is permissible to present a calculation scheme
composed of two-branch composite bars.
8.14. When calculating a column for bending in the direction of the longitudinal axis of the building due to
eccentric application of vertical loads, as well as when calculating in the transverse direction, two types of
columns are distinguished.
Blocks in columns of the first type have an opening in only one end wall, usually theouter one. Their cross-
section is considered monolithic. The forces in such a column are determined as for a monolithic rod, taking into
account its anchoring at the level of each floor.
Blocks in columns of the second type have openings in both end walls. The column design scheme in this case is
represented by a cantilever composite rod with elastically compliant shear connections dependent on the
flexibility of the lintels.
According to this scheme, the columns are calculated for the action of temporary loads applied after the
completion of installation. It is permissible to use the same scheme when calculating the permanent loads due to
the dead weight of the blocks.
To account for the redistribution of forces between the branches of the composite rod during installation when
calculating the action of loads due to the dead weight of floor panels supported by blocks, it is recommended to
use a floor-by-floor variable design scheme.
8.15. After determining the horizontal axial and eccentric vertical loads in the wall planes, applied to each of the
vertical elements (block columns and panel diaphragms), the forces acting in the plane of the walls should be
calculated for the most hazardous sections.
8.16. Vertical normal stresses in a horizontal joint of a volumetric block column, arising in the areas of block
support due to the action of forces M , M , N perpendicular to the plane of the joint , may be determined using
the formula
s = N/A ± M y/I ± M x/I , (269)
where N , M , M are, respectively, the axial force and bending moments relative to the axes passing through
the center of gravity of the block section;A — area of load-bearing walls of block less openings (in contour
support scheme) or corner sections (in corner scheme); I , I — moments of inertia of horizontal section of
block (in contour scheme) or corner sections (in corner scheme) relative to axes passing through the center of
gravity of section of load-bearing walls of block; х , y — distances from the center of gravity of horizontal section
of load-bearing walls of block (support sections in corner scheme) to the point of determination of ordinates of
diagram s. It is recommended to determine the values of ordinates of diagram for corner points of block, taking
intermediate values by linear interpolation.
8.17. To calculate for bending from the plane of faces of blocks, it is recommended to take into account spatial
work of blocks themselves and, in contour support scheme, their joint work in column (clamping of blocks).
Most significant is clamping of longitudinal (long) walls of blocks. Therefore, a possible simplification of the block
calculation scheme is the introduction of hinged cylindrical connections of the end faces with the longitudinal
faces that do not transmit bending forces.
To determine the maximum values of bending moments along the average cross-section of blocks that do not
have wide (more than 1.2 m) openings in the longitudinal walls, it is possible to replace the spatial column of
volumetric blocks with a flat multi-story frame with elastically compliant connections of the beams and mullions
(Fig. 63, a ).
Fig. 63. Calculation schemes for determining the forces in a column of volumetric blocks taking into account
partial clamping of blocks in horizontal joints
a — column of blocks, b — volumetric block
8.19. To approximately determine the values of bending moments along the average cross-section of blocks
without special programs, it is permissible to use a calculation scheme in the form of a single-story frame, taking
into account additional connections that conditionally replace the influence of the overlying blocks (Fig. 63, b ).
The bending stiffness of additional ties can be approximately determined by the formula
C = ( b ‑ d ) /(12 l ), (270)
where b is the width of the contact area, taking into account the possibility of non-concreting of the edge
sections; d is the possible displacement of the volumetric blocks from the design position horizontally; l is the
compressive flexibility of the mortar joint.
For practical purposes, it is possible to use the same scheme for calculating blocks with asymmetric wall
thicknesses (but differing in thickness by no more than a factor of 2) for asymmetric loads.
8.20. When calculating a block column for bending from the plane of the face, the following loads are taken:
when calculating an individual block — vertical loads distributed on the floor due to its own weight g ;
when calculating a column — vertical loads distributed on the floor, with the exception of loads due to its own
weight ( p — g ); vertical loads Q
distributed along the joint from the support of the floor slab on the block stack, applied with eccentricity e 
relative to the neutral axis of the wall; vertical loads from the overlying floors N distributed along the joint , applied
with eccentricity e relative to the neutral axis of the wall. It is recommended to consider the eccentricities e to be
x y
nt x x x y
x y
nt
x y
con w
3
m
c on
w m
Q
the same along the height of the column. 8.21. The eccentricity e is equal to the sum of the eccentricities e and
e respectively, due to the presence of a geometric eccentricity of the center of gravity of the joint cross-section
relative to the neutral axis of the wall of the lower block and due to a possible deviation from the design value of
the shift of the lower supporting part of the upper block relative to the upper supporting part of the lower block
(Fig. 64). In the absence of experimentally substantiated values, it is recommended to take the values e = 0.5
cm, e = 1 cm. Fig. 64. Schemes for determining the eccentricities at the joint of volumetric blocks 8.22. To check
the strength of each of the load-bearing walls of the block, it is necessary to provide a combination of load
eccentricities e , e and e , which lead to the most unfavorable combination of the normal force and moment
from the plane of the wall (as a rule, M , N ). These values can be conditionally considered for the block as
the eccentricities of external vertical loads applied in the planes of the walls. 8.23. After determining the bending
moment diagram in the middle section of the block or at the edge of the opening, their intermediate values along
the length of the wall may be considered as distributed over a half-wave of a sinusoid with a maximum in the
middle section (at the edge of the opening) and zero at the edge of the wall. 8.24.
The bending moment included in the calculation when determining the load-bearing capacity of the wall for each
vertical section is taken to be maximum in the middle third of the floor height according to diagram M for the
frame formed by this section.
The calculated eccentricity of the compressive force in the middle section of the block shall be taken to be equal
to that obtained from calculating the block (or replacing frame) as a statically indeterminate structure, but not less
than the value e, equal to 0.1 of the section height for h £ 10 cm and 1 cm for h ³ 10 cm. This method can be
used when the calculated value of the eccentricity of internal forces in the middle section of the block does not
exceed the limits of the section core. Otherwise, it is necessary to clarify the calculation model or change the
geometric characteristics of the elements and block joints.
8.25. The bearing capacity of volumetric blocks is checked for two horizontal sections:
in the support section (horizontal joint);
at the intermediate height of the wall (in its middle third), where the maximum bending moment (from the plane of
the wall) acts.
8.26. The strength of the supporting sections (horizontal joints) of volumetric blocks is recommended to be
checked as for platform joints with one-sided support of the floors.
8.27. When checking the bearing capacity of intermediate sections of walls of volumetric blocks by height, it is
allowed to conditionally divide the walls into vertical sections (Fig. 65) andindependently determine the average
bearing capacity N of the divided sections taking into account the value of eccentricity е (vertical forces acting
in each section, after which they are summed up over the length of each wall and compared with the design load
acting on it
(271)
where n is the number of sections of fragmentation of the wall length (without openings); it is recommended to
take n ³ 5. It is advisable to divide ribbed walls with regular vertical ribs into identical sections of a T-section with a
width equal to the distance between the ribs; N is the average bearing capacity of a unit of length of the 1st
vertical section of the wall; b is the length of the 1st section; N , N are the ordinates of the diagram N at the
edges of the wall; l , l , l are the lengths, respectively, of the wall, the section before the opening and opening.
1
2,
1
2
Q 1 2
max
i i
i
i 1 3
1 2
Fig. 65. Diagrams of forces in the walls of a volumetric block
a - without openings; b - with an asymmetrically located opening; c— with a symmetrically located opening; г —
diagram of a volumetric block
8.28. The load-bearing capacity of corner sections of walls (with monolithic connection of adjacent walls) may be
determined separately as for concrete (reinforced concrete) elements of an angle profile with the length of the
angle feathers equal to six wall thicknesses.
The eccentricity of the compressive force at this angle is taken to be at least 2 cm.
If there are openings on one or both sides of the corner section, it is mandatory to take into account the
longitudinal bending of the corner element.
8.29. The design length (height) of block walls (frame uprights) l is taken equal to 0.8 H if at least four storeys
of blocks are located above the design section. In other cases, l = 0.9 H , where H is the storey height minus
the floor thickness.
8.30. When taking into account transport and installation effects, it is necessary to calculate the bearing capacity,
crack resistance and deformations due to corner overhang for an individual block. The deflection of a free corner
of a block supported at three corners is determined by the formula
(272)
where P is the weight of a block symmetrical in wall thickness (excluding the external wall and balcony) taking
into account the dynamic coefficient; Gi , t are the shear modulus and the thickness of the i -th face ( i = 1, 2, ...,
6). For solid faces 
when determining Gi it is permissible to assume that they work without cracking if the condition
P £ 4 htR is met . (273)
For faces with openings, the value of Gi can be determined based on the condition of equality of the horizontal
displacements of the solid face and the face with an opening, which has the same external dimensions.
8.31. In the presence of non-monolithic shear connections connecting individual faces of blocks, their rigidity shall
be included in the value G of the corresponding face.
The possible deflection of the free corner of a block longer than 4.8 m must be limited to 10 mm under static
loads and 15 mm under dynamic loads; for block lengths up to 4.8 m, 7 and 10 mm.
8.32.The load-bearing capacity of a block with a suspended corner may be determined using the limit equilibrium
method. Cracks due to distortions primarily appear and develop in the corners of openings. In a state of limit
equilibrium, these areas in the calculation model should be transformed into plastic hinges. To determine the
o o
o o o
i
,
,
bt,ser
destructive forces on a block and check or select the reinforcement for all faces, the block should be converted
into a spatial mechanism. This requires successively converting each face with an opening into a plane
mechanism; the remaining faces are assumed to be absolutely rigid in their plane.
The load-bearing capacity should be determined in accordance with probable fracture patterns of the faces,
based on the least favorable structural behavior for the longitudinal faces. In this case, the forces from block
torsion and bending in the vertical plane should be summed.
It is recommended to assign reinforcement to block elements 20-30% higher than that obtained from the limit
equilibrium calculation.
8.33. Lintels above and below wall openings when a block corner hangs must be checked for transverse force Q
equal to:
for end faces
Q == P /8; (274)
for longitudinal faces
Q = P ( 3 ‑ b/a )/8. (275)
8.34. All flat elements, including block components (floor panels, external wall panels) must be checked for
strength and crack opening width when subjected to formwork stripping, assembly and transport loads, taking into
account possible changes in the design schemes of the elements when working under these effects.
In this case, the actual minimum strength of the element's concrete at the time of impact is taken into account.
Transportation of volumetric elements is not permitted until the concrete reaches a strength of 0.7 and flat
elements up to 0.5 of the standard resistance.
Formwork stripping forces on the element are taken into account based on special studies, but not less than 20
MPa (200 kgf/m ).
When calculating for transport and installation loads, the effect of dead weight is assumed with a dynamic
coefficient equal to 1.8 during transport and 1.5 during installation.
The maximum short-term crack width is 0.4 mm.
8.35. Horizontal block elements are calculated for vertical transport loads taking into account spatial work and the
actual design scheme (the presence of temporary supports, damping struts, etc.).
The block ceiling slab must be tested for strength under the action of a concentrated standard load of 2000 N (the
weight of two installers with tools).
APPENDIX 2
RECOMMENDATIONS FOR ENSURING THE STABILITY OF LARGE-PANEL BUILDINGS UNDER
EMERGENCY IMPACTS
1. The load-bearing system of residential buildings must be resistant to progressive (chain) failure in the event of
localized failure of individual structures under emergency impacts (explosion of household gas or other explosive
substances, fire, etc.). This requirement means that in the event of emergency impacts not provided for by the
conditions of normal operation of buildings (explosions, fires, impact impacts of vehicles, etc.), localized failures
of load-bearing structures (complete or partial failure of individual walls within one floor and two adjacent axes of
the building) are permitted, but this primary failure must not lead to the collapse of structures or to the failure of
adjacent load-bearing elements to which the load previously supported by the elements damaged by the
emergency impact is transferred.
The building's structural system must ensure its strength and stability in the event of localized failure of the load-
bearing structures, at least for the time required to evacuate people. Movement of structures and the opening of
cracks in them are not limited.
2. The building's resistance to progressive collapse is verified by calculating a specific combination of loads and
impacts, including permanent and temporary long-term loads, as well as the impact of hypothetical local failures
of the load-bearing structures. Permanent and temporary long-term loads must be determined in accordance with
SNiP 2.01.07-85. In this case, the load combination factors and the load safety factors for permanent and long-
term loads should be assumed equal to one.
The impacts of local failures of load-bearing structures are taken into account by removing individual elements
from the building's structural system that could be destroyed during emergency impacts.
For panel residential buildings, the local failure calculation scheme should be considered as the failure (removal)
of two intersecting walls within one (any) floor in sections from their vertical junction (in particular, from the corner
of the building) to the nearest opening in each wall or to the next vertical junction with a wall in a perpendicular
direction.
To assess the building's resistance to progressive collapse, only the most hazardousinterfloor slabs are recommended to be designed with a solid cross-section (single- or three-layer)
or with voids.
Single-layer precast slabs with a solid cross-section are recommended to be designed from heavy-weight or
lightweight concrete of classes no lower than B12.5. For separate and layered floors, the slab thickness is
recommended to be at least 10 cm. For single-layer floors
, the minimum slab thickness is determined by airborne noise insulation requirements. Room-sized slabs
supported along the perimeter, two long and one short sides, or only two long sides are recommended to be
reinforced with welded mesh located in the lower (extended) zone of the slab. Reinforcing bars located along the
short span of the slab are recommended to be partially extended beyond the supports in accordance with the
change in bending moments along the slab span. If half of the bars do not reach the supports, sparse
reinforcement is adopted in sections with a width on each side of the slab no greater than a = 0.14 l - 20 d ,
where l is the length of the short span of the slab, and d is the diameter of the bars.
For precast single-layer slabs 6 m or longer, supported on two short sides or two short sides and one long side, it
is recommended to provide prestressed reinforcement along the long side of the slab. For slabs subject to out-of-
plane bending in two directions, in addition to prestressed reinforcement, it is recommended to install transverse
reinforcement in the form of welded mesh.
Slabs supported on two short sides and one long side may be designed without prestressed reinforcement.
Three-layer precast floor slabs are recommended to be designed as precast. The upper and lower layers are
made of heavy-duty concrete with a lower grade of B15, and the middle layer is made of large-pore concrete
(e.g., expanded clay concrete) with a grade of at least B3.5. The bearing zones of three-layer floor slabs should
be made of heavy-duty concrete throughout the entire slab thickness.
Hollow-core precast floor slabs are recommended to be designed using heavy-duty or lightweight concrete with a
grade of at least B15.
Voids in slabs can be positioned transversely or along the supports, depending on the wall support pattern and
the slab strength across the voids and along the inter-voids ribs.
When platform joints between hollow-core slabs and walls are used, it is recommended to provide structural and
technological measures to increase the strength of the supporting sections.
6.12. For precast slabs, it is recommended to consider their combined out-of-plane bending, ensured by concrete
keyed joints and reinforcement ties. When considering the combined slab performance, the design gap thickness
through which the joint is concreted is recommended to be at least 40 mm.
6.13.When reinforcing precast slabs with welded mesh, it is recommended to use primarily 6-14 mm diameter
class A-III reinforcement rods and 3-4 mm diameter class Bp-I reinforcing wire. To minimize the cost and
consumption of reinforcement, it is recommended to assign the spacing of longitudinal and transverse bars in
welded mesh according to Table 10.
Table 10
Steel diameter,
mm
Steel
grade
Step,
mm
Cross-sectional area A 
, mm /m
Calculated tensile force
N , N/mm
Steel consumption, kg per 1
m2 mesh
 100 71 27.31 0.55
3 Bp-l 200 35 13.48 0.27
 250 28 10.78 0.22
 300 23 8.86 0.18
s
2
s
of
 100 120 47.25 0.99
 150 81 31, 0.66
4 Bp-l 200 63 23.63 0.5
 250 50 18.75 0.4
 300 42 15.75 0.33
 100 283 101.88 2.22
6 A-III 150 189 68.04 1.45
 200 141 50.8 1.11
 250 113 40.7 0.89
 300 94 33.8 0.74
8 A-III 300 168 60.5 1.3
10 A-III 300 261 98 2.04
12 A-III 100 1131 424 8.88
12 A-III 200 5.65 212 2.44
 300 377 141.3 2.96
 100 1539 577 12.1
14 A-III 200 769 288.5 6.1
 300 513 192 4
6.14. The placement and number of lifting loops or openings used for lifting the slabs shall be such as to
eliminate the need for additional reinforcement of the products against installation and transport impacts.
6.15. It is recommended to provide channels for hidden electrical wiring in floor slabs. The diameter of the
channels in solid slabs shall be no more than 30 mm.
It is recommended to seal through technological and communication openings in floor slabs with mortar on
expanding cement or gypsum.
6.16. The depth of support of precast slabs on walls, depending on the nature of their support, shall be no less
than, in mm: for support along the contour, as well as two long and one short sides — 40; for support along two
sides and a span of slabs of 4.2 m or less, as well as along two short and one long sides — 50; When supported
on two sides and the span of the slabs is more than 4.2 m — 70.
When assigning the support depth of floor slabs, the requirements of SNiP 2.03.01-84 for anchoring
reinforcement at the supports should also be taken into account.
6.17. When using precast floor slabs in buildings with monolithic concrete walls, it is recommended to structurally
ensure their continuity on the supports. For this purpose, it is recommended to provide loop connections of the
slabs, monolithed with concrete. To increase the size of the cavity monolithed with concrete, it is permissible to
support the slabs during installation on assembly tables or telescopic supports.
6.18. Precast-monolithic layered slabs are recommended to be designed from a precast reinforced concrete shell
slab, which serves as the remaining formwork, and a layer of monolithic concrete. It is recommended that the
shell slab be made of heavy-duty concrete of at least class B15, 4–6 cm thick. The monolithic layer should be
made of heavy-duty concrete of at least class B12.5 or lightweight concrete of at least class B7.5. The thickness
of the monolithic concrete layer should be no less than the shell thickness.
The lower tensile reinforcement of the slab should be placed in the precast shell slab, using prestressed
reinforcement. The upper tensile reinforcement, necessary to withstand bending moments at the supports, should
be located in the monolithic layer of the slab. To ensure the combined action of the precast and monolithic layers,
it is recommended to provide local recesses on the upper surface of the precast element to form keys and/or
reinforcement outlets.
6.19. Monolithic floor slabs should be designed as single-layer slabs made of heavy-duty or lightweight concrete
of at least class B12.5. It is recommended that the slab thickness be no less than that required for sound
insulation against airborne noise for single-layer floors.
6.20. Monolithic and precast-monolithic floor slabs are recommended to be designed as restrained by walls in the
supporting sections.
When constructing buildings using volumetric-relocatable formwork that is extracted to the façade, the floor slab
is concreted simultaneously with the interior walls. When using precast external wall panels, it is recommended to
consider the floor slab as clamped on three sides with the fourth side free.
For monolithic external walls that are concreted after the construction of the internal structures, the floor slabs,
depending on their junction with the external wall, can be designed as clamped along the contour or along three
sides along the internal walls and with free support on the external wall.
When erecting monolithic external and internal walls in a single cycle (for example, in block or panel formwork), it
is recommended to design monolithic and precast-monolithic floor slabs as clamped along the contour.
6.21. Monolithic floor slabs are recommended to be reinforced with welded meshes. The diameters and pitches of
the longitudinal and transverse mesh reinforcement are recommended to be taken in accordance with Table 10. It
is permitted to use standard meshes produced by industry.
For one-sided support of floor slabs on walls, in case of insufficient anchorage length of the upper mesh, it is
recommended to provide for welding of transverse anchor rods to it.
In continuous floor slabs, the working reinforcementfailure calculation schemes
may be considered:
local failures, including the failure of external walls weakened by doorways leading to balconies and loggias
(Schemes 1, 2, 3 in Fig. 11);
localized damage, including damage to internal walls weakly connected to the remaining vertical structures due to
the presence of doorways (see diagrams 1, 4, 5 in Fig. 11), due to beam cutting of large-span slab floors (see
diagrams 2, 5 in Fig. 11) or due to partial absence of connections through floors (walls adjacent to stairwells;
diagram 4 in Fig. 11).
3. When calculating the resistance of panel buildings to progressive collapse, the standard resistances of
materials are taken in accordance with SNiP 2.03.01-84 and SNiP 11-23-81. The design characteristics of the
resistance of materials, determined by dividing the standard resistances by the safety factors, for concrete and
2
reinforced concrete structures are increased through the use of the safety factors specified in Table 1. In addition,
the calculated resistances are multiplied by service factor coefficients that take into account the low probability of
accidental impacts and the rapid growth of concrete strength in the first period after the building's construction, as
well as the possibility of using reinforcement beyond the material's yield point. Service factor coefficients for
concrete are taken from Table 2; for reinforcement of classes A-I, A-II, and A-III, a single coefficient of = 1.1 is
introduced.
Table 1
Material Stress state or characteristic of a materialConventional designationReliability factor for materials
Concrete Compression
Stretching
y 
y 
1.15
1.25
Reinforcement
Class AI, A-II
Class A-III
Wire
y 
1.1
1.05
1.2
Table 2
Factors determining the introduction of coefficients Conventional
designation
Concrete
performance factor
1. Concrete structures y 0.9
2. Increase in concrete strength over time, except for concrete of class
B50 and higher, concrete on aluminous cement, aluminate and alite
Portland cements
y 1.25
3. Factory-made elements (concrete and reinforced concrete) y 1.15
The design resistances of rolled steel are adopted in accordance with SNiP II-23-81, taking into account the
permissibility of ductile steels operating beyond the yield point. The service factor for ductile steels is assumed to
be 1.1.
4. To assess the resistance of panel buildings to progressive collapse, two types of intact structural elements
should be distinguished. In elements of the first type, the effects of local failures do not cause a qualitative
change in the stress state, but lead only to an increase in stresses and forces (undamaged wall diaphragms and
floor slabs not located above the local failure). In elements of the second type (these include structures that have
lost their original supports—wall panels and floor slabs located above the local failure), the stress state in the
building under consideration changes qualitatively.
Since type I elements are subjected to loads two to three times lower than the failure load under normal operating
conditions, and estimated local failures generally cannot overload these structures by more than twice the failure
load, the strength of type I elements need not be tested. The primary objective of the calculation is to verify the
stability of wall panels and floor slabs located above the local failure and that have lost their support as a result of
the localized wall failure. The stability of these structures depends both on the strength of the suspended
elements themselves and on the strength of their connections to each other and to intact walls.
The building's resistance to progressive collapse should be ensured primarily through the rational design of
connections between precast elements. Reinforcing the precast elements themselves located above the localized
failure is not recommended.
6. To improve the cost-effectiveness of structural solutions for ties that prevent progressive collapse, it is
necessary to enhance their ductility, ensuring that in the ultimate state, after exhaustion of the load-bearing
capacity, the tie does not fail and allows for relatively large absolute deformations (on the order of several
millimeters) without failure.
To ensure the ductility of connections between precast elements, their design solutions must include special
ductile elements made of ductile sheet or reinforcing steel.
A tensile linear tie between precast elements typically consists of a chain of sequentially connected elements—an
anchor of the embedded part, the embedded part, the tie itself, the embedded part of the second element, and its
anchor. Due to the random variability of the resistance of individual elements of this chain and their connections,
the ultimate state of the entire joint is determined by the weakest link. Accordingly, the actual ductility of the entire
connection depends on which element turns out to be the weakest:
If the concrete in which the embedded part is anchored is chipped, the failure will be brittle, with very small
absolute strains preceding the failure of the connection (Fig. 1, a );
If one of the welded joints fails, then, although plasticity will be evident in high-quality welding due to the small
length of the link being broken, the absolute strains preceding the failure of the connection will be comparatively
small (Fig. 1, b );
only if the weakest link in the connection turns out to be the metal connection itself will the entire connection
exhibit the maximum possible plastic properties (Fig. 1, c ).
σ s
b
bt
s
b1
b2
b3
Fig. 1. Diagram of deformation of a stretched linear connection upon failure of its various elements :
a — upon chipping out of the anchoring concrete; b — upon failure of the welded joints; c — in case of failure of a
sheet or rod tie.
Precast element connections that prevent progressive collapse of panel buildings must be designed with unequal
strength, with the element whose failure results in the greatest plastic deformations of the connection being the
weakest.
To meet this condition, it is recommended that all connection elements, except the most plastic, be designed for a
force 1.5 times greater than the strength of the plastic element. For example, anchoring of embedded parts and
welded joints should be designed for a force 1.5 times greater than the tie itself.
Lintels acting as shear ties must be designed to fail due to bending, not due to transverse force.
Keyed shear connections must be designed so that the shear strength of individual keys is 1.5 times greater than
their compressive strength.
In addition to ensuring the plasticity of connections to protect buildings from progressive collapse, it is
recommended to use the following structural measures in combination:
connecting individual interfloor slabs into a single disk using special metal ties that operate in the plane of the
floor in tension and shear;
inserting floor slabs into load-bearing walls in a perpendicular direction, using them as a shear key tie (at platform
joints, such a tie is formed naturally);
Arrange interfloor ties that ensure the operation of horizontal joints between floors and walls in tension and shear.
To arrange such ties, it is recommended to use lifting loops, pins, etc., parts, for example, as shown in Fig. 2.
Such ties are very plastic both in tension and in shear, they ensure the combined operation of all structures
located above the local destruction; the possibility of arranging such ties does not depend on the features of the
building plan.
Fig. 2. Variant of the design solution for an interfloor tie
I — nut; 2 — washer; 3 — lifting pin
6. To calculate the resistance of panel buildings to progressive collapse, it is recommended to use a spatial
calculation model in the form of a system of plates (with or without openings) connected to each other by
concentrated ties, the strength of which is equivalent to the strength of the actual ties between the panels (Fig. 3,
a ). Such a building model must be calculated for all local destructioncalculation schemes of structures selected
in accordance with the recommendations of paragraph 2.
Fig. 3. Calculation model of a building with local failures
1 ¾ local failures
In case of ensuring plastic performance of the building structural system in the limit state, it is recommended to
carry out the calculation using the kinematic method of limit equilibrium theory. In this case, it is permissible to
check the stability of only the elements located above the local failure, and the calculation of the building for each
selected local failure scheme is reduced to the following procedure:
the most probable mechanisms of progressive (secondary) collapse of the building structures that have lost
support are specified (specifying the failure mechanism means determining all destructible connections and
finding the possible generalized displacements ( w ) in the direction of the forces in these connections);
for each of the selected mechanisms of progressive collapse, the strengths of all plastically destructible
connections ( S ) are determined; the resultants of external forces applied to individual links of the mechanism,
that is, to individual indestructible elements or their parts ( G ), and displacements in the direction of their action (
u ) are found: the work of internal forces ( W ) and external loads ( U ) on the possible displacements of the
mechanism under consideration is
determined and the equilibrium condition W ³ U is checked . (1)
This calculation procedure is valid only if the requirements of paragraph 5 regarding ensuring the ductility of
individual panels and the connections between them in the ultimate limit state are met. If the ductility of any
connection is not ensured, its performance should not be taken into account (the connection is considered
absent). If there are many connections and elements susceptible to brittle failure, and their formal exclusion
significantly reduces the building's resistance to progressive collapse, the ductility of the connections should be
ensured or the calculation procedure itself should be modified. In the latter case, the building should be
calculated using an elastic plate model that includes calculated local failure and allows for the changed behavior
of elements that have lost support. The resulting forces in individual elements should be compared with their
calculated load-bearing capacities. The building's stability against progressive collapse shall be ensured if the
condition F £ S is satisfied for any element , where F and S are , respectively, the force in the element found from
the elastic calculation and its calculated load-bearing capacity found taking into account the instructions of
paragraph 3.
Calculation Features of Buildings with Transverse-Wall and Cross-Wall Systems with Non-Load-Bearing
Longitudinal External Walls Made of Lightweight Non-Concrete Materials
7. For buildings with load-bearing transverse and internal longitudinal walls and non-load-bearing non-concrete
longitudinal external walls, the risk of local collapse is determined only by its location on the building plan, but
does not depend on its location along its height. The most dangerous and, therefore, calculated local collapses
are:
collapse of the panel of the end transverse wall adjacent to the corner of the building;
collapse of the panel of the internal transverse wall bearing the load from the hanging loggias or balconies and
weakened by doorways.
The number of calculated local failures of the specified types in each specific case is determined individually
depending on the features of the building plan and the adopted design solutions. With a unified solution for
i
i
i
i
precast elements and connections between them and a relatively simple building plan, it is possible to limit the
consideration to two or three of the most dangerous local failures.
For each selected local failure, it is necessary to consider all the mechanisms of progressive collapse specified in
paragraphs 8 - 11 and check the design conditions corresponding to the case under consideration.
8. The first mechanism of progressive collapse is characterized by a simultaneous downward translational
displacement of all wall panels (or individual parts thereof) located above the local failure (Fig. 4). Such a
displacement is possible when the shear connections between the longitudinal and transverse walls are
destroyed (Fig. 4, a) or in case of destruction of the lintels and floor slabs above the openings (Fig. 4, b , c ).
When assessing the possibility of simultaneous collapse of the structures of all floors, the equilibrium condition
(1) is replaced by the condition
W ³ U (2)
where W and U are, respectively, the work of internal and external forces on the displacements of the elements
of one floor; the floors are separated by the lower surface of the floor, which belongs to the floor located above
the floor.
If the floor slabs are not inserted into the longitudinal load-bearing walls, collapse is prevented only by the shear
connections between the panels of the destroyed transverse wall and the longitudinal wall (Fig. 4, a ). In this
case, the equilibrium condition (2) is equivalent to the requirement
S ³ G + G + 0.5( G¢ + G¢¢ ) + 0.5( q¢L¢l¢ + q¢¢L¢¢l¢¢ ), (3)
where S is the strength of the shear bonds in the vertical joint between the longitudinal and transverse walls; G
 , G are, respectively, the weight of the transverse wall panel and the load from the loggia falling on it; G¢ 
, G¢¢ are, respectively, the weights of the external wall panels adjacent on both sides to the destroyed
transverse wall; q' , q¢¢ is the uniformly distributed load on the floor slabs; L' , L" , 1' , 1" are the dimensions of
the floor slabs resting on the destroyed wall.
f f
f f
1 w,in l w,ex w,ex
1
w,in l w,ex
w,ex
Fig. 4. Variants of the type I progressive collapse mechanism
If the floor slabs are inserted into longitudinal and transverse walls (platform joints), they form a practically
indestructible shear connection between them. In this case, only those types of type I collapse mechanism are
considered that are possible when the transverse wall is weakened by doorways (see Fig. 4, b , c ). In this case,
condition (2) takes the form
W + W ³ U + U + U , (4)
where W , U —respectively, the work of internal and external forces on the displacements of individual
parts of the internal wall panel; W , U — respectively, the work of internal and external forces applied to the
floor slabs; U — the work of external forces applied to the external panels.
The work W is determined by the bending resistance of the above- and below-the-lintels and, in the general
case, is determined by the relationship
W = ( M¢ + M¢¢ + M' + M" )/ b , (5)
where M¢ , M¢¢ , M' , M" — respectively, the bending strength of the left and right support sections of
the upper and lower lintels, and b is the span of the lintels.
If the transverse wall is separated from the longitudinal wall by a doorway and there is no connection between
them, then W = 0. If the connection between the transverse and longitudinal walls is realized by a lintel - a
“flag” (see Fig. 4, c ), then the strength of the left support section ( M¢ ) is determined by the strength of the
horizontal linear connection ( S ); in this case, the strength of the shear connection, in accordance with the
recommendations of paragraph 4, must satisfy the condition
S ³ l.5 M¢¢ / b . (6)
The work U is determined by the weight of the collapsing part of the internal wall panel aG , (where G 
is the weight of the entire panel, 0in the direction of the longitudinal walls and the span in the transverse direction
for the building; M ( M¢ ), M ( M' ) are the bending moments supported by the i -th floor slab during its
bending according to the beam scheme, respectively, along the spans l , and L under tension of the lower fibers
(upper fibers); t is the width of the doorway in the internal wall (see Fig. 4, b , c ); f is the reference of the
beginning of the opening to the internal end.
I 
w,in
I 
p
I 
w,in
I 
p w,ex
I 
w,in
I 
w,in
I 
p
I 
p
w,ex
I 
w,in
I 
w,in sup sup inf inf
sup sup inf inf
I 
w,in
sup
2
1 sup
w,in w,in w,in
l
I 
w,in w,in l
I 
p
I 
p
I 
p p
I 
p
I 
p
i i
1 i 1i 2i 2i
i i
If the floor is made of beam slabs, then in inequality (9) we adopt
W = 0; U = 0.5 ( q¢L¢l¢ + q¢¢L¢¢l¢¢ ). (10)
The work of the forces caused by the weight of the external panels adjacent to the damaged wall on the left and
right ( G¢ and G¢¢ ) is approximately calculated as follows:
U = 0.5( G¢ W¢ + G¢¢ W¢¢ ). (11)
Fulfilment of requirement (4) is a necessary condition for preventing progressive collapse of the building with
comparatively small displacements (less than 10 cm) of the structures that have lost support. If it is met, one
should proceed to checking the additional conditions set out in paragraphs 9 - 11.
If condition (4) is not met, two options are possible:
first, by strengthening (or redistributing) the reinforcement of the lintels of internal walls and floor slabs, it can be
achieved;
the second is to move on to other structural methods of protection against progressive collapse, allowing for very
large displacements (tens of centimeters) of elements that have lost support and requiring, accordingly,
calculations to be performed using a deformed model (see paragraph 12).
9. The mechanism of progressive collapse of the second type is characterized by the simultaneous rotation of
each wall panel located above the local destruction, around its center of rotation (Fig. 5). Such a displacement
requires the destruction of the tensile connections of these panels with the intact wall ( S ; in Fig. 5, a),
destruction of the shear bonds of the wall panels with the floor slabs in the horizontal joints ( S in Fig. 5) and
plastic fracture of the floor slabs, initially supported on three sides, according to the scheme shown in Fig. 5, d .
Fig. 5. Mechanism of progressive destruction of type II
In the case under consideration, condition (2) takes the form
I 
p
I 
p
w,ex w,ex
w,ex w,ex w,ex w,ex w,ex
2
3
W + W ³ U + U + U , (12)
where W , U , U , U ¾ are the same as the quantities W , U , U , U in (4), and W 
is the work of the resistance forces of the bonds ( S and S ) of the exchange panels that have lost support,
with intact structures. Individual terms from (12) are calculated as follows:
W = S y /L + S h/L ; (13)
U = G x/L + G , (14)
where y , h , x are the distances from the center of rotation to the line of action of the forces S , S and the
force of gravity G (see Fig. 5); W , U are calculated using formulas (8) with the appropriate replacement
of the superscript, where
W = ( M' / l + M¢ / L ) w ; U = q L l u /6. (15)
Here, all quantities have the same meaning as in (9); the quantity U is calculated using formula (11).
Condition (12) should be satisfied primarily by increasing the shear ties ( ) , since increasing the strength of the
tensile tie ( ) is not always possible (Fig. 5, b ), and is sometimes impractical: if a transverse wall is attached to
a longitudinal wall only on one side, then to take this tie into account in the calculation, it is necessary to estimate
the strength of the longitudinal wall in bending from its plane (see Fig. 5, c ).
10. In addition to the non-collapse conditions (4) and (12), it is necessary to estimate the possibility of collapse of
only the floor slabs located directly above the knocked-out panel of the transverse wall and initially supported on
three sides (third mechanism).
In order to prevent these slabs from collapsing, it is sufficient to fulfill the condition
W ³ U + U ‑ S w , (16)
where S is the strength of the shear connection between the curtain wall panel and the transverse wall (Fig. 6);
in formula (16), S is taken from the calculation, but not more than the value of U .
Fig. 6. Scheme of collapse of floor slabs
If relation (16) is not fulfilled, this means that the slabs must be attached to the transverse wall located above by
ties that perceive tension (Fig. 6). Then condition (16) is replaced by the following:
W + W ³ U + U ‑ S w , (17)
where W is the work of the tensile forces of ties S . This work is calculated by the formula
W = nS wx /L , (18)
n is the number of ties; x is the coordinate determined by the line of action of the resultant reaction of the
connections under consideration, assuming that all of them have reached their limiting value, S .
If the floors are made of beam slabs, condition (16) is not satisfied ( W = 0); therefore, in this case, the
installation of connections of the type under consideration is mandatory. In this case, their strength is determined
by the magnitude of the support reactions of each beam slab.
11.The fourth collapse mechanism involves the displacement of structures of only one floor, located directly
above the knocked-out panel of the transverse wall (Fig. 7). This mechanism involves a combination of
translational displacement of the transverse wall (as in the first mechanism) with the fracture of slabs,
characteristic of the second mechanism (see Fig. 5, c , d). Such a mechanism is possible only if the transverse
wall is weakened by door or window openings.
Fig. 7. Diagram of collapse of structures of one floor
Condition for the impossibility of forming a mechanism of the type under consideration
W (1 ‑ c / L ) + W + W ³ (1 ‑ c / L ) U + U + U ‑ S ( w ‑ w ), (19)
where W is the work of tensile forces of vertical ties of types S and S ;
II 
t
II 
p
II 
w,in
II 
p w,ex
II 
p
II 
w,in
II 
p w,ex
I 
p
I 
w,in
I 
p
I 
w,ex
II 
t
2 3
II 
t 2 2 3
II 
w,in w,in l
2 2 3
w,in
II 
p
II 
p
II 
pi 1i i 2i i i
II 
pi i i i i
w,ex
 S3
 S2
II 
p
II 
p w,ex 4 w,ex
4
4 w,ex
II 
p
III 
t
II 
p w,ex 4 w,ex
III 
t 5
III 
t 5 5
5
5
II 
p
I 
w,in
II 
p
IV 
t
I 
w,in
II 
p w,ex 4 w,ex w,in
IV 
t 5 6
(20)
where k is the number of ties of the sixth type; S , S — ultimate forces in ties of types sixth and fifth; w —
displacements in the direction of the i -th tie of type five, defined as the difference in displacements of the tie
attachment point to the slab and the tie attachment point to the transverse wall panel.
If, in the absence of ties of type sixth ( S = 0), condition (19) is not satisfied, it is not recommended to achieve its
fulfillment by strengthening ties of type fifth — this is uneconomical, since these ties, as follows from equation
(20), operate unevenly. In this case, the most rational solution is to install ties of type sixth and form a tie of the
type described in paragraph 5.
12.If, in the event of localized failure of an internal transverse wall, condition (4) cannot be met, i.e., progressive
collapse cannot be prevented according to the first scheme (see Fig. 4), it is recommended to use special ties
between the floor slabs to ensure their effective resistance to progressive collapse, even with large deflections as
elements of the suspension system (Fig. 8). This approach is usually more appropriate and necessary for
localized failure of a transverse wall located significantly away from the other load-bearing walls and connected to
them only by beam floor slabs or lightly reinforced large-span slabs, initially supported on three sides.
Fig. 8. Performance of Floor Slabs as Elements of a Suspension System
The requirements to be met by the ties and slabs forming the suspension system follow from the calculation using
the deformed scheme (see Fig. 8, b ): the chain ofsuccessively connected elements (tie — slab — tie — slab —
tie) must include a highly flexible link that would provide a total chain elongation of the order of several percent
(naturally, any cracks in the slabs are allowed). To meet this condition, it is necessary that
(21)
where G is the linear load falling on the destroyed wall from each floor
G = 0.5 q ( l¢ + l¢¢ ) + G / L ;
N is the linear bearing capacity of the weakest link of the suspension chain; e is the calculated relative elongation
of the slab with a smaller span (more precisely, the relative increase in the distance between the junction points
of this slab with other slabs); w is the deflection at which equilibrium is achieved; l , l — the minimum and
maximum spans, respectively.
Relationships (21) are obtained from the assumption that, due to random variability in the strength of materials,
the maximum possible elongation is realized in only one slab. Thus, in the case of l = l = l with e = 4 ¸ 6%,
it follows from (21) that N = (2 ¸ 2.5) and w = (0.2 ¸ 0.25) l .
The maximum possible relative elongation of a slab depends significantly on the design of its reinforcement and
the connections between the slabs, on the strength ratio of individual elements, on their ductility, and on the
strength of the connection between these elements; it is generally impossible to determine this value theoretically,
and therefore it is recommended to evaluate each specific design solution experimentally.
Calculation Features of Buildings with Cross-Wall Structural Systems with External Walls Made of
Concrete or Reinforced Concrete Panels
13. For the calculation of buildings with reinforced concrete external walls, the same basic types of progressive
collapse mechanisms should be used as for buildings with non-load-bearing external walls made of lightweight
6 5 i
6
w,in
min max
min max
non-concrete materials. However, it should be noted that the formation of these mechanisms requires the failure
of not only the internal wall panels and floor slabs, but also the external wall panels, which in this case are
necessarily included in the process, even if they are designed as curtain walls.
External wall panels with an opening, regardless of the type of general progressive collapse mechanism, operate
in distortion like rectangular frames (Fig. 9). Moreover, if the floor slabs are inserted into the external walls, they
are also involved in the process, and the nature of their failure changes—to the primary plastic hinges shown in
Fig. 4 and 5, hinges associated with the fracture of the outer edge of the slab are added (Fig. 10). When checking
the possibility of collapse of floor slabs alone (see p. 10), these hinges are not included.
Fig. 9. Work of external wall elements
Fig. 10. Work of floor slabs in buildings with reinforced concrete external walls
In order to take into account the resistance of external walls to progressive collapse and the associated additional
resistance of floor slabs, it is necessary to calculate the work of the corresponding internal forces ( W )
according to p. 14 and use it when checking the equilibrium conditions specified in p. 15.
14. In order to take into account the resistance of an external wall to progressive collapse, it is necessary to
calculate the work of internal forces during the destruction of external wall panels of a typical floor ( W ).
Since, in the case of local failure of the internal wall, progressive collapse on each floor is resisted by two panels
of the external wall (or one two-module panel), the value of W in the general case is considered as the sum of
the terms
W = W¢ + W¢¢ . (22)
The magnitude of the work W¢ ( W¢¢ ) depends on the ratio of the geometric dimensions of the panel
and the reinforcement of its lintels and piers, as well as on the presence of an opening for a balcony door in it. In
the general case, any external panel can be considered as a frame that collapses due to the formation of four
plastic hinges in it (see Fig. 9, b , c ), so that
(23)
In this case, the ultimate bending moments acting in the corner hinges (for example, M¢ — in the upper left
corner), are defined as the smaller of the two values of the bending load-bearing capacity of the lintel and pier
forming this corner.
In the case of local failure of the transverse wall adjacent to the corner of the building, the panel of the external
wall may fail according to the rigid disk rotation scheme (see Fig. 9, a ); in this case, the work of the internal
forces will be determined by the strength of the shear connection of this panel with the overlying floor ( V ) and
the tensile connection with the adjacent façade panel ( S )
W = ( S + V ) h/l. (24)
Of the two possible values of W , determined by formulas (23) and (24), the smaller one is taken into account
in further calculations.
15. To take into account the resistance of an external wall to progressive collapse, it is first necessary to ensure
that it “supports itself”, that is, to check the condition
R = W ‑ U > 0, (25)
in which the work of external forces U is determined by formula (11).
In cases where condition (25) is not satisfied ( R R (28)
In this case, the verification of the possibility of progressive collapse is carried out sequentially according to the
recommendations of paragraphs 8 - 11 with the following minor changes:
in relations (4) and (12), the work U is replaced by the value - R ;
in formulas (16), (17) it is assumed that U = S w ;
in formula (19) it is assumed that U ‑ S ( w ‑ w ) = ‑ R .
If the floor slabs are inserted into the external wall, then the shear connection between the internal transverse
w,ex
w,ex
w,ex
w,ex w,ex w,ex
w,ex w,ex
sup
w,ex
w,ex
w,ex w,ex w,ex
w,ex
w,ex
w,ex w,ex
4
4 w,ex
w,ex w,ex
w,ex 4 w,ex
w,ex 4 w,ex w,im w,ex
and longitudinal external walls may not be installed ( S = 0), and to assess the protection of the building from
progressive collapse, only conditions (4) and (12) are checked for
U = ‑ R ‑ W , (27)
where W is the additional work of the floor slabs associated with the fracture of their outer edge inserted into
the external wall; this work depends on the type of progressive collapse mechanism under consideration.
The resistance of the outer edge of the floor slab inserted into the outer walls creates additional work of internal
forces calculated for the collapse mechanism of the first type (see Fig. 10, a ) for the i -th slab
(28)
where e , d , S are the attachments of the edge hinges in the slab, and the remaining quantities are the same
as in (9).
For the collapse mechanism of the second type
(29)
When using formula (27), it should be remembered that it is applicable only for R > 0, that is, for U = ‑ ( R
 + W ) R , then U = ‑ R ;
if S w £ R , then U = S w ; W = 0, (30)
where Si the bearing capacity of the tension connection between the outer wall and the floor.
Example of calculating the stability of structures against progressive collapse under emergency impacts
applicable to 9-story large-panel buildings
1. Initial data. The structural systemof the building is transverse-wall with a mixed (600 + 300 cm) step of
transverse load-bearing walls (Fig. 11). Floor heighth = 280 cm. External walls are 35 cm thick, single-layer
expanded clay concrete, two-module at 600 cm pitch, single-module at 300 cm pitch; internal walls are 16 cm
thick, made of heavy concrete B15 (Fig. 12 and Table 3). Solid floor slabs are 16 cm thick, made of heavy
concrete B15 and B20, reinforced with a bottom mesh.
Fig. 11. Fragment of a residential building
4
i 
w,ex
i 
w,ex
i 
p,bor
i 
p,bor
i i i
w,ex w,ex
w,ex p,bor
w,ex 4 W,ex
7 w,ex w,ex w,ex
7 w,ex w,ex 7 w,ex
is
f
Fig. 12. Wall panels
Characteristics of panels DesignationUnit of
measurement
External
walls
Internal
walls
Floor
slabs
 P1 P2,
P3
Concrete class In ¾ B7.5 B15 B15 B20
Standard resistance of concrete to axial
compression R MPa 5.5 11 11 15
Standard resistance of concrete to axial
tension R. MPa 0.7 1.15 l,15 1.4
Condition coefficients y ¾ 1.25 1.25 1.251.25
work y ¾ 1.15 1.15 1.151.15
Panel thickness t mm 350 160 160 160
Standard loads on floors: permanent load g = 5.8 kN/m ; long-term (part of temporary load) q = 0.5 kN/m .
Total q = ( g + q ) = 6.3 kN/m .
Standard load on loggias g = 0.6 kN/m .
Calculation is made according to Appendix 1. Bearing capacities of elements are determined according to SNiP
2.03.01—84. The most dangerous cases of the location of hypothetical local destructions on the building plan in
accordance with paragraph 7 are shown in Fig. 11. Here, as an example, destruction schemes No. 1 and No. 2
are considered.
2. Checking the stability of the building with local destruction of its load-bearing structures according to scheme
No. 1. (Fig. 13). The collapse of the structural cell in axes 1-3 and B-C of the i -th floor is considered. The initial
failure occurs with the internal wall panel along axis 2 between axes B and C and the adjacent piers of external
wall panels along axis B. The impossibility of collapse of the structures of floors and wall panels hanging above
the local failure is checked. In this case, progressive collapse is resisted by two slabs P1 on each floor; second-
type tension ties connecting the internal transverse wall with the longitudinal internal wall; shear ties between the
external walls and the internal one; two external wall panels collapsing like frames with the formation of four
plastic hinges (see section 14).
b
b p
bt,n
b1
b2
w
2
l
2
l
2
l
2
Fig. 13. 1st diagram of fracture of elements of fragment
2.1. Calculation of the bearing capacity of individual sections of structural elements.
2.1.1. External wall panel НС1. The design resistance of materials is determined according to the instructions of
section 3 of this appendix.
Concrete: R y y / y = 5.5/1.15 × 1.15 × 1.25 = 6.9 MPa; R = R y y y = 0.7 × 1.15/1.25 × 1.25
= 0.805 MPa.
Reinforcement with a diameter of 8 mm, class A-III R = 390/l.05 × 1.1 = 408 MPa.
Upper lintel
The bending capacity of the upper lintel is determined according to SNiP 203.01-84 at As = 1.508 cm (3 rods
with a diameter of 8 mm, made of steel class A-III); b = 35 cm; h = 29 cm; h = 29 - 3 = 26 cm.
The section is symmetrical.
The height of the compressed zone x = ( R A )/( R b ) = (408 × 150.8)/(6.9 × 350) = 25.5 mm
Bearing capacity of sections M = M = R bx ( h ‑ 0.5 x ) = 6.9 × 350 ´ 25.5(260 ‑ 0.5 × 25.5) = 15.2 × 10 
N×mm = 15.2 kN×m.
The impossibility of brittle failure of the elements of the external panel is checked in accordance with the
requirements of clause 5. When the external wall is destroyed as shown in Fig. 13, b , the value of the transverse
force corresponding to the occurrence of ultimate bending moments in the upper lintel with a coefficient of 1.5 is
equal to: Q = 1.5( M + M )/ l = 1.5(15.2 + 15.2)/1.61 = 28.3 kN.
The transverse reinforcement consists of stirrups of 3 rods with a diameter of 5 mm made of grade Bp-1 steel,
pitch s = 200 mm: A = 0.59 cm ; R = 395/1.2 × 1.1 × 0.8 × 0.9 = 261 MPa.
The strength along an inclined strip between inclined cracks is checked from the condition: Q £ 0.3 j j R bh
 m = A /( bs ) = 59/(350 ´ 200) = 0.00084; a = E / E = (17 × 10 )/(16 × 10 ) = 10.6; j = 1 + 5 am =
1 + 5 × 10.6 × 0.00084 = 1.04; b = 0.02; j = 1 ‑ bR = 1 ‑ 0.02 × 6.9 = 0.862; 0.3 j j R bh = 0.3 × 1.04 ×
0.862 × 6.9 × 350 × 260 = 169,000 N = 169 kN > 28.3 kN.
The strength condition is met.
The strength along an inclined crack is checked by the condition Q £ Q + Q , where Q = j (1 + j + j ) R
 bh / c , j = 1.9; j = 0; j = 0; (1 + j + j ) = 1.
The check is performed twice: for c = 200 mm and for c . c = 200 mm, Q = 0; Q = (l.9 × 0.805 × 350 × 260 
)/200 = 180.9 × 10 = 180.9 kN > 28.3 kN.
The strength condition is met.
where q = ( R A )/ S = (261 × 59)/200 = 77 N/mm;
 Q = q c = 77 × 686 = 52822 N = 52.8 kN; Q = (1.9 × 0.805
× 350 × 260 )/686 = 527.52 N > 52.8 kN; Q + Q = 52.8 × 2 = 105.6 kN; 28.3 kNFig. 13), 13 - 15 of this appendix. 2.3.1.
Analysis of resistance of external walls. Since this example considers a building with external walls made of
reinforced concrete panels, in accordance with the instructions of paragraph 14, the calculation should begin with
an assessment of the resistance to progressive collapse of the external wall panels and only then proceed to
checking the possibility of forming various types of progressive collapse mechanisms, as described in paragraphs
8 - 11. The assessment of the resistance of external wall panels to progressive collapse is performed using
formulas (22), (23).
On the left and on the right there are identical panels НС 1, their destruction is the same, the ultimate bending
moments are adopted according to paragraph 2.1.1: M¢ = M¢¢ = 15.2 kN×m; M¢ = 2.9 kN×m; M¢¢ =
0; l = 1.61 m; l = 0.89 m; w = 1.
The work of internal forces is determined by formula (23): W' = W¢¢ = (15.2 × 2/1.61 + 2.9/0.89)1 = 22.1
kN, W = 2 × 22.1 = 2 kN.
The work of weight forces is determined by formula (11) with G¢ = G¢¢ = 26.6 kN; U = 2 × 0.5 × 26.6
× 1 = 26.6 kN.
Condition (25) is verified: R = W ‑ U > 0, R = 44.2 – 26.6 = 17.6 kN > 0.
The condition is met.
2.3.2. Collapse resistance of floor slabs. The floor slabs are inserted into the external walls, therefore the
resistance of their outer edge is determined for them according to clause 15. The left and right slabs are identical,
their fracture patterns are also identical and are shown in Fig. 13, c . The bending moments supported by the
sections of slab P1 are taken according to clause 2.1.2: M¢ = M¢ = 0; M = 49.4 kN×m; M = 9.7 kN×m.
The resistance of the outer edge of the floor slab inserted into the external walls is calculated using formula (29)
s
2
o
in f 1
2
b3 n bt
2 
o b3 n b3 n bt
2 
o
- 3
sup sup inf inf
1 2
o
2
Rs = 405 MPa
M1 =
o s
2
s
2
3
st
2
2
sup sup inf inf
sup inf
w,ex w,ex
w,ex
w,ex w,ex w,ex
w,ex w,ex w,ex w,ex
1 2 1 2
of this appendix, which in the case of M¢ = M¢ = 0 takes the form W = s ( M / L + M / l ) w / d ,
then with s = s = 0.6 m and d = d = l.61 m for each plate we obtain:
W = W = 0.6/1.61(49.4/5.4 + 9.7/3) × = 4.6 kN; W = W + W = 2 × 4.6 = 9.2
kN.
Now, using formula (27), we determine U = ‑ R ‑ = ‑17.6 ‑ 9.2 = ‑26.8 kN×m, and then the entire
calculation is performed in accordance with the requirements of clause 9.
The work of internal and external forces on the movements of floor slabs is calculated using formulas (15): W 
= W = W = 0 when
M' = M¢ = M ' = M' = 0;
 
2.3.3. The work of connections is determined using formula (13), which, when S = 0, takes the form: W = S 
y /L.
In clause 2.1.3, it is defined that S = 53.1 kN; y = 2.6 m (wall height); L = 5.4 m; W = 53.1 × 2.6/5.4 = 25.5
kN.
2.3.4. Work of the transverse internal wall. The panel of the internal wall rotates like a rigid disk, and the work of
the weight forces is determined by the formula (14) U = G x / L + G , where G = 54.9 kN; G = 2.2
kN; x = 0.5 L ; U = 54.9 × 0.5 + 2.2 = 29.7 kN.
2.3.5. Checking the general condition for the impossibility of forming a mechanism of the second type. The check
is carried out using the formula (12)
W + W > U + U + U ; W + W = 25.5 kN;
U + U + U = 29.7 + 25 ‑ 26.8 = 27.9 kN > 25.5 kN.
The equilibrium condition is not met. It is necessary to either strengthen the connection of the second type or
install connections of the third type.
In the latter case, the required bearing capacity of the connections, taking into account formula (13), is
determined by S = (27.9 - 25.5) L / h = (2.4 × 5.4)/ 2.6 = 5 kN, which corresponds to the cross-sectional area of 
the rod made of A-I steel A = 5 × 10/235 = 0.21 cm .
2.4. Assessment of the possibility of occurrence of the progressive collapse mechanism of the third type.
The check is carried out in accordance with paragraph 10. For the third collapse mechanism, the collapse of only
the floor slabs located directly above the knocked-out panels is considered; the clamping of the slabs in these
panels is not realized and, in accordance with the requirements of paragraph 15 of this appendix, in formulas (16)
and (17), it is necessary to take U ‑ S w = 0. Then formula (16) takes the form: W ³ U , where W 
= 0, U = 25 kN (see paragraph 2.3.2).
Condition (16) is not satisfied (0 25 kN, the non-collapse
condition is met.
2.5. Assessment of the possibility of occurrence of the fourth type of progressive collapse
mechanism.Since the internal transverse wall has no openings, and the floor slabs are inserted into the walls,
this collapse mechanism is impossible (see paragraph 11).
3. Checking the building stability under localized collapse of its load-bearing structures according to scheme No.
2. The collapse of a structural cell in axes 2–5 and A–B (Fig. 14) on the i -th floor of the building is considered.
The initial collapse occurs with the internal wall panel along axis 3 between axes A and B and the two adjacent
piers of the external walls along axes A and B. The impossibility of collapse of the overhanging structures of the
floors and wall panels above this local collapse is checked. In this case, progressive collapse is resisted on each
floor by the internal wall panel; shear and tension ties connecting it to the internal longitudinal walls; floor slabs to
the left and right of axis 3; external walls and shear ties between the external walls and the internal wall panel.
1 2
II 
pi,bor i 1i i 2i i i i
1 2 1 2
II 
p 1 ,bor
II 
p 2 ,bor
II 
p,bor
II 
p 1 ,bor
II 
p 2 ,bor
w,ex w,ex Wp,bor
II 
p
II 
p 1
II 
p 2
11 12 21 22
3
II 
t 2
2
2 2
II 
t
II 
w,in w,in 1 w,in 1
II 
w,in
II 
t
II 
p
II
w,in
II 
ð w,ex
II 
t
II 
р
II 
w,in
II 
ð р ,ex
3
s
 2
w,ex 4 wex
II 
р
II 
ð
II 
р
II 
ð
5 5
II 
р w,ex 4
wex
III 
t
II 
ð
III 
t 5 5
Fig. 14. 2nd diagram of fracture of fragment elements
3.1. Calculation of the bearing capacity of individual sections of structural elements.
3.1.1. External wall panel НС1. The bearing capacities of the panel sections upon fracture (as a frame with four
plastic hinges) will be adopted based on the calculation results given in p. 2.1.1: M¢ = M¢¢ = 15.2 kN×m;
M' = 2.9 kN×m; M¢' = 0.
3.1.2. External wall panel НС2. The panel is two-module; upon loss of one support, it functions as a frame with
formation of four plastic hinges.
Limit bending moments in sections of the upper lintel. At R = 12.6 MPa; R = 405 MPa; А = 1.01 cm ; b = 35
cm, h = 46 cm are determined by analogy with the lintels of the НС1 panel, and are equal to M = M = 17.3
kN×m.
The ultimate bending moments in the sections of the sill lintel at A = 1.01 cm ; b = 35 cm, h = 87 cm, are
equal to M = M = 34.5 kN×m.
The bearing capacity of the piers in bending is obviously greater than that of the lintels, since with the same
reinforcement as the lintel, they have a greater section height.
The possibility of panel failure due to the action of a transverse force is checked as shown in the calculation of
the НС1 panel. This calculation is not presented here; it gives a satisfactory result.
The ultimate bending moments acting in the corner hinges of the frame are equal to M¢ = M¢¢ = 17.3 =
17.3 kN×m; M¢ = M¢¢ = 34.5 kN×m.
3.1.3. Floor slabs. The ultimate moments in the sections of slab P1 are taken from the calculation given in clause
2.1.2: M¢ = M¢ = 0; M = 49.4 kN×m; M = 9.7 kN×m.
Floor slab P2 does not have upper reinforcement, therefore M' = M¢ = 0. With characteristics h = 16 cm,
concrete class M20, R = 18.8 MPa determine the bearing capacitiesof the sections.
Bending along the short side: b = L = 600 cm, h = 14.5 cm, A = 6.09 cm (31 rods with a diameter of 5 mm
made of wire of class Bp-I); R = 362 MPa, M = 32.1 kN×m. Bending along the long side: b = l = 300 cm; h =
13 cm; A = 35.41 cm (23 rods with a diameter of 14 mm made of steel of class A-III); R = 405 MPa; M =
150.4 kN×m.
Floor slab P3 is similar to slab P2 in dimensions, concrete class, section height and reinforcement, therefore the
bending capacities of its sections are equal to M¢ = M¢ = 0; M = 32.1 kN×m; М = 150.4 kN×m.
3.1.4. Internal wall panel. The flexural strength of the lintel-flag section is determined by analogy with the sections
of external wall lintels with the following characteristics: h = 52.5 cm; R = 13.8 MPa; b = 16 cm; А = 1.508 cm 
, R = 405 MPa. Ultimate bending moment М¢¢ = 29.7 kN×m.
The shear tie strength S is determined according to the recommendations of section 5.36 and formula (124).
Manuals: S = h R A , where h = 0.7; R = 235 MPa, A = 2.260 cm (2 rods with a diameter of 12 mm
made of steel class A-I), S = 0.7 × 235 × 226 × 10 = 37.2 kN. Next, condition (6) is checked: S > l.5 M¢¢ 
sup sup
inf inf
b s s
2
1 2
s
2
1 2
w,sup w,sup
w,inf w,inf
11 21 11 21
12 22
b
o s
2
s 12 o
s
2
s 22
13 23 13 23
b s
2
s sup
1
1 fr s s,tr fr s s,tr
2
1
-3
1 sup
/b , l.5 M¢¢ /b = l.5 × 29.7/1.35 = 33 kN 0. R = 113.8 — 30.5 = 83.3 kN > 0, the
condition is satisfied.
3.2.2. Collapse resistance of floor slabs.
a) The left floor slab has the characteristics: M¢ = M¢ = 0; M = = 49.4 kN×m; M = 9.7 kN×m; L = 5.4 m;
t = 1.35 m; f = 0. For the first collapse mechanism, the resistance of the outer edge is determined by formula (28),
which in the case of M¢ = M¢ = 0 takes the form:
Here s = 1.32 m; d = 0.89; e = 0.79 m (Fig. 15, b ).
The work of internal and external forces on the displacements of the floor slab P1 is calculated by formula (9)
when M¢ = M¢ = 0 W = M / t = 97/1.35 = 7.2 kN; U = 0.5 ql ( L ‑ 2/3 t ) = 0.5 × 6.3 × 3(5.4 ‑ 2/3 ´
1.35) = 42.5 kN.
b) Floor slab P2 (see Fig. 15, c , d).
Since Appendix 2 does not consider the case of cutting a floor in a room into two or more slabs, the work of
internal and external forces is determined by the formulas in paragraph 6. 
The fracture diagram of slab P2 is shown in Fig. 15, d., the dotted line indicates a plastic hinge with tension of the
lower reinforcement. The direction of this hinge is chosen such that the work of the internal forces is minimal.
From the geometric relationships we find h = 1.55 m; h = 1.03 m; a = 20.1°. The angle of fracture of the slab in
the plastic hinge w = (0.911 - 0.048)/1.03 - (1 - 0.911)/1.55 = 0.781 1/m.
sup
2
sup 2 o
inf inf
1 s,tr
2
4
sup inf sup
inf inf inf w,ex
sup inf
sup sup inf inf
w,ex
w,ex
w,ex w,ex
w,ex
w,ex w,ex
w ,ex W,ex w,ex w ,ex
11 21 11 21
11 21
11 21
I 
p1 21
I 
p1
1 2
Fig. 15. Possible fracture patterns of floor slabs
Ultimate bending moment in the section along the hinge line M = M a cos a/L + M a sin a/l = 32.l/6 × 4.5
× cos 20.l° + 150.4/3 × 1.65 × sin 20.1° = 53.4 kN×m. W = M = 53.4 × 0.781 = 41.7 kN. U = 1/6 ×
6.3[[4.5 × l.65(l + 1 + 0.25) + 1.5 × 3(0 + 0 + 0.25) + l.35 × 4.5(0 + l+ 0.25)] = 26.7 kN.
c) Floor slab P3 (see Fig. 15, d , e ).
Reinforcement of slab P3 is similar to slab P2. Bearing capacity of slab cross-sections in bending M = 32.1
kN×m; M = 150.4 kN×m. Plastic hinges pass through the edges of the window opening in the external wall
(Fig. 15, e). A plastic hinge with tension of the lower fibers occurs in the slab due to its clamping in the external
walls, therefore the work of internal forces on the displacements of this hinge is related to the resistance of the
external edge. From the geometric relationships h = 0.787 m; w = 1.161/m; a = 70.9°. In the same way as for slab
P2, M = 144 kN×m is calculated, as well as the values of W and U 
W = M = 144 × 1.16 = 167 kN; U = 34.5 kN×m.
d) The value of W for the additional slab is equal to zero, the work of external forces is determined by
U = 0.5 qLl = 0.5 × 6.3 × 6 × 0.6 = 11.3 kN.
d) Summing up over all the floor slabs of the cell, we get
W = W + W = 16.4 + 167 = 183.4 kN,
W = W + W = 7.2 + 41.7 = 48.9 kN,
U = U + U + U + U = 42.5 + 26.7 + 34.5 + 11.3 = 115 kN.
In accordance with the instructions of paragraph 15, using formula (27), U = ‑ R ‑ W = ‑83.3 ‑
183.4 = ‑ 266.7 kN is determined.
3.2.3. Work of the transverse internal wall. Limit moments in the lintel - "flag" (see paragraph 3.1.4 of the Manual)
М¢ = 27 kN×m; М¢¢ = 37.2 kN×m. In the absence of the lower lintel M¢ = M¢¢ = 0, and then formula
(5) takes the form W = ( M¢ + M¢¢ )/ b = (27 + 29.7)/1.35 = 42 kN.
12 1 22 2
I 
p2 w
I 
p2
13
23
I 
p3,bor
I 
p3
I 
p3,bor w
I 
p3
p4
I 
p 4
I 
p,bor
I 
p1,bor
I 
p3,bor
I
p
I 
p1
I 
p2
I 
p
I 
p1
I 
p2
I 
p3
I 
p4
I 
w,ex
I 
w,ex
I 
p,bor
sup sup inf inf
I 
w,inf sup sup
The weight of the panel G = 55.5 kN.
The load transferred from the loggia C = 14 + 0.6 × 1.2 × 3 × 1/2 = 15.1 kN, where the weight of the loggia wall
is 14 kN.
The work of external forces on a single displacement is calculated using formula (7) U = 70.6 kN.
3.2.4. Checking the general condition for the impossibility of forming a mechanism of the first type. The check is
carried out using formula (4), which in case of a negative value of U we write as W + W ‑ U ³ U 
 + U .
Substituting the values obtained above into this formula, we obtain 42 + 48.9 + 266.7 > 70.6 + 115; 357.6 >
185.6, the condition is met, the collapse of structures according to the considered scheme (mechanism of type I)
is impossible.
3.3. Assessment of the possibility of occurrence of themechanism of progressive collapse of the second
type (Fig. 16). The calculation is carried out in accordance with the requirements of paragraph 9 and taking into
account paragraphs 13 - 15, as well as the design features of the cell under consideration.
Fig. 16. 3rd scheme of fracture of elements of fragment
3.3.1.Analysis of resistance of external walls. The fracture patterns of external expanded clay concrete walls are
the same as for the first collapse mechanism, with the only difference being that the displacement of the left panel
НС1 is w¢¢ = w¢¢L¢ / L¢¢ = l × 5.4/6.6 = 0.82.
Then, using the result obtained in section 3.2.1 a , we determine: W¢ = 37.4 × 0.82 = 30.7 kN.
For the right external panel w = 1, which means, as in section 3.2.1 b, W¢ = 113.8 kN; W¢ = 30.7 + 113.8
= 144.5 kN.
When calculating the work of the weight forces, taking into account that the displacement of НС1 w = 0.82, we
obtain U = 0.5(26.6 × 0.82 + 0.5 × 68.7) = 28.1 kN; R = 144.5 - 28.1 = 116.4 kN > 0.
3.3.2. Collapse resistance of floor slabs.
a) The resistance of the outer edge of the left slab P1 is determined by formula (29), which for М¢ = М¢ = 0
has the form
W = s/d ( M /L + M /l ) w¢ = 1.32/0.89 (49.4/5.4 + 9.7/3) 0.82 = 15.1 kN.
The work of internal and external forces applied to slab P1 is taken from the calculation described in section
2.3.2, with w = 0.82, W = 0; U = 0.82 × 12.5 = 10.2 kN.
b) Slab P2 fails with the formation of one plastic hinge with tension of the upper fibers (see Fig. 16). Since there is
no upper reinforcement in the slab, W = 0. U = l/6 × 6.3 × 3 × 6 × 0.455 = 8.6 kN.
c) Failure of slab P3 is shown in Fig. 16, d , the plastic hinge with tension of the lower fibers determines the
resistance of the outer edge of the floor slab inserted into the outer wall. From the geometric relationships, the
values w = 1.42 1/m and a = 37.5° are determined .
The ultimate bending moment supported by the section of the slab along the plastic hinge line is calculated using
w,in
l
I 
w,in
w,ex
I 
w,in
I 
p w,ex
I
w,in
I 
p
w,ex
w,ex w,ex
1
w,ex w,ex
11 21
II 
p,bor 11 21
II 
p1
II 
p2
II 
p2
II 
p2
the formula given in paragraph 3.2.2 b and is equal to M = 16.4 kN. Then the work of external and internal forces
applied to slab P3 will be: W = 42.3 kN; W = 0; U = 10 kN.
d) The work of external forces on the movements of the additional slab U = 0.5(0.455 +0.545)0.5 × 6.0 × 6.3
× 0.6 = 5.7 kN.
d) The sum of the work of internal forces in the floor slabs of the cell will be W = 15.1 + 42.3 = 57.4 kN; W 
 = 0; U = 10.2 + 8.6 + 10 + 5.7 = 34.5 kN.
Using formula (27), we determine U = ‑ R ‑ W = ‑116.4 ‑ 57.4 = ‑173.8 kN.
3.3.3. Work of connections. There are no shear connections of the third type between the floor and the underlying
internal wall in the structure, therefore formula (13) takes the form W = S y /L, where S = 53 kN; y = 2.6
m; L = 6.6 m; W = 20.9 kN.
3.3.4. Resistance of the internal wall. The work of external forces applied to the internal transverse wall is
calculated using formula (14) with G = 55.5 kN; G = 15.1 kN, L = 6.6 m; x = [15.14 × 2.6(1.35 + 0.5 × 5.14) +
0.5 × 0.525 × 1.35 ]/(5.14 × 2.6 + 1.35 × 0.525) = 3.75 m.
U = G x / L + G = 55.5 (3.75/6.6) + 15.l = 46.6 kN.
3.3.6. Checking the general condition for the impossibility of forming a mechanism of the second type. The check
is carried out using formula (12). which in this case is more convenient to write as W ‑ U ³ U + U ;
26.9 + 173.8 > 46.6 + 34.5; 200.7 kN > 81.1 kN, the condition is met. Collapse of structures according to the
considered scheme (mechanism of the second type) is impossible.
3.4. Assessment of the possibility of occurrence of the mechanism of progressive collapse of the third type. As
indicated in section 2.4, the resistance to progressive collapse in this case should be checked using the formula
W ³ U .
Since the floor on the right is cut into three slabs, the failure patterns of these slabs differ from the patterns
described in Appendix 2; therefore, condition (16) is checked separately for each slab.
a) The collapse of slab P1 (see Fig. 15, a ) was considered in section 2.4; the calculation showed the need to
install a tie with a diameter of 10 mm attaching the corner of the slab to the wall located above.
b) The collapse pattern of slab P2 is shown in Fig. 15, c . The occurrence of a plastic hinge in the slab with
tension of the upper reinforcement does not cause the work of internal forces due to the absence of the upper
reinforcement, i.e. W = 0. The work of external forces on the displacements of the slab U = 1/6 qLl =
18.9 kN.
The condition of stability against collapse W ³ U is not satisfied, since 0 U , where W = 18.4 kN.
Thus, 18.4 kN » 18.9 kN, the tie is sufficient.
c) The need to install ties of the fifth type 2 of a rod with a diameter of 10 mm made of steel of class A-I in slab P3
is determined in a similar way; the fracture pattern of which is shown in Fig. 15, d. Having determined the values 
of the work of internal and external forces on the displacements of slab P3: W = 0; U = 31.2 kN, W 
= 2 × 18.4 = 36.8 kN, we check the condition of impossibility of collapse: W = 3668 kN > 31.2 kN, the
condition is satisfied.
3.5. Checking the general condition of impossibility of forming a mechanism of the fourth type.
3.5.1. Analysis of resistance of external walls. According to the instructions of paragraph 15 of this appendix, it is
necessary to check the condition S w > R . Since there are no tensile connections of the seventh type
between the external walls and the floor slabs in the structure, S w= 0, and the above-mentioned condition is not
met; in accordance with paragraph 15 in formula (19), it is necessary to take U = 0, w = 0.
3.5.2. Work of floor slabs. Since the left floor is cut into separate slabs, the values of W and U are
calculated in accordance with the fracture patterns of the elements shown in Fig. 17.
Fig. 17. 4th fracture pattern of the fragment elements
All floor slabs fail with the formation of upper plastic hinges, therefore W = 0.
To calculate the work of external forces applied to the floor slabs, their displacements are determined from
obvious geometric relationships: w = 1; w = (0.25 × 3)/1.35 = 0.56; w = w = 0.25. Next, determine the
work of external forces on the displacements of each floor slab: U = 6.3 × 5.4 × 2.21 × l/6 = 12.5 kN; U = 6.3
× 3 × 6 × 0.56/6 = 10.6 kN; U = 6.3(3 × 6 × 0.25 + l.95 × 3 × 2 × 0.25)/6 = 7.8 kN; U = 0.5 × 6.3 × 0.6 × 6 ×
II 
p 3 ,bor
II 
p3
II 
p 3
II 
p 4
II 
p,bor
II
p
II 
p
II 
w,ex w,ex
II 
p,bor
II 
t 2 2 2 2
II 
t
w,in t
 2
II 
w,in w,in t
II 
t w,ex
II 
w,in
II
 p
III 
p
III 
p
III 
p 2
III 
p 2
III 
p
III 
p
5 5
III 
t 2
III 
p 2
III 
t 2
III 
p3
III 
p 3
III 
t 3
III 
t 3
t w,ex
t
w,ex w,ex
IV 
p
IV 
p
IV 
p
p1 p2 p3 w,in
p1 p2
p3 p4
0.5(0.25 + 0.56) = 3.2 kN; U = 12.5 + 10.6 + 7.8 + 3.2 = 34.1 kN.
3.5.3. Work of connections.
a) The resistance of the fifth type of ties (see section 3.4) S = 18.4 kN.
There are no ties of the sixth type in the structure.
The work of internal forces during the destruction of the ties is determined by formula (20)
b) The shear ties of the fourth type in the structure are represented by three rods with a diameter of 12 mm made
of grade A-I steel, one rod between the internal wall and each external panel, and also between the loggia wall
and the internal wall, the bearing capacity of each rod in accordance with section 3.1.5 is equal to 18.6 kN, then S
 = 18.6 × 3 = 55.8 kN.
Resistance of the internal wall
From section 3.2.3 it is adopted W = 42 kN; U = 70.6 kN.
3.5.4. Checking thegeneral condition of impossibility of forming a mechanism of the fourth type. The check is
carried out according to formula (19), which, in the case of equality to zero of the quantities W , U and w
 , takes the form (1 ‑ c / L ) W + W ³ (1 ‑ s / L ) U + U ‑ S w ,
where L = 5.4 m; L — c = 1.35; 1 ‑ s / L = 0.25.
Substituting the values calculated above, we obtain
(1 ‑ s / L ) W + W = 0.25 × 42 + 19.5 = 30 kN;
(1 ‑ s / L ) U + U ‑ S w = 0.25 × 70.6 + 34.1 ‑ 55.8 × 0.25 = 37.7 kN >30 kN.
If the non-collapse condition is not met, it is recommended to install type 6 ties, the bearing capacity of which,
taking into account formula (20), is determined by
S = L/(L - c ) × (37.7 - 30) = 30.8 kN. The value of S 
can be ensured, for example, by installing two rods with a diameter of 10 mm made of grade A-I steel.
IV 
p
5
4
I 
w,in
I 
w,in
IV 
p w,ex
w,ex
I
w,in
IV 
t
IV 
p
IV 
p 4 w,in
I 
w,in
IV 
t
I 
w,in
IV 
p 4 w,in
6 6above the supports should be cut off at a distance of no
closer than 0.25 l from the support face, where l is the slab span. The span reinforcement in the support sections
of the slab is inserted beyond the support face by at least 20 mm; the joint of the reinforcing meshes is made with
an overlap in compliance with the requirements of SNiP 2.03.01-84.
In slab sections where cracks do not form during the operational stage, it is permissible to increase the distance
between the working reinforcement bars to 400 mm in compliance with the requirements of SNiP 2.03.01-84.
In slabs clamped on three sides, the free edge is additionally reinforced with a three-dimensional cage of four
bars with a diameter of 10 mm made of grade A-III steel to withstand shrinkage and temperature effects.
The reinforcement scheme for a monolithic floor slab clamped on three sides with a fourth free bar is shown in
Fig. 42.
Fig. 42. Reinforcement schemes for a monolithic slab
a — clamped along the contour; b — clamped on three sides and a fourth free
SV — upper reinforcement mesh, SN — lower reinforcement mesh, KP — spatial cage
It is recommended to reinforce precast-monolithic floor slabs in the same way as monolithic slabs; it is
recommended to place the overbearing reinforcement in the monolithic layer, and the span reinforcement in the
shell.
The shell size in the plan is recommended to be determined based on the condition: Precast-monolithic floor
slabs are recommended to be reinforced similarly to monolithic slabs; the supporting reinforcement is
recommended to be placed in the monolithic layer, and the span reinforcement is recommended to be placed in
the shell. The shell size in the plan is recommended to be determined based on the condition of ensuring the
strength and crack resistance of the concrete during its manufacture and installation. The shell joint in the cell
being covered should not be located in the zone of maximum moments. In the joint zone, reinforcement with an
area equivalent to the bending moment in the design section of the slab is placed along the shells with an overlap
of at least l , where l is the design anchorage length of the reinforcement. The shell is extended beyond the
wall edge by at least 20 mm.
The combined action of the precast and monolithic floor layers should be ensured by the adhesion of the
concrete and the assembly reinforcement elements installed in the precast shell slab.
The reinforcement diagram of the precast-monolithic floor slab is shown in Fig. 43.
Fig. 43. Precast-monolithic slab
a ¾ reinforcement diagram of the precast-monolithic slab, clamped along the contour; b — design solution of the
precast shell slab without external reinforcement; c ¾ the same, with external reinforcement
SV — upper reinforcement mesh, PS — shell slab
1 — assembly loop, 2 — loop releases
Calculation of reinforced concrete floor slabs
6.22. When calculating reinforced concrete floor slabs for the limit states of the first group (by strength) and the
sp sp
second group (by deformations, formation and opening of cracks), it is recommended to distinguish between
slabs working in bending out of the plane in one and two directions.
Slabs supported along the contour and having a ratio of the dimensions of the long side to the short side of 3:1 or
less, as well as slabs supported on three sides and having a ratio of the dimensions along parallel supports to the
dimension along the free edge of 1.5:1 or less, are recommended to be calculated as working in out-of-plane
bending in two directions. The calculation of such slabs may be performed using the methods described in this
Manual. If necessary, a more accurate calculation of such slabs can be performed using special computer
programs that take into account the non-linear behavior of reinforced concrete with cracks.
Other slabs are recommended to be calculated as working in bending in one direction in accordance with SNiP
2.03.01-84 and relevant manuals.
6.23. For slabs working in out-of-plane bending in two directions, the design lengths l and l are distinguished .
For slabs supported along the contour, it is assumed that the span l does not exceed the span l . For slabs
supported on three sides, the span corresponds to the distance between parallel supports (the dimension along
the free edge of the slab).
For simply supported slabs, the design span is taken equal to the distance between the centers of the bearing
pads of the floor slabs. For slabs clamped on supports, the design span is taken equal to the clear span (to the
edge of the supports).
6.24. For floor slabs working in bending in two directions, the reinforcement ratios (the ratio of the cross-sectional
area of the reinforcement to the effective cross-sectional area of the slab perpendicular to the reinforcement) m 
è m along the spans, respectively l è l are recommended to be assigned so that the following conditions are
met:
m ³ m ;. (149)
0.5 ( m + m ³ m , (150)
where m is the minimum value of the reinforcement coefficient, taken according to CHiP 2.03.01-84 as equal
to 0.05%.
For lightly reinforced reinforced concrete elements, the bearing capacity of which is exhausted simultaneously
with the formation of cracks in the concrete of the tensile zone, the cross-sectional area of the longitudinal tensile
reinforcement should be increased compared to that required from the strength calculation by at least 15%
(according to SNiP 20301-84).
6.25. When calculating floor slabs, the loads from the weight of non-load-bearing external walls and partitions
resting on them should be taken into account as follows:
for rigid non-load-bearing walls and partitions in the form of precast concrete and reinforced concrete panels, the
load from their weight is applied to the slab in the form of concentrated forces, which are considered to be
located:
for panels without openings, as well as piers of panels with openings wider than half the floor height - at a
distance of 1/12 of the length of the panel and pier, respectively, from their edges; for the outer piers of panels
with openings no wider than half the floor height - at a distance of 1/3 from the outer edge of the pier, and for
middle piers - in the middle of their length;
for non-rigid non-load-bearing walls and partitions made of masonry, small blocks, sheet materials, 60% of the
load from their weight is considered to be distributed along the length of the piers, and the rest in the form of
concentrated forces, the position of which is assigned similarly to the load from rigid walls and partitions.
If during the operation of the building it is possible to change the position of the partitions, then the load from the
weight is recommended to be specified in the form of a distributed load equivalent to the most unfavorable
arrangement of partitions in the structural cell, but not less than 0.5 kN / m (50 kgf / m ).
Calculation of reinforced concrete floor slabs for limit states of the first group
6.26. Precast slabs that do not have special ties to ensure continuity at the supports, are calculated for strength
assuming their free (without restraint) support on the walls. For a slab working in out-of-plane bending in two
directions, at a platform junction with the walls, it is allowed to assume that the slab corners are fixed from uplift.
Monolithic slabs, as well as precast slabs with special ties to ensure continuity at the supports, are recommended
to be calculated taking into account their restraint by the walls at the supports. In this case, for precast and
precast-monolithic slabs, it is necessary to consider two stages of their work: before and after the installation of
ties ensuring restraint of the slab.
The strength calculation of slabs working in out-of-plane bending in two directions is recommended to be
performed using the kinematic method of limit equilibrium.
When calculating the strength of slabs, the following cases are distinguished:
the slab reinforcement is specified; It is required to determinethe ultimate strength value of a uniformly distributed
load on a slab ;
the load on the slab is specified; it is required to determine the required reinforcement.
6.27 . For a slab with specified reinforcement, the strength calculation is performed in the following sequence:
the design sections are identified; for all slabs, the sections perpendicular to the spans l2 and passing through the
center of the slab are conventionally considered as design sections; for slabs with clamped supports, the sections
along these supports are also considered, in addition, the sections where the slab reinforcement changes must
be considered. For hollow-core slabs, the sections along the voids adjacent to the supports are additionally
considered; 
1 2
1 2
1
2 1 2,
1 min
1 2 min
min
2 2
the
values of the bending moments supported by the slab along the design sections are determined; with one-sided
reinforcement, the bending moment for the i -th section of the slab is determined by the formula
(151)
where R , A are, respectively, the design resistance and the cross-sectional area of the longitudinal
reinforcement in the i -th section of the slab; h is the working height of the section; R is the calculated
compressive strength of the concrete slab (prism strength); d is the length of the slab along section i ;
the fracture pattern of the slab in the ultimate state is outlined and the angles of inclination of the fracture lines
relative to the side of the slab along the span l ; for simply supported slabs and those clamped along
the contour, the fracture patterns are recommended to be adopted according to Fig. 44 and 45, respectively,
while the angle of inclination of the fracture lines to the sides along the span may be taken as 45°. For slabs
simply supported along three sides, it is recommended to consider two fracture patterns (Fig. 44, b, c), while for
slabs with the aspect ratio l / l ³ l, it is allowed to assume that the angle j = 45°;
Fig. 44. Design patterns of fracture of a simply supported slab
a — supported along the contour; b, c — supported along three sides
si si
oi b
i
2 are determined.
2 2
Fig. 45. Design patterns of fracture of a slab clamped along the contour ( a ) and three sides ( b )
1 , 2 , 3 — design sections when determining the crack formation load ,
the limit value of the uniformly distributed load on the slabs is determined ;
the load is compared with the design load on the slab q; the strength of the slab is considered to be ensured if
³ 1.
When loading a slab in different areas with unequal distributed loads, as well as point and strip concentrated
loads, it is permissible to replace the specified loads with a reduced uniformly distributed load, determined from
the condition of equality of the work of the actual and reduced loads on displacements that correspond to the
specified fracture pattern of the slab.
For a simply supported slab along its contour, the ultimate load is calculated using the formulas:
when reinforcing with meshes, all the rods of which along spans l and l are brought to the supports or break off
in the span according to the moment diagram according to clause 6.11:
(152)
where M , M are the values of the bending moments supported by the slab during bending according to beam
schemes along spans l , l , respectively ; g is the working conditions coefficient, determined according to the
graph in Fig. 46;
l = l /l . (153)
Fig. 46. Graph for determining the coefficient g , taking into account the spatial work of a slab supported along
the contour
a - with uniform reinforcement; b - with reinforcement concentration in the middle part of the slab
When reinforcing with meshes in which the rods along the span are alternately not brought to the supports at a
distance of a > 0.14 l , and along the span l all are brought to the supports
, (154)
where x = a / l . (155)
1 2
1 2
1 2 p
2 1
p
1 2
1
For a slab simply supported on three sides, reinforced in two directions, the ultimate load is taken to be equal to
the smaller of the values calculated for the two fracture patterns according to Fig. 44, b , c.
When the slab fractures according to the pattern in Fig. 44, b
 (156)
where (157)
y is the coefficient of orthotropy of the reinforcement
(158)
When the slab fractures according to the pattern in Fig. 44, c
 (159)
where (160)
In formulas (156) - (159), the value of l is calculated according to formula (153), and the span l is considered to
be the span along the free edge of the slab.
For a slab with clamped supports, the ultimate load is calculated using the formulas:
for clamping along the contour (Fig. 45, a )
(161)
for clamping along three sides and one free edge along span l (Fig. 45, b )
(162)
where M , M are the bending moments perceived in the slab span during bending along spans l and l ,
respectively ; M , M¢ are the bending moments perceived at the supports during bending along span l ; M ,
M¢ ‑ the same, along span l .
6.28. Slabs prestressed in one direction are calculated for strength taking into account the following features:
when calculating strength, it is assumed that the value g = 1;
when calculating the strength of slabs supported on three sides and having reinforcement only along the span l 
, in the form of prestressed reinforcement, in formulas (156) and (159) it is assumed that the value M = 0, and
the orthotropy coefficient y is calculated based on the bending moments M and M , at which cracks form in
the slab during bending, respectively, along the spans l and l ,In this case, the effect of prestressing is taken
into account.
Hollow-core slabs must also be checked by calculation in accordance with the instructions of Sec. 6.33.
6.29. For reinforced concrete floor slabs, in addition to the calculation in accordance with the instructions of Sec.
6.27, it is necessary to check the strength of inclined sections under the action of the shear force. The calculation
is performed in accordance with the instructions of the design codes for reinforced concrete structures for inclined
sections passing through supports.
The value of the shear force in the support section for a slab working in bending in two directions is
recommended to be taken as the greater of the two values calculated based on the elastic stage of the slab's
operation and in the ultimate state (for the slab fracture pattern adopted in the calculation).
For the preliminary calculation, it is permissible to determine the shear force based on the condition of the slab
being supported on two sides. If the requirements for the calculation of the shear force are met without additional
reinforcement or an increase in the class of concrete for the slab, then no further clarification of the value of the
shear forces is required.
6.30. In case the load on slabs is specified and it is required to determine its reinforcement, it is recommended to
perform the calculation in the following sequence:
a) the type and scheme of slab reinforcement are specified and the class of reinforcement is preliminarily
assigned;
b) the optimal ratio of the values of bending moments in the design sections is determined and the required
cross-sectional area of the reinforcement is determined;
c) when reinforcing the slab with welded meshes, using the data from Table 10, the diameters of the reinforcing
bars and their pitches in the mesh are assigned; if necessary, the calculation results are adjusted taking into
account the adopted classes and diameters of reinforcement.
6.31. For a simply supported slab along the contour, reinforced with a mesh, all the rods of which are brought to
the support or half of the rods break off at a distance of à £ 0.14 l ‑ 20 d , the bending moments M and M ,
acting respectively along the spans l and l , are recommended to be determined by the formulas:
M = M g (1 ‑ 2/3 n / l ); (163)
M = M g n /3 l, (164)
where M is the bending moment in the middle section of the slab, corresponding to thebeam scheme of the
1
1
1 2 1 2
I I 1 II
II 2
p
1
2
b1 b2
1 2
1 1 2
1 2
1 o p op t
2 o p
2 
op t
o
slab's work along the span
M = q l l /8; (165)
g — the working conditions coefficient determined according to clause 6.27; n — the coefficient equal to the
cotangent of the angle of inclination of the fracture line to the side of the slab along the span l ; for the slab
reinforcement optimal in terms of strength conditions, the coefficient n is recommended to be determined by
the formula
n = g h /( lh ); (166)
g — the coefficient depending on the type of reinforcement along the spans l and l ; for reinforcement with
the same reinforcement in both directions, the coefficient g = l; for reinforcing the slab along the span l with
class A-III rod reinforcement and along the span l with class Вр-1 wire reinforcement, the coefficient g = 0.9; in
other cases, the coefficient g is determined by the formula
g = R C /( R C ); (167)
R , C — design resistance and cost of 1 m of reinforcing bars located along span l ; R , C — the
same, along span l , h , h — working height of slab section during bending respectively along spans l and
l .
Cross-sectional areas of reinforcement A , A , located respectively along spans l and l , are determined by
formulas:
A = R l x / R ; (168)
A = R l x / R , (169)
where (170)
(171)
If, according to the conditions of calculation for installation loads or for design reasons, reinforcement along span
l is given, then the bending moment M , by which the area of reinforcement along the span l is determined , is
calculated by the formula
M = [ М ( l ‑ n /3) ‑ М l / n ] g / l , (172)
where (173)
6.32. For a slab simply supported on three sides, reinforced with a mesh, all the rods of which are brought to the
support, the bending moments M and M , by which the area of reinforcement along the spans l and l ,
respectively, is determined, are calculated by the formulas:
if l > 0.25 g h / h , then
M = M (l ‑ l/3 n / l ); (174)
M = M n /(3 l ), (175)
where
n = g h /(2 lh ); (176)
if l £ 0.25 g h / h 
M = M / (4 n l ); (177)
M = M ( n ‑ 4/3 l ), (178)
where
(179)
Features of strength calculation of hollow-core slabs
6.33. Hollow-core slabs with cylindrical voids, working in out-of-plane bending in two directions, as well as slabs
supported on two sides, in which the voids are located parallel to the supports, shall be calculated taking into
account the features set out in this paragraph.
The calculation of the slab strength for normal sections perpendicular to the direction of the voids is performed for
the reduced I-section, for which the widths of the compressed and stretched flanges are b¢ and b are
equal to the width of the slab b along the section under consideration, and the reduced heights (thicknesses) of
the flanges h¢ , h è the wall thickness b are determined by the formulas,
h¢ = h¢ + 0.0569 d ; (180)
h = h + 0.0569 d ; (181)
h = b — 0.8862 dn , (182)
where h¢ , h — the minimum thicknesses of the compressed and stretched flanges, respectively; d — the
diameter of the voids in the slab; n — the number of voids intersecting the calculated section of the slab.
The calculation of the slab strength for normal sections parallel to the direction of the voids under the action of a
bending moment is performed as for a rectangular section, while the calculated height of the compressed zone
must not exceed the minimum thickness of the compressed flange (in the section along the axis of the void).
Bending moments acting in the calculated sections may be determined as for slabs of solid section.
In a hollow-core slab, the shear strength of the ribs must be checked along the horizontal sections and the shear
strength of the flanges along the vertical sections.
For a slab supported on two sides with voids located parallel to the supports, the shear strength is checked using
the formulas:
for the support rib
o
2 
1 2
p op t
2
op t
op t s 02 01
s 1 2
s 1
2 s
s
s s2 s1 s1 s2
s1 s1 1 s2 s2
2 01 02 1
2
s1 s2 1 2
s1 b 2 1 s1
s2 b 1 2 s2
2 1 1
1 o
2
2 р
1 2 1 2
2
s 02 01
1 o ор t
2 o
2 
op t
op t s 02 01
2
s 02 01
1 o t op t
2 o op t
f ,red f,red
f,red f,red w ,red
f,red f
f,red f
w ,red
f f
(183)
for the intermediate rib closest to the support
(184)
for the flanges (in the section along the void closest to the support)
(185)
where q is the design load on the slab; l is the design span of the slab; b is the minimum thickness of the
support rib; b — the same, of the intermediate rib; R — the calculated tensile strength of concrete; j — the
coefficient adopted according to SNiP 2.03.01-84 as equal to the following for concrete: heavy and cellular — 0.6;
fine-grained — 0.5; lightweight with an average density grade of D1900 and higher — 0.5; D1800 and lower —
0.4.
For a slab supported on four sides with voids located along the long side of the slab, as well as for a slab
supported on three sides with voids located perpendicular to the free edge, the calculation of the ribs and slabs
for shear strength is recommended to be determined by formulas (183) and (185) as for a slab supported on two
sides parallel to the voids.
For support on three sides of a slab with voids located parallel to the free side of the slab, with the ratio of its
sides l / l > 2, the shear strength of the ribs is checked by the formulas:
for the outer support rib
(186)
for the intermediate rib closest to the support rib
(187)
where b is the minimum thickness of the support rib; b is the same, for the intermediate rib; s is the
horizontal distance from the support axis to the center of the first void in the slab. It is allowed to approximately
assume that
s = ( b + d)/2; (188)
s is the step of voids;
(189)
I is the moment of inertia during bending for the section of the slab perpendicular to the voids; with a symmetrical
arrangement of voids along the height of the slab
I = l h /12 ‑ npd /64; (190)
I is the moment of inertia in free torsion for the section of the slab perpendicular to the voids; the value of I 
may be determined as for a closed box section using formula
91)
h is the number of voids, h is the thickness of the flange.
Features of strength calculation of prestressed slabs supported on three sides
6.34. When calculating the strength of slabs supported on three sides with combined reinforcement in the form of
prestressed reinforcement with a cross-sectional area A and non-stressed reinforcement with a cross-sectional
area A , the reduced resistances ( R ), the cost of reinforcement ( C ) and the calculated height of the
section with combined reinforcement ( h ) are introduced, which are calculated using the formulas:
R = ( R A + R А )/ А ; (192)
C = ( C A + C А )/ А ; (193)
h = ( h A + h A R / R )/ A , (194)
where A = A + A ; (195)
R , C , are respectively the calculated tensile strength and the cost of prestressed reinforcement; R , C —
the same, for non-stressed reinforcement; h — the calculated section height for prestressed reinforcement; h
 — the same, for non-stressed reinforcement.
6.35. When calculating the strength of slabs supported on three sides and reinforced only with prestressed
reinforcement parallel to the free edge of the slab, it is necessary to additionally check the crack resistance of the
slab for sections along the voids.
When checking the crack resistance, the calculated tensile resistance of concrete R , which is determined as
for a concrete element, is taken into account.
The strength of a hollow-core slab across its cross-section along the average void across its width under the
combined action of general and local bending is checked using formula
w o
w bt b3
2 1
w o w o
o w o
2
3 4
tor tor
f
sp
s s,red s,red
o , red
s,red sр sp s s s, red
s,red sр sð s s s, red
o , red o р sp os s s sp s, red
s, red sp s
sp sp s s
o p
os
bt
(196)
where 0.85 is a coefficient that approximately takesinto account the possible decrease in the tensile strength of
concrete when establishing the class of concrete for compressive strength; h is the reduced shelf height
calculated using formula (181).
If condition (196) is met, the slab may be reinforced in one direction. The calculation of such a slab is performed
using the following assumptions:
the direction of cracks during slab failure coincides with the direction of the initial cracks and depends on the ratio
of the sides of the slab l = l / l and the moments of crack formation of the concrete section of the slab M 
and M respectively, during bending along spans l and l ;
the moment of crack formation M is determined taking into account the influence of prestressing of
reinforcement according to the formula
M = R W + P ( e + r ), (197)
where R — the calculated resistance of the concrete slab to axial tension for the limit states of the second
group; W — plastic moment of resistance of the section of the slab perpendicular to the free edge (determined
according to the instructions of the design standards for reinforced concrete structures and manuals thereto); P
— preliminary compression force minus prestress losses; e — eccentricity of force P relative to the center of
gravity of the reduced section; r — distance from the center of gravity of the reduced section to the core point
most distant from the tensile zone, the cracking of which is checked;
r = jW / A , (199)
j = 1.6 ‑ s /R , (199)
but not less than 0.7 and not more than 1; s — maximum stress in compressed concrete from the external load
and the prestress force, calculated as for an elastic body along the reduced section;
cracking moment M is determined for the section along the void; with symmetrical arrangement of voids along
the height
M = R h ( h ‑ h ) l . (200)
The strength of a slab with a given reinforcement of prestressed reinforcement located parallel to the free edge
must satisfy the conditions:
(201)
(202)
where M is the bending moment supported by the slab when supported on two sides; the coefficients n and n 
are calculated accordingly using formulas (157) and (160).
Features of strength calculation of monolithic slabs
6.36. To determine the reinforcement of monolithic slabs required by the strength conditions, it is recommended
to pre-set the values of the reinforcement orthotropy coefficients y , y , y , which characterize the ratio of
bending moments in the span and support sections of the slab per unit length of the section (Fig. 47).
red
2 1 crc1
crc2, 1 2
crc1
crc1 bt,ser pl,1 op
bt,ser
pl,1
op
re d red
b b,ser
b
crc2
crc2 bt,ser f f 1
1 1 2
I II
Fig. 47. Schemes of action of bending moments and distribution of working reinforcement in slabs
a — clamped along the contour; 6 — clamped on three sides and the fourth free
Depending on the slab support scheme and the ratio of its dimensions in the plan, it is recommended to assign
orthotropy coefficients according to Table 11.
Table 11
Method of clamping the plate
Along the contour 1 1 - 0.9 
 0.8 - 0.6 
 0.7 - 0.5 1 - 2 1 - 2
 0.5 - 0.3 
 0.4 - 0.2 
 0.2 - 0.15 
On three sides, one edge free0.7 - 1.50.3 - 0.1 1 - 2 1 - 2
For a given distributed load q on a slab, the linear bending moment m , according to which the span
reinforcement is selected, is located along the span l , and is determined by the formulas:
for a slab clamped along the contour,
(203)
for a slab clamped along three sides and one free,
(204)
where y , y¢ are the orthotropy coefficients for parallel support sections along the side of the slab of length l ;
y , y¢ ‑ the same, of length l , (for the free edge, the value y¢ ).
The linear bending moments in other sections of the slab are calculated by the formulas:
m = m y; (205)
m = m y ; (206)
m = m y , (207)
where m is the linear bending moment in the slab span causing bending along span l ; m is the linear
bending moment at the slab support causing bending along span l ; m is the same, along span l .
6.37. For one-sided clamping of the slab by the wall (see Fig. 42), the bending moment in the support section
should be limited by the bearing capacity of the anchor
m £ 0.9 h n , (208)
where n is the linear tensile force in the anchors determined by the concrete puncture calculation,
1
1
I I 2
II II I II
2 1
I I I
II 2 II
2 2 I
1 II 2
I ( II) o an
an
n = 0.5 A R ; (209)
A is the area of the projection of the puncture surface onto the plane normal to the anchor.
When anchoring the mesh with a transverse rod, the area of the puncturing surface is determined by the formula
A = 2 l b , (210)
where l is the length of the embedment of the upper mesh beyond the edge of the support, taken to be no less
than 10 d ( d— the diameter of the longitudinal rod of the upper mesh).
The transverse anchor rod is recommended to be made of grade A-III steel and assigned according to Table 12
depending on the force n per longitudinal rod.
Table 12
n , kN 4.5813.519.5263143.5
Diameter of the cross rod d , mm6 810 12 141018
6.38. In precast-monolithic floors, an additional check is made of the strength of the joint between the monolithic
and precast parts of the slab for shear based on the condition
t £ R , (211)
where t is the shear stress in the joint, determined by the formula
t = Q /( bz ), (212)
Q is the transverse force from external loads in the normal section of the precast-monolithic floor; b is the design
width of the section, z is the arm of the internal pair of forces; R is the ultimate shear resistance, depending on
the nature of the contact surface of the joint, taken equal to 0.2 MPa for a smooth surface of the shell and 0.3
MPa for mechanical creation of nicks and dents.
Calculation of reinforced concrete floor slabs for limit states of the second group
6.39. Precast slabs that do not have special connections to ensure the continuity of the floors on supports are
calculated for the ultimate states of the second group as simply supported. When floors are clamped by walls,
provided that no cracks form at the support, and in the presence of special ties ensuring the continuity of the
floors at the supports, it is permissible to consider two stages of their performance when calculating slabs for
group II limit states: before and after clamping.
The group II limit state calculation before slab clamping is performed assuming the slab is freely supported. For
this stage, the possibility of cracks forming in the slab span is checked, and their short-term opening under loads
applied before the slab clamping is determined. The calculation takes into account the loads from the slab's own
weight and the precast elements resting on it (floor base slabs, panel partitions, sanitary cabins, etc.), installed
before the installation of the slabs of the next floor, as well as the temporary load from the weight of installation
equipment (struts, jigs, etc.), mortar containers, or materials stored on the floor. It is recommended that the
temporary installation load be no less than 0.5 kN/m2 50 kgf/m2 .
For the second stage of slab operation, short-term deflections are determined from the load applied after the slab
is clamped (partitions made of individual materials, floors, temporary load), as well as the incremental deflections
from all long-term loads caused by the development of creep deformations in the slab's concrete. The possibility
of cracks forming in the span and at the supports under the combined loads is also checked. If cracks form at the
supports in the absence of special ties designed to withstand bending moments in the support sections, the slab
is calculated as simply supported. If cracks form in the span, their opening under the long-term load is checked.
When calculating precast slabs taking into account clamping at supports, it is recommended to take into account
the ultimate rigidity when rotating the support fixtures.
6.40. For monolithic slabs, all loads may be considered applied after formworkremoval.
Precast shell slabs of precast-monolithic floors may be checked using the second-group limit state calculation for
installation only. To reduce their deflections and prevent cracking until the monolithic concrete has reached the
design strength, it is recommended to use temporary telescopic supports. For installation of precast shell slabs, it
is recommended to use lifting schemes that do not lead to cracking.
After the concrete has reached the design strength, the precast-monolithic floor is calculated in the same way as
a monolithic floor.
6.41. When determining the deflections of floor slabs, the load from the weight of non-load-bearing panel external
walls and partitions is taken in accordance with paragraph 6.25.
Concentrated loads from external walls and partitions may be replaced by a uniformly distributed load equivalent
in magnitude to the bending moment in the floors.
6.42. When calculating floor slabs for limit states of the second group, the following loads are distinguished: q ‑
the standard load, which is used to check the formation of cracks in the slab; q ‑ the standard long-acting load,
which is used to check deflections and crack opening; q ‑ the load applied to the slab before its clamping (when
taking into account two stages of the slab's operation); q ‑ the same, after the slab is clamped.
When determining the load q (150 kgf/m ) for
apartments in residential buildings . When determining the load q , only the long-acting part of the temporary
load is taken into account, equal to 0.3 kN/m (30 kgf/m ).
Loads q , q are determined according to clause 6.39.
All loads are determined with a load safety factor equal to 1.
6.43. Deflections and crack openings of a slab subjected to out-of-plane bending in two directions may be
determined approximately by linear interpolation of deflections corresponding to the load at which cracks form in
the slab q , and the ultimate load q ,determined based on the characteristics of the slab material for the limit
an an bt
an
ap ap
ap
an
an
an
t
t
( )
n
l
1
2
n ,
 the full value of the temporary load is taken into account, which is equal to 1.5 kN/m 2 2
1
2 2
1 2
crc ser
states of the second group. For a slab calculated taking into account two stages of work (before and after
clamping), when determining deflections and crack openings, a distinction should be made between cases where
cracks form before and after the slab is clamped.
Calculation of reinforced concrete slabs for crack formation
6.44. Crack formation is checked for the section along the middle of the span l of the slab, and for slabs
clamped by walls also for the supporting sections.
6.45. For a precast simply supported slab, the load q , under which cracks form in the span, is determined by
the formula
q = M /( a l l ), (213)
where M is the bending moment corresponding to the formation of cracks in the design section of the slab; for
prestressed slabs, the value of M is calculated taking into account the effect of prestressing reinforcement on
the moment of crack formation; a is the coefficient determined for slabs supported on four and three sides (Figs.
48 and 49); for a slab supported on two opposite sides, the coefficient a = 0.125.
For precast slabs calculated taking into account two stages of work (before and after clamping), the loads q 
and q , under which cracks form respectively in the span and at the support, are recommended to be
calculated using the formulas:
(214)
(215)
where q is the load applied to the slab before it is clamped; a , a are the coefficients determined for slabs
supported on four and three sides, according to the graphs in Figs. 48 and 49; for a slab supported on two
opposite sides, a = 0.0417; a = 0.0833; a is the coefficient taking into account the elastic compliance of the
clamping,
(216)
K is the coefficient of support rigidity during rotation, calculated for the platform joint using the formula
(217)
Ei is the flexural rigidity of the floor slab during bending along the span l ; d is the length of the slab along the
support; b , b —depths of the supporting areas of the floor slab for the upper and lower mortar joints,
respectively; l , l — coefficients of compliance under compression of the upper and lower mortar joints,
respectively, determined according to Appendix 2; M — bending moment at which cracks form in the
supporting section of the slab.
If q q 
f = j l b q /( j E h ), (219)
where b is the coefficient calculated from the graphs in Figs. 50 and 51 depending on the slab support scheme;
q is the long-term load used to check the slab deflection; E is the initial modulus of elasticity of the slab
concrete; h is the slab thickness;
crc , i
crc , i
o 
i
2
bt
o 
i
2 1
about 
1
about 
2
about 
3
o
crc n
b2
4 
1 1 l b1 b 3
1
l b
Fig. 50. Coefficients b for slabs simply supported along the contour
Fig. 51. Coefficients b for slabs simply supported on three sides
in the case when cracks form under load ( q 1,
determined accordingto the instructions of clause 6.27; n is the coefficient characterizing the elastic-plastic state
of concrete in the compressed zone, adopted according to SNiP 2.03.01-84. For long-term action of loads for
structures made of heavy and lightweight concrete at ambient air humidity of 40-75% n = 0.15; below 40% n =
i
i
crc l
b2 crc s er b2 crc l crc ser crc
crc crc
b1
b2
b2
b2 ser
s,s er
1 s1 1 o1
1
1
2 
j 2
2 
j
1 2
1 2 j
0.1;
x = 0.1 + 0.5 m R / R , (224)
h is the coefficient taking into account possible deviations in the thickness of the protective layer of
reinforcement; for mesh-reinforced slabs supported along the contour and less than 16 cm thick,
h = h /( h - 0.7), (225)
but not more than 1.2; in other cases, it is adopted according to SNiP 2.03.01-84. In formula (225), the value of h
 is taken in cm. h is a coefficient that takes into account the discrepancy between the greatest deflection of the
slab and the deflection at the intersection point of the fracture lines and is determined by the formulas:
for slabs supported along the contour,
h = 1 + 0.2( l / l ‑ 1); (226)
for slabs supported on three sides
with l ³ 0.5l , h = 1 + 0.2(2 l / l ‑ 1); (227)
for l £ 0.5 l , h = 1 ‑ (1 ‑ 2 l / l ) ; (228)
q is the ultimate load on the slab, calculated in section 6.27 using the design characteristics of the
reinforcement and concrete for the ultimate states of the second group;
in the case when cracks are formed under a load q ³ q ,
f = f ( j q ‑ q + q )/ q + ( f ‑ f )( q ‑ q )/( q ‑ q ), (229)
where f is calculated using formula (222) for n = 0.45.
6.48. The maximum deflections from long-term loads of precast slabs, calculated taking into account two stages
of their operation (before and after clamping), may be determined using the formulas:
in the case where cracks in the span do not form ( q > q ), then
f = j l [ b q ‑ a ( q ‑ q )( b ‑ b )]/( j E h ), (230)
where b , b are coefficients determined from the graphs in Figs. 50 and 51; a is a coefficient taking into
account the compliance of the clamping of the slab and determined using formula (216); q is the load at which
elastic clamping of the slab occurs;
in the case where cracks in the span form before elastic clamping of the slab, q ³ q 
f = j f + ( f ‑ j f )( q ‑ q ‑ D q )/( q ‑ q ), (231)
where f is calculated by formula (221); f is calculated by formula (222);
D q = a ( q ‑ q )(1 ‑ b / b ); (232)
in the case when cracks in the span are formed after elastic clamping of the slab, q q 
s = s + ( R ‑ s )( q ‑ q )/( q ‑ q ); (241)
for q £ qper plate, kN
(kgf)
Loop diameter,
mm
Ultimate static force per plate kN
(kgf)
6 1 (100) 18 25 (2500)
8 3 (300) 20 31 (3100)
10 7 (700) 22 38 (3800)
с rс l с rс n
o 
crc
o 
ser
o 
crc n crc ser crc l n
s
l crc
s s,crc s,ser s,crc l crc ser crc
l crc n
s s,ser s,crc n crc ser crc l n
s,crc
с rc
1 2
1
n l n l
n crc ser crc n crc ser crc
l crc ser crc l crc ser crc
ser
o
o
2
2
2 crc n
o n 2
12 10 (1000) 25 49 (4900)
14 15 (1500) 28 61 (6100)
16 20 (2000) 32 80 (8000)
When using assembly crossbars that ensure the load is applied at an angle to the loop symmetry axis of less
than 15°, as well as when lifting slabs by four loops with a non-balancing crossbar (statically indeterminate
system), when the entire load from the panel weight is considered to be applied only to any two loops located
diagonally, the values of the ultimate static forces given in Table 15 may be increased by 50%.
6.55. When calculating slabs for assembly loads, their own weight, determined taking into account the production
humidity, is assumed to be with a dynamic factor of 1.4. Concentrated forces at the panel suspension points also
increase accordingly. All design properties of concrete are assumed to be reduced taking into account the ratio of
the release strength of concrete to the design strength. Taking into account the short-term nature of dynamic
overloads, the design properties of concrete are multiplied by the service condition factor g = 1.1.
6.56. The sections parallel to the sides of the slab, passing through the axes of the lifting loops or mounting
holes, as well as those in which the shear force values are equal to zero, are checked for assembly effects. The
bending moments in the specified sections are determined from the condition of equilibrium of external and
internal forces according to the formulas for the strength of materials for statically determinate bar systems.
The bending moment per unit width of the section is determined by the formula
m = Mg / b , (250)
where M , in N×m, is the bending moment from the assembly effects, acting in the section of width b ; g is the
coefficient of non-uniformity of the distribution of the bending moment across the width of the section, taking into
account the plastic redistribution of stresses.
When the section in which the shear force is equal to zero is located at a distance greater than 0.4 of the distance
between the nearest loops or mounting holes to the axis of these loops (or holes), the coefficient g is taken equal
to 1.2 for cracking calculations, and 1 for calculating the required reinforcement. In other cases, the coefficient g
is taken equal to 1.4 and 1.2, respectively.
6.57. Slabs up to 2 m wide, lifted by 4 loops with an unbalancing crossbeam, are considered suspended only
from any two loops located diagonally.
When calculating such slabs for installation effects, the need for installation and the cross-section of the upper
transverse reinforcement with respect to the span are checked.
Upper reinforcement is not provided if the condition
M ³ 0.175 Gb , (251)
where M , kN/m ¾ bending moment in the longitudinal section of the slab, at which the stresses in the upper
tension zone of the concrete reach the value of the design tensile resistance R taking into account the ratio of
the release and design strength of concrete; G , kN — assembly weight of the slab, multiplied by the dynamic
coefficient of 1.4; b , m ¾ width of the slab.
For slabs of solid section, condition (251) can be written as
R ³ 0.6 Gb (252)
where l and h are the length and thickness of the slab, respectively.
If condition (251) is not met, the upper transverse reinforcement, distributed along the length of the element, is
selected based on the condition of receiving a bending moment
M ³ 0.15 Gb. (253)
6.58. Slabs lifted from 6 points using a crossbeam that ensures equal forces in all slings are calculated assuming
equal vertical components of the forces applied to the lifting loops or openings. For the average cross-section, the
vertical components of the forces applied to the middle pair of loops (or openings) are taken with a coefficient of
1.2, and the vertical components of the forces applied at the remaining four points are taken with a coefficient of
0.9.
6.59. In cases where, for technological or structural reasons, lifting loops are installed along the side faces of the
slabs, at least 50% of the upper design reinforcement must be located in the zone of tensile stress concentration
in the immediate vicinity of the loops.
To prevent the loops from being pulled out of the plane of the panels at the edge of the loop niche in the concrete,
anchor loops must be provided, equipped at the bending points with anchor rods of a periodic profile, with a
diameter not less than the diameter of the lifting loop. Anchor loops are made of grade AI steel, and their cross-
section is calculated for the assembly force acting on the loop, with a dynamic coefficient of 1.4 (excluding the
decomposition of the force along both branches of the anchor loop).
6.60. In order to approximate the nature of the slab's operation during lifting to the nature of the operation when
supported on four sides, it is also recommended to place the lifting loops on four sides: in the middle of the short
sides and 1/3 from the edges of the long sides (Fig. 52).
The values of the bending moment during lifting per unit width of the slab, in this case, should be determined by
the formula
m = Gb , (254)
where b is a dimensionless coefficient adopted for various points of the slab according to Table 16, depending on
the ratio of the sides of the slab l = l / l .
Table 16
 Coefficient b for a slab lifted by six lifting loops (Fig. 52) when determining bending forces
l = l / l in the transverse direction at points in the longitudinal direction at points
b2
crc,lon
crc,lon
bt
bt
2 1
2 1
 A C B C
1.0 -0.0188 0.0693 -0.0572 0.0278
1.1 -0.0232 0.0657 -0.0567 0.0258
1.2 -0.0277 0.0625 -0.0562 0.0245
1.3 -0.0325 0.0598 -0.0558 0.0240
1.4 -0.0375 0.0575 -0.0555 0.0242
1.5 -0.0427 0.0555 -0.0553 0.0247
1.6 -0.0482 0.0537 -0.0053 0.0255
1.7 -0.0538 0.0520 -0.0553 0.0267
1.8 -0.0597 0.0505 -0.0553 0.0280
1.9 -0.0657 0.0491 -0.0555 0.0293
2.0 -0.0718 0.0478 -0.0556 0.0307
2.1 -0.0780 0.0465 -0.0558 0.0320
2.2 -0.0843 0.0453 -0.0560 0.0332
2.3 -0.907 0.0441 -0.0562 0.0343
2.4 -0.0972 0.0430 -0.0563 0.0353
2.5 -0.1036 0.0418 -0.0565 0.0363
Note. A negative value of the coefficient means that the upper zone of the slab is stretched.
The cross-section of the upper reinforcement, designed to withstand tensile forces at points A and B (see Fig.
52), should be determined based on the values of the bending moments at these points, assuming that the width
of the cross-section is equal to 0.1 of the slab width (smaller than its span). All this reinforcement should be
concentrated in the immediate vicinity of the hole or niche in which the lifting loop is installed. The length of the
rods of this reinforcement should be equal to 100 of its diameters, at least 800 mm (50 d or 400 on both sides of
the loop axis, d is the loop diameter).
Fig. 52. Placement of lifting loops in a slab supported on walls along the contour
a — symmetrical slab, b — asymmetrical slab (with balcony); c — symmetrical slab 4.2 m long or less; A, B, C —
points at which the forces are determined; e ¾ distance between the centers of gravity of the load-bearing part of
the entire complex panel.
In the case of asymmetric slabs with balconies and base slabs of a separate (floating) floor, the lifting loop
located on the balcony side is recommended to be shifted towards the center of gravity of the product by a value
of 6 e (Fig. 52, c ). This method achieves centering of the slab and partial use of the load-bearing capacity of the
balcony console during installation. The specified slabs may be calculated using formula (254), taking into
account their full length.
In slabs supported along the contour with a length of no more than 4.2 m, it